Panasonic PRO-HT Tank Series Technical Manual page 84

Table of Contents

Advertisement

How to make Settings
!
i
9
82
Important
All settings are necessary, otherwise faultless operation is not possible. Please follow the se-
quence described above!
M PAW-VP380L – U-200PZH2E8 (PACi R32)
Indoor Unit Tank detailed settings; Remote controller CZ-RTC5B
Parameter
Default
"DN" code
value
10
0006
11
0015
06
0004
0b
0002
0C
0000
0d
0000
15
0022
16
0000
1F
0000
20
0000
21
0030
22
0018
28
0001
2C
0000
2d
0008
Note
"DN" codes 10 & 11 must be set first.
"DN" 15 display temperature sensor TA, E1, E2, E3*, BL* change 0022 -> 0031
* to be purchased separately
Outdoor unit detailed settings by CZ-RTC2/4
Parameter
Default
"DN" code
value
7
000
42
002
4b
001
35
000
36
000
A5
000
New value
Explanation
to set
0031
Unit Type
0021
Capacity code
0000
Inlet temperature shift in heating mode.
0001
EXCT setting
0001
Heating preparation display
0001
Cool/ Heat auto
0022
Temperature sensors
0000
Fan speed adjustment
0015
Cooling upper limit 15°C
0005
Cooling lower limit 5°C
0055
Heating upper limit 55°C
0035
Heating lower limit 35°C
0001
Automatic restart after power failure activated
0006
Expansion valve setting
0010
Operation mode Cooling and Heating
New value
Explanation
to set
001
Specific tank setting
000
Tank offset
001
Specific tank setting
Condensation temperature minimum shift in
005
heating
Condensation temperature maximum shift in
005
heating
-04
Frost adherence temperature
Check and adjust
Check and adjust
PAW-VP•LDHW - Technical Manual – 2020-07