1MRK505382-UEN Rev. K
LOCAL
IEC07000157 V1 EN-US
Figure 81:
IED
Transceiver 21–219
SDH MUX
Both line differential protection IEDs are set as slaves.
5.6.4
Setting up transceiver 21–219
IEC07000245 V1 EN-US
Figure 82:
Communication set-up, 670/650 series
Application Guide
< 10 m
SDH
IED
Transceiver
MUX
21-219
Multi-mode
fibre-optic
< 3.5 km Galvanic
connection
interface
G.703 E1
(2Mbit)
Slave
21-219
master
Communication structure with PDH/SDH port synchronized from transceiver
21-219
Terminal used for binary signal transfer
Optical-to-electrical interface converter
SDH multiplexer
Transceiver 21–219 parts
© 2017 - 2023 Hitachi Energy. All rights reserved
< 10 m
SDH
Transceiver
MUX
21-219
Galvanic
connection
interface
G.703 E1
(2Mbit)
Slaves (external clock)
Transparent
Communication set-up
REMOTE
IED
Multi-mode
fibre-optic
< 3.5 km
IEC07000157-1-en.vsdx
GUID-8020026C-EFF7-48BD-973C-7AC7573F1A22 v1
IEC07000245-1-en.vsdx
Section 5
81