Section 14
Control
14.3.3
Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
14.4
Single point generic control 8 signals SPC8GAPC
14.4.1
Identification
Function description
Single point generic control 8 signals
14.4.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single point
commands that can be used for direct commands for example reset of LED's or putting IED in
"ChangeLock" state from remote. In this way, simple commands can be sent directly to the IED outputs,
without confirmation. Confirmation (status) of the result of the commands is supposed to be achieved by
other means, such as binary inputs and SPGAPC function blocks.
14.4.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via the local
HMI or PCM600.
Operation: turning the function operation Enabled/Disabled.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) or Pulsed.
tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (in seconds).
14.5
AutomationBits, command function for DNP3.0
AUTOBITS
200
IEC 61850
identification
SPC8GAPC
PSTO is the universal operator place selector for all control functions. Even if PSTO can be
configured to allow LOCAL or ALL operator positions, the only functional position usable with
the SPC8GAPC function block is REMOTE.
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Phasor measurement unit RES670
1MRK511407-UUS Rev. N
SEMOD55398-5 v5
SEMOD176448-1 v3
SEMOD176456-2 v3
SEMOD176511-4 v7
SEMOD176518-4 v7
SEMOD158589-1 v3
Application manual