Section 6
Wide area measurement system
IEC140000118 V2 EN-US
Figure 32:
Figure
33
in the bottom of each function block. For each instance, there are four separate PHASORREPORT
blocks including 32 configurable phasor channels (8 phasor channels in each PHASORREPORT block).
Each phasor channel can be configured as a 3-phase (symmetrical components positive/negative/zero)
or single-phase phasor (A/B/C).
IEC140000119 V2 EN-US
Figure 33:
Figure
34
the bottom of each function block. For each instance, there are three separate ANALOGREPORT blocks
capable of reporting up to 24 Analog signals (8 Analog signals in each ANALOGREPORT block). These
can include for example transfer of active and reactive power or reporting the milliampere input signals to
the PDC clients as defined in IEEE IEC/IEEE 60255-118 (C37.118) data frame format.
IEC140000120 V2 EN-US
Figure 34:
78
Multiple instances of PMUREPORT function block
shows both instances of the PHASORREPORT function blocks. The instance number is visible
Multiple instances of PHASORREPORT blocks
shows both instances of ANALOGREPORT function blocks. The instance number is visible in
Multiple instances of ANALOGREPORT blocks
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC140000118-2-en.vsd
IEC140000119-2-en.vsd
IEC140000120-2-en.vsd
Phasor measurement unit RES670
1MRK511407-UUS Rev. N
Application manual