Advertisement
This guide provides basic guidelines for Rosemount 3051 Pressure Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (IS) installations. Refer to the Rosemount 3051 Manual for more instructions. This guide is also available electronically at Emerson.com.
Confirm HART® revision capability
Rosemount 3051 device revisions and drivers
Table 2-1 provides the information necessary to ensure you have the correct device driver and documentation for your device.
Table 2-1: Rosemount 3051 with 4-20 mA HART® protocol device revisions and files
Release date | Device identification | Device driver identification | Review instructions | Review functionality | |||
NAMUR hardware revision (1) | (1) | HART software revision (2) | HART universal revision | Device revision (3) | Rosemount 2088, 2090P, and 2090F pressure transmitters | Change description | |
Aug-16 | 1.1.xx | 1.0.xx | 3 | 7 | 10 | with HART and 1–5 Vdc Low Power Protocol Reference Manual | (4) |
5 | 9 | ||||||
Jan-13 | N/A | 1.0.xx | 1 | 7 | 10 | (5) | |
5 | 9 | ||||||
Jan-98 | N/A | N/A | 178 | 5 | 3 | with 4–20 mA HART and 1–5 Vdc Low Power Protocol Reference Manual | N/A |
Procedure
Procedure
Procedure
Figure 3-4: Panel and pipe mounting
If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow the assembly guidelines to ensure a tight seal for optimal performance. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 3-5 illustrates common transmitter assemblies with the required bolt lengths.
Figure 3-5: Common transmitter assemblies
Bolts are typically Carbon Steel (CS) or Stainless Steel (SST). Confirm the material by viewing the markings on the head of the bolt and referencing Table 3-1. If bolt material is not shown in Table 3-1, contact a local Emerson representative for more information.
Table 3-1: Torque values for the flange and flange adapter bolts
Bolt material | Head markings | Initial torque | Final torque | ||
CS | ![]() | 300 in-lb | 650 in-lb | ||
SST | ![]() | 150 in-lb | 300 in-lb |
CS bolts do not require lubrication, and SST bolts are coated with a lubricant to ease installation. When installing either type of bolt, do not apply additional lubricant.
Procedure
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 3-6)
Figure 3-6: In-line Gage Low Side Pressure Port
Mounting the transmitter so that the process can drain away keeps the vent path free of any obstruction, including but not limited to paint, dust, and lubrication.
To improve field access to wiring or to better view the optional LCD display:
Procedure
(1) Rosemount 3051D original position aligns with "H" side; Rosemount 3051G original position is the opposite side of bracket holes.
Overrotation of housing may cause damage to module communication cable.
Procedure
Figure 3-9: Transmitter Wiring Diagrams (4–20 mA)
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5,000 ft. (1500 m) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051 case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the terminal block.
To wire the transmitter:
Procedure
Figure 3-10: Wiring
Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow Connect the wiring and power up. When the transmitter is properly wired, refer to Figure 3-10 for internal and external transient grounding locations.
Verify the configuration using any HART®-capable configuration tool. Configuration instructions for a Field Communicator are included in this step. See Rosemount 3051 Reference Manual for configuration instructions using AMS Device Manager.
A Rosemount 3051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences for the latest DD are shown in Table 2-2. For Fast Key sequences using legacy DD's, contact your local Emerson representative.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit Field Communicator for information on updating the DD library.
Procedure
Verify device configuration using the Fast Key sequences in Table 2-2.
Function | Fast Key sequence | ||||||
HART® 7 | HART 5 | ||||||
✓ | Alarm and Saturation Levels | 2, 2, 2, 5, 7 | 2, 2, 2, 5, 7 | ||||
✓ | Damping | 2, 2, 1, 1, 5 | 2, 2, 1, 1, 5 | ||||
✓ | Range Values | 2, 2, 2 | 2, 2, 2 | ||||
✓ | Tag | 2, 2, 7, 1, 1 | 2, 2, 7, 1, 1 | ||||
✓ | Transfer Function | 2, 2, 1, 1, 6 | 2, 2, 1, 1, 6 | ||||
✓ | Units | 2, 2, 1, 1, 4 | 2, 2, 1, 1, 4 | ||||
Burst Mode | 2, 2, 5, 3 | 2, 2, 5, 3 | |||||
Custom Display Configuration | 2, 2, 4 | 2, 2, 4 | |||||
Date | 2, 2, 7, 1, 4 | 2, 2, 7, 1, 3 | |||||
Descriptor | 2, 2, 7, 1, 5 | 2, 2, 7, 1, 4 | |||||
Digital to Analog Trim (4–20 mA output) | 3, 4, 2 | 3, 4, 2 | |||||
Disable Configuration Buttons | 2, 2, 6, 3 | 2, 2, 6, 3 | |||||
Rerange with Keypad | 2, 2, 2, 1 | 2, 2, 2, 1 | |||||
Loop Test | 3, 5, 1 | 3, 5, 1 | |||||
Lower Sensor Trim | 3, 4, 1, 2 | 3, 4, 1, 2 | |||||
Message | 2, 2, 7, 1, 6 | 2, 2, 7, 1, 5 | |||||
Scaled D/A Trim (4–20 mA output) | 3, 4, 2 | 3, 4, 2 | |||||
Sensor Temperature/Trend (Rosemount 3051S) | 3, 3, 3 | 3, 3, 3 | |||||
Upper Sensor Trim | 3, 4, 1, 1 | 3, 4, 1, 1 | |||||
Digital Zero Trim | 3, 4, 1, 3 | 3, 4, 1, 3 | |||||
Password | 2, 2, 6, 5 | 2, 2, 6, 4 | |||||
Scaled Variable | 3, 2, 2 | 3, 2, 2 | |||||
HART revision 5 to HART Revision 7 switch | 2, 2, 5, 2, 3 | 2, 2, 5, 2, 3 | |||||
✓ | Long Tag | 2, 2, 7, 1, 2 | N/A | ||||
✓ | Find Device | 3, 4, 5 | N/A | ||||
✓ | Simulate Digital Signal | 3, 4, 5 | N/A |
Note
See Figure 3-11 to confirm external button functionality.
Figure 3-11: Internal and External LOI Buttons
The optional local operator interface (LOI) can be used for commissioning the device. The LOI is a two button design with internal and external buttons. The internal buttons are located on the display of the transmitter, while the external buttons are located underneath the top metal tag. LOI button functionality is shown on the bottom corners of the display.
To activate the LOI, push any button. See Table 3-2 and Figure 3-12 for button operation and menu information.
Table 3-2: LOI Button Operation
Button | ![]() | ![]() |
Left | No | SCROLL |
Right | Yes | ENTER |
Figure 3-12: LOI Menu
If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 3051 will load a generic menu with limited capability. The following procedures will switch the HART revision mode from the generic menu:
Procedure
Manual Setup → Device Information → Identification → Message
Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage and differential pressure transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
For instructions using AMS Device Manager, see the Rosemount 3051 Reference Manual.
Note
When performing a zero trim, ensure that the equalization valve is open and all wet legs are filled to the correct level.
Procedure
Procedure
Analog zero (Set 4 mA) | Digital zero | |
Fast Key sequence | 3, 4, 2 | 3, 4, 1, 3 |
For safety certified installations, refer to the Rosemount 3051 Reference Manual for installation procedure and system requirements.
Explosions
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 3051 Manual for any restrictions associated with a safe installation.
In an explosionproof/flameproof installation, do not remove the transmitter covers when power is applied to the transmitter.
Process leaks
Process leaks may cause harm or result in death.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Entries marked M20 are M20 x 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users' equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental in protecting your system. Restrict physical access by unauthorized personnel to protect end users' assets. This is true for all systems used within the facility.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Emerson Rosemount 3051 - Pressure Transmitter Manual
Advertisement
Need help?
Do you have a question about the Rosemount 3051 and is the answer not in the manual?
Questions and answers