Extinguishing Terminal Installation And Wiring; Description - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Mounting and installing extinguishing control panels
6

Extinguishing terminal installation and wiring

6.4 Extinguishing terminal installation and wiring

6.4.1 Description

72 | 248
Building Technologies
Fire Safety
The extinguishing terminal XTO2001 is used for the indication and operating
functions of the extinguishing card. It is part of the operating add-ons for
extinguishing control panels and of the remote control panel. Every flooding zone
has its own extinguishing terminal. The extinguishing terminal can be used as a
primary Person Machine Interface installed in an extinguishing control panel or
separately as a secondary Person Machine Interface in its own housing. The
primary extinguishing terminal must always be present and, if possible, integrated
into the control panel. The secondary extinguishing terminal is generally installed
externally and is an additional terminal with full functionality.
The extinguishing terminal XTO2001 is used in the following components:
Exting. terminal (1 sector) XCM2002-A2
Exting. terminal (4 sectors) XCM2003-A2
Extinguish. terminal (remote) XT2001-A2
Properties
Supply via the extinguishing control panel
Separate supply as secondary (remote) extinguishing terminal possible
With a separate supply, monitoring for power loss, battery fault, and ground
fault
Connection of a 3rd source of voltage [FR] possible
Addressable via DIP switch
6 freely programmable 3-color LED indicators
28 permanently assigned 3-color LED indicators
4 dot matrix displays (5 x 7) for countdown display
10 operating buttons, 4 of which are freely programmable
Prepared for the installation of a key switch
A6V10210390_m_en_--
2018-08-29

Advertisement

Table of Contents
loading

Table of Contents