Wiring; Caution; Control Box And Connecting Position Of Wiring; Wiring Transmission Cables - Mitsubishi Electric CITY MULTI PUHY-TMU-A Installation Manual

Air-conditioners for building application outdoor unit
Table of Contents

Advertisement

Available languages

Available languages

9. Wiring

9.1. Caution

1 Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric
power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm
[1-31/32 in] or more) apart from power source wiring so that it is not influenced
by electric noise from power source wiring. (Do not insert transmission line
and power source wire in the same conduit.)
3 Be sure to provide designated grounding work to outdoor unit.
4 Give some allowance to wiring for electrical part box of indoor and outdoor
units, because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor trans-
mitting and receiving will cause erroneous operations.
7 Only the transmission line specified should be connected to the terminal block
for outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB3 for
transmission line, Other : Terminal block TB7 for centralized control)
Erroneous connection does not allow the system to operate.
8 In case to connect with the upper class controller or to conduct group opera-
tion in different refrigerant systems, the control line for transmission is required
between the outdoor units each other.
Connect this control line between the terminal blocks for centralized control.
(2-wire line with no polarity)
When conducting group operation in different refrigerant systems without con-
necting to the upper class controller, replace the insertion of the short circuit
connector from CN41 of one outdoor unit to CN40.
9 Group is set by operating the remote controller.
9.2. Control box and connecting position of
wiring
1. Connect the indoor unit transmission line to transmission terminal block (TB3),
or connect the wiring between outdoor units or the wiring with the central con-
trol system to the central control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmis-
sion line to the earth screw (
) and connect shield ground of the line between
outdoor units and the central control system transmission line to the shield (S)
terminal of the central control terminal block (TB7) shield (S) terminal. In addi-
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are
necessary.)
<Examples of Transmission Cable Wiring>
[Fig. 9.3.1] M-NET Remote Controller (P.4)
[Fig. 9.3.2] MA Remote Controller (P.4)
A Group 1
B Group 3
( ) Address
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals A and B and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2 and
terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).
d. Connect together terminals A, B and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40.
f.
Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which the jumper connector was inserted into CN40 in Step
above to the ground terminal
g. Set the address setting switch as follows.
*
To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.
Unit
Range
IC (Main)
01 to 50
IC (Sub)
01 to 50
Outdoor Unit
51 to 100
M-NET R/C (Main)
101 to 150
M-NET R/C (Sub)
151 to 200
MA R/C
10
C Group 5
in the electrical component box.
Use the most recent address within the same group of indoor units
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)
Use the most recent address of all the indoor units plus 50
Set at an IC (Main) address within the same group plus 100
Set at an IC (Main) address within the same group plus 150
Unnecessary address setting (Necessary main/sub setting)
tion, in the case of outdoor units whose power supply connector CN41 has
been replaced by CN40, the shield terminal (S) of terminal block (TB7) of the
central control system should also be connected to the ground (
[Fig. 9.2.1] (P.4)
A Power source
2. Conduit mounting plates (ø27 [1-3/32 in], ø33 [1-5/16 in]) are being provided.
When installing wiring, always ensure that the appropriate conduit mounting
plate in the table below is fitted in the knock-out hole. Note: In the case of
wiring from below or in front, the conduit mounting plate may be fitted without
further modification, however mounting holes must be drilled when installing
wiring from the side.
Pass the power supply and transmission wires through the appropriate knock-
out holes, then remove the knock-out piece from the bottom of the terminal box
and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile
force (PG connection or the like).
Model
PUHY-80TMU-A
PUHY-100TMU-A

9.3. Wiring transmission cables

1 Types of control cables
1. Wiring transmission cables
Types of transmission cables: Shielding wire CVVS or CPEVS
Cable diameter: More than 1.25 mm
Maximum wiring length: Within 200 m [655 ft]
2. Remote control cables
Kind of remote control cable
Cable diameter
Remarks
2 Wiring examples
Controller name, symbol and allowable number of controllers.
Name
Symbol
Outdoor unit controller
Indoor Unit Controller
Remote Controller
D Shielded Wire
E Sub Remote Controller
Setting Method
B Transmission line
(Unit: mm [in])
Hole size of plate
ø27 [1-3/32]
ø33 [1-5/16]
2
[AWG 16]
2-core cable (unshielded)
2
0.3 to 1.25 mm
[AWG 22 to 16]
When 10 m [30 ft] is exceeded, use cable with
the same specifications as (1) Transmission line
wiring
Allowable number of controllers
OC
IC
Two to ten controllers for one OC
RC
Maximum of two per group
).

Advertisement

Table of Contents
loading

This manual is also suitable for:

City multi puhy-80tmu-aCity multi puhy-100tmu-a

Table of Contents