≥500mm
≥500mm
For proper air circula�on to dissipate heat, allow a clearance of approx. 50cm to the side and
approx. 50cm above and below the unit. And 100cm to the front.
Moun�ng the inverter
Remember that this inverter is heavy! Please be careful when li�ing out from the package.
Choose the recommend drill head(as shown in below pic) to drill 4 holes on the wall,
62-70mm deep.
1. Use a proper hammer to fit the expansion bolt into the holes.
2. Carry the inverter and holding it, make sure the hanger aim at the expansion bolt,fix the
inverter on the wall.
3. Fasten the screw head of the expansion bolt to finish the moun�ng.
Inverter hanging plate installa�on
- 07 -

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUN-50K-SG01HP3-EU-BM4 and is the answer not in the manual?

Questions and answers

سالم عمر سعيد كعدور
February 12, 2025

الانفرتر لايستحيب الشحن من الكهرئبه العامة ثلاثي الاطوار

1 comments:
Mr. Anderson
February 12, 2025

The Deye SUN-50K-SG01HP3-EU-BM4 inverter may not be responding to charging from the three-phase power supply due to several possible reasons:

1. Insufficient Ventilation – If the inverter is not properly ventilated, it may overheat and prevent charging.
2. Incorrect Use or Operation – Improper configuration or installation could prevent the inverter from functioning correctly.
3. Failure to Comply with Safety Standards – If the system is not installed according to regulations, it may not operate as expected.
4. Damage from External Factors – Natural disasters, overvoltage, or electrical surges could have affected the inverter.
5. Battery Configuration Issues – The inverter supports lithium-ion batteries with a voltage range of 160-800V. Incorrect battery settings or connections may prevent charging.
6. Communication Failure – If the CAN or RS485 communication ports are not properly connected to the battery management system (BMS), the inverter may not charge.
7. Incorrect Priority Settings – If the charging priority is set incorrectly via the LCD settings, it may not charge from the three-phase supply.
8. Protection Mechanisms Activated – Built-in protections against overload, over-temperature, or short circuits may be preventing charging.

Checking battery connections, communication ports, ventilation, and configuration settings should help identify and resolve the issue.