1MRK 506 377-UEN Rev. L
X1Start
IEC15000432 V2 EN-US
Figure 16:
Table 18:
Test point
P1
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
P12
P13
Table continues on next page
Railway application RER670
Commissioning manual
jX(Ohm/phase)
P1
RFPPStart
P16
P 15
P12
P11
RLd
P 10
P9
P8
Proposed test points for phase-to-phase loop of quadrilateral characteristic in
solidly earthed system
Test points for phase-to-phase loop of quadrilateral characteristic in solidly earthed system
R
0
(X1Start / tan(LineAng))
RFPPStart
0.8 ∗ RFPPStart
RLd
RFPPStart
0
-(X1Start / tan(LineAng))
-RFPPStart
-0.8 ∗ RFPPStart
-RLd
-RFPPStart
0.8 ∗ RFPPStart
© 2017 - 2022 Hitachi Energy. All rights reserved
P2
RFPPStart
P3
P4
R(Ohm/phase)
P5
P6
RLd
P 13
P 14
P7
IEC15000432-2-en.vsdx
X
X1Start
X1Start
0.8 ∗ X1Start
0.8 ∗ RFPPStart ∗
tan(ArgLd)
0
0
-X1Start
-X1Start
-0.8 ∗ X1Start
-0.8 ∗ RFPPStart ∗
tan(ArgLd)
0
0
-0.8 ∗ RFPPStart ∗
tan(ArgLd)
Section 10
Testing functionality by secondary injection
Comment
If OpLoadEnch = Off
If OpLoadEnch = Off