Panasonic U-10MF1E8 Service Manual page 43

3-way system
Hide thumbs Also See for U-10MF1E8:
Table of Contents

Advertisement

19. Other Functions
(3) Outdoor unit PCB LED indications in judgment mode
Judgment mode
Normal
Insuffi cient gas
Overcharge
Judgment not
possible
When judgment mode is not engaged, the LED indicates the normal display (OFF), or else indicates alarms or
other information.
If the insufficient gas or overcharge judgment is not stable, then recover refrigerant a little at a time when the
overcharge display appears. End refrigerant adjustment when the normal or insufficient gas display appears.
(4) Canceling judgment mode
When judgment mode is cancelled, the LED returns to the standard status display (OFF unless an alarm or
other event has occurred).
[1] Automatic cancel
Judgment mode is canceled automatically when 4 hours have passed after it was started.
[2] Forced cancel
Short-circuit the CHECK pin while the judgment mode display is active in order to cancel judgment mode.
<Reference> General Guidelines for Insufficient Gas and Overcharge
Judgment in automatic judgment mode can be problematic in some cases. Therefore, the following guidelines
are provided for general judgment of the refrigerant amount.
• Symptoms of insufficient gas
Cooling
There is an indoor unit where the position of the electronic control valve is much higher (open by
operation
300 pulses or more) than it was at start, and the difference [E3 – E1] at that indoor unit is large
(15°C or more).
Heating
There is an outdoor unit where the position of the electronic control valve is much higher (open by
operation
300 pulses or more) than it was at start, and the difference [Liquid temp. – Gas temp.] at that
outdoor unit is large (15°C or more).
• Symptoms of overcharge
Cooling
The high-pressure sensor temperature is 57°C or higher, and the difference [Pressure sensor
operation
temp. – Liquid temp.] at that outdoor unit is large (15°C or more).
Heating
There is an indoor unit where the position of the electronic control valve is much higher (open by
operation
300 pulses or more) than it was at start, and the difference [Pressure sensor temp. – E3] at that
indoor unit is large (25°C or more).
These are only guidelines, therefore the judgment may vary depending on the installation conditions, load
characteristics, and other elements.
LED1
LED2
Blinking
Blinking
ON
ON
Blinking
OFF
OFF
Blinking
Blinking
alternately
Recommended response
Charge with refrigerant a little at a time.
Recover refrigerant a little at a time.
1 - 37
3-WAY SYSTEM