Maintenance Events - Siemens SIMATIC ET 200eco PN M12-L Equipment Manual

Communications module
Hide thumbs Also See for SIMATIC ET 200eco PN M12-L:
Table of Contents

Advertisement

PROFINET IO
5.2 Interrupts/diagnostics alarms
5.2.3.2

Maintenance events

Maintenance event for IO-Link master
All IO-Link events of the type Warning generated by the IO-Link device or port are mapped to
the PROFINET diagnostics alarm of the type "Maintenance" of the assigned submodule. The
aim is the early detection and elimination of potential faults.
For the IO-Link master, maintenance events signal to the user when a network component
must be checked or replaced.
Example of displaying the IO-Link event codes:
An IO-Link device generates EventCode 0x8CA0
The channel diagnostics results from the event code:
• PROFINET channel diagnostics type: Maintenance CET: 0x9501
Maintenance "IO-Link Device Diagnostics - Page 2, Ambient light interference", generated
from the IO-Link event code 0x8CA0
Maintenance event for DIQ and for IO-Link master
The MultiFieldbus interfaces of the ET 200eco PN M12-L support the diagnostics concept and
maintenance concept in PROFINET according to the IEC 61158-6-10 standard. The goal is to
detect and remove potential problems as early as possible.
The I/O device signals a maintenance event to the higher-level diagnostic system on the
following event:
Table 5- 9
Maintenance alarm
Maintenance demanded
(maintenance demanded)
MT/IO LED is lit
The maintenance information is generated in STEP 7 with the following system alarms:
• Maintenance demanded - indicated for each port by a yellow wrench icon
device view or in the hardware configuration.
You can find more information in the STEP 7 online help.
46
Triggering of a maintenance event
Error code Event
2
H
CM 8x IO-Link + DIQ 8x24VDC M12-L 8xM12 (6ES7148-6JJ00-0BB0) communications module
(type "Warning")
H
.
H
Meaning
Undervolt-
Supply voltage 1L+ is below the toler-
age
ance limit.
Equipment Manual, 12/2022, A5E51718265-AB
.
, ECET: 0x0CA0
.
H
H
in the

Advertisement