Line Differential Protection L4Cpdif; Setting Example With A Two-End Power Line - Hitachi 670 Series Application Manual

Hide thumbs Also See for 670 Series:
Table of Contents

Advertisement

1MRK505382-UEN Rev. K
Settings
PDIF
NoOfUsedCTs
TraAOnInpCh
TraBOnInpCh
Currents from the secondary and tertiary windings of the power transformer are connected to one
line differential protection IED. Currents for each CT group are sent to the IED at station A by the
LDCM. To inform the differential algorithm that currents are coming from the LV sides of the
transformers, TraAOnInpCh must be set to 2 and TraBOnInpCh to 3 (channel1 is reserved for local
measurement). This is to ensure that proper turn ratio and vector group correction is done.
4.7.2

Line differential protection L4CPDIF

4.7.2.1

Setting example with a two-end power line

In this example, a two-end 220 kV and 200 km power line is protected using L4CPDIF.
The protected zone is determined by CT positions. One three-phase CT group is placed at one end
of the power line, and another three-phase CT group is placed at the other end. Everything that is
placed between these two CT groups (including CBs) are included in the protected zone.
To apply the exact (voltage-based) method of charging current compensation, the power line's
positive and zero-sequence capacitances must be known. If not known, the approximate method can
be applied instead.
Table
4
Table 4:
Power system parameters
Power line data
Number of three-phase CT groups
(each group represents an
independent source of information
about the current)
Source impedance at both ends
Power line length
Rated voltage
Line impedance ZL ≈ XL
Total zero sequence line
capacitance, C0
Total positive sequence line
capacitance, C1
Charging current
(measured without charging current
compensation)
Rated current
Table
5
Communication set-up, 670/650 series
Application Guide
Station A
L3TCPDIF
3
2
3
shows the power system parameters in this example.
Value
2
4.84 Ω
200 km
220 kV
58.64 Ω
7.751e-9 x 200
12.74e-9 x 200
92 A
1000 A
shows the relevant settings in this example.
© 2017 - 2023 Hitachi Energy. All rights reserved
Analog and binary signal transfer for line differential protection
Station B
L3TCPDIF
3
1
2
Remark
A two-end power line with one three-phase CT group installed at each
end.
Setting NoOfUsedCTs is used to indicate to L4CPDIF how many current
input channels (2, 3 or 4) with current samples are to be read and
processed.
-
-
-
-
7.751e-9 F per 1 km of line
12.74e-9 F per 1 km of line
Measured at rated voltage as the differential current under normal load.
Section 4
GUID-4C105C98-F9FE-41B3-A7E0-FC5430EC141A v2