4. 3-WAY Alarm Codes
F08 Alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
F12 Alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
5
F08
Outdoor air temperature sensor trouble
(1) A/D step is 10 steps or less (short circuit).
(2) A/D step is 1014 steps or more (open circuit)
(1) Sensor malfunction (including connector)
(2) PCB malfunction
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
F12
Compressor intake temperature sensor trouble
(1) A/D step is 10 steps or less (short circuit).
(2) A/D step is 1014 steps or more (open circuit)
(1) Sensor malfunction (including connector)
(2) PCB malfunction
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
5 - 14
3-WAY SYSTEM
Trouble Diagnosis