Introduction to the SCO Section 1 – Introduction to the SCO The SCO it is a control and protection panel used for generating sets; it shows the settings measured on its displays. The Unit is designed for easy use, for both installer and end-user alike. Remote control The SCO controller can be remotely controlled.
Section 2 – Technical data Technical Data Power supply SCO 5 SCO 10 SCO 11 Voltage supply 8 V to 36 V DC 8 V to 36 V DC 8 V to 36 V DC 60 mA to 12V DC...
Then, it is necessary to connect male connector (engine installation wire) to female connector (SCO 5). 3.2. SCO 10 and SCO 11 panel installation The controller must be mounted onto the switchboard door. Requested cutout size is: SCO 10: 175 mm x 115 mm.
SCO 5 panel operation Section 4 – SCO 5 panel operation 4.1. Buttons and indicators POSITION BUTTON DESCRIPTION Graphic B/W display. 128 x 64 pixels. Alarm red LED. The LED will blink when there is one or more active warning or active shutdown alarm.
SCO 5 panel operation 4.2. Display screens and page’s structure The displayed information is structured into "pages" and "screens". Use buttons ▲ or ▼ to change the screen page. Voltage (V) Power (kW) Frequency (Hz) Operation hours Engine speed (RPM) Voltage between pahses (V) Frequency (Hz) L1 Current (A)
SCO 5 panel operation Oil pressure (Bar) Coolant temperature (ºC) Fuel level* (%) Battery voltage (V) Total power (kWh) Total R power (kVarh) Alarms, events and history Return to the main screen 4.3. Alarms, Events and History The folowing list shows the type of events and alarms that may appear in the history. Events Warnings Shutdowns...
SCO 5 panel operation A symbol corresponding to an event appears on the display followed by a number that indicates the total number of hours of the engine in which the event occurred. 4.3.1. Events list SYMBOL DESCRIPTION Manual start: Engine was manually started by pressing button START in Manual mode.
SCO 5 panel operation 4.3.2. Warnings list Active warning: When a warning occurs, O04 Alarm and O15 Common Warning outputs will close and the red LED above STOP button will blink. Warning symbol will blink in the upper-right corner of the LCD and the proper warning symbol will be displayed in the history with running hours stamp. Active warning can’t be confirmed.
Page 13
SCO 5 panel operation Binary inputs (Negative signal “-”): Low oil pressure (I13) Remote Start/Stop or Exhaust temperature (I12) * High coolant temperature (I08) Emergency stop (I04) Binary outputs (Positive signal “+”): Buzzer (O10) Preheating (O05) Fuel feed pump (O07) Stop solenoid (O06) Starter (O05) Analog inputs:...
Page 14
SCO 5 panel operation SYMBOL DESCRIPTION Emergency stop: the binary input (IO4) is activated. Overspeed: The protection comes active if the speed is greater than 120 % of nominal engine RPM. Actual speed value is derived from genset frequency or is sensed directly using magnetic pick-up input. Underspeed: Low engine RPM.
Page 15
SCO 5 panel operation SYMBOL DESCRIPTION Generator Overfrequency: The genset frequency is out of limits given by setpoints G03 Generator Overfrequency Shutdown and G04 Generator Underfrequency Shutdown. Generator Underfrequency: The genset frequency is out of limits given by setpoints G03 Generator Overfrequency Shutdown and G04 Generator Underfrequency Shutdown.
SCO 5 panel operation 4.4. Connections description Code Terminal Signal type Description Color Analog input Oil pressure sensor Brown Analog input Coolant temperature sensor Grey Binary input Oil pressure switch Blue Binary input Exhaust temperature switch* Purple Black Binary output Alarm No wired Binary output...
SCO 10 panel operation Section 5 – SCO 10 panel operation 5.1. Buttons and indicators GENSET CONTROL BUTTONS POSITION BUTTON DESCRIPTION START button. Works in MAN mode only. Press this button to initiate the start sequence of the engine. STOP button. Works in MAN mode only. Press this button to initiate the stop sequence of the genset.
Page 18
SCO 10 panel operation POSITION BUTTON DESCRIPTION MODE LEFT button. Use this button to change the mode. The button works only if the main screen with the indicator of currently selected mode is displayed. Note: This button will not work if the controller mode is forced by one of the binary inputs Remote OFF, Remote MAN, Remote AUT.
SCO 10 panel operation 5.2. Display screens and pages structure The displayed information is structured into "pages" and "screens". Use PAGE button to switch over the pages. 1. The Measurement page consists of screens which display measured values like voltages, current, oil pressure etc., computed values like genset power, statistic data and the alarm list on the last screen.
Page 20
SCO 10 panel operation Binary Inputs – Binary signals from the genset to control panel. BI1: Remote control – Start or Stop • • BI2: Alarm / Temperature switch (shutdown) • BI3: Emergency STOP. • BI4: Alarm / Pressure switch •...
SCO 10 panel operation 5.2.2. Setpoint. Controller information screen Enter Page Hold the ENTER and PAGE button at the Page same time. Page Page Enter If the panel is more than 5 seconds in a screen, it returns to initial screen automatically. In this case, you must begin all the procedure again.
SCO 10 panel operation 5.2.3. Setpoint. Maintenance hours change When the following warning appears in the Alarm list screen of SCO 10: First of all you must carry out the maintenance tasks according to the Maintenance task table, attached in the end. You also can consult this information in the Warranty manual.
SCO 10 panel operation 5.2.5. Alarms list Fault Reset Active unconfirmed alarm Active confirmed alarm Alarm desactivation 5.2.6. Display contrast adjustment Enter Enter Hold ENTER button and, ↑ or ↓at the same time. Solé, S.A. C-243 b, km 2 · 08760 Martorell (Barcelona) ·Tel. +34 93 775 14 00 · www.solediesel.com · info@solediesel.com Operator’s manual.
SCO 10 panel operation 5.2.7. Change language If the panel is more than 5 seconds in a screen, it returns You must follow these steps to change the panel language. to initial screen automatically. In this case, you must begin all the procedure again.
SCO 10 panel operation 5.3. Alarm management The following alarms are available: • Breaker open and cooling (BOC) • Warning • Shut down 5.3.1. Breaker open and cooling (BOC) When the control panel detects a problem related to the alternator. The panel stops the genset gradually.
SCO 10 panel operation 5.4. Genset operation states 5.4.1. Engine status list Init Autotest during controller power on Not ready Genset is not ready to start Prestart Prestart sequence in process, Prestart output is closed Cranking Engine is cranking Pause Pause between start attempts Starting Starting speed is reached and the Idle timer is running...
Page 28
SCO 10 panel operation Configurable Warning/BOC/Shutdown alarms on the inputs of IL-NT. IOM Bin Inp CONFIG. Configurable Warning/BOC/Shutdown alarms on the IL-NT-BIO8 CONFIG inputs of IG-IOM/IGS-PTM. ActCallCH1Fail Active call on channel 1 failed. ActCallCH2Fail Active call on channel 2 failed. RTC backup battery is flat BackupBatt ChargeAlt Fail...
Page 29
SCO 10 panel operation Shutdown alarm in case of lost connection to IG- Sd IOM Fail IOM/IGS-PTM module. Warning alarm in case of lost connection to IGL- Wrn RA15 Fail RA15 module. Wrong checksum of parameters. Happens typically after downloading new firmware or changing of the ParamFail parameter.
SCO 11 panel operation Section 6 – SCO 11 panel operation 6.1. Buttons and indicators GENSET CONTROL BUTTONS POSITION BUTTON DESCRIPTION START button. Works in MAN mode only. Press this button to initiate the start sequence of the engine. STOP button. Works in MAN mode only. Press this button to initiate the stop sequence of the genset.
Page 31
SCO 11 panel operation POSITION BUTTON DESCRIPTION MODE LEFT button. Use this button to change the mode. The button works only if the main screen with the indicator of currently selected mode is displayed. Note: This button will not work if the controller mode is forced by one of the binary inputs Remote OFF, Remote MAN, Remote AUT.
SCO 11 panel operation Light mode 6.2. Display screens and page’s structure The displayed information is structured into "pages" and "screens". Use PAGE button to switch over the pages. 4. The Measurement page consists of screens which display measured values like voltages, current, oil pressure etc., computed values like genset power, statistic data and the alarm...
Page 33
SCO 11 panel operation • Voltage between phases and neutral • Voltage between different phases • Genset frequency • Electric current / Phase current* *Para poder visualizar estos valores es necesario tener instalado el Pack Amperométrico. • Oil pressure •...
Page 34
SCO 11 panel operation • BI1: Alarm / Temperature switch. • BI2: Exhaust gas temperatura*. • BI3: Alarm / Pressure switch. • BI4: Remote control – Start / Stop. • BI5: Sd Override. • BI6: Delta Configuration. • E-Stop. Binary outputs – Binary outputs from the control panel to the genset.
SCO 11 panel operation • The left column shows the active power of each pase and total current (if the amperometric kit is installed). • The middle column shows the power factor of each pase and total (if the amperometric kit is installed).
SCO 11 panel operation 6.2.6. Display contrast adjustment Hold ENTER and UP or DOWN at the same time. If the panel is more than 5 seconds in a screen, it returns to initial screen automatically. In this case, you must begin all the procedure again.
Wrong phase sequence There is a fix defined phase sequence in SCO 11 controller L1, L2, L3. When the phases are connected in different order (e.g. L1, L3, L2 or L2, L1, L3) the following alarms are detected: Solé, S.A.
SCO 11 panel operation ALI Gen Ph Rotation Opposite = wrong genset phase sequence. Hint: Phase sequence detection is active when voltage in all three phases is >50VAC and all phases’ angles are in the range 120° ± 20. Phase sequence alarm detection is 1 sec delayed avoiding transient effects.
Page 42
SCO 11 panel operation Failed genset start. SD Start Fail Failure of alternator for charging the battery. Wrn Charging Alternator Fail This alarm informs the operator that the supply Wrn Battery <>Voltatge voltage to the controller is too high or too low.
SCO 11 panel operation 6.5. Connections description Code Terminal Tipo de señal Description Color Analog Input Oil pressure sensor Brown Analog Input Coolant temperatura sensor Grey Analog Input Black Binary Input Coolant temperatura switch White Binary Input Exhaust temperatura switch...
Optional equipment Section 8 – Optional equipment 8.1. Panel SCO 5 / Panel SCO 10 / SCO 11 Amperometric Pack In order to measure the phase current, it is necessary to install the Amperometric Pack, supplied as an option. The necessary toroidal transformers are included in each pack and must be suitable for each genset set model.
Optional equipment 8.3. SCO 10 Third Panel Kit The third panel kit consists of two remote SCO 10 panel, three communication cards (one for each panel) and a communication wire. To install the remotes panels, first connect the communication wires between the main SCO 10 panel and the remotes SCO 10 panel as shown below.
To install the remote panel, first the communication cable must be connected between the main SCO 11 panel and the remote SCO 11 panel as shown below. It should be noted that the black- coloured wire of the communication cable at the remote SCO 11 end must be connected to ground.
(red wire to the positive and black wire to the negative of the source). Connect to a power source (8 to 36 V). The third panel kit is only available in the SCO 11 model. It is not possible to operate the SCO 5 panel remotely through another SCO panel.
Page 58
PANEL COMAP SCO5 SOLÉ SCO 5 PANEL MATERIAL ACABADO TRATAMIENTO PRESENTACIÓN ESCALA DIBUJADO FECHA CREACIÓN VERIFICADO GRADO PRECISIÓN ÚLTIMA REVISIÓN 01/03/2023 VICTORG MEDIO P.IGLESIAS 26/07/2022 61972100S SOLÉ, S.A.
Page 59
PANEL SCO 10 BASADO EN CONFIGURACION 60973400S MATERIAL ACABADO TRATAMIENTO PRESENTACIÓN ESCALA DIBUJADO FECHA CREACIÓN VERIFICADO GRADO PRECISIÓN ÚLTIMA REVISIÓN MEDIO P.IGLESIAS 16/12/2016 3002 SOLÉ, S.A.
Page 60
PANEL COMAP SCO 11 SOLÉ SCO 11 PANEL MATERIAL ACABADO TRATAMIENTO PRESENTACIÓN ESCALA DIBUJADO FECHA CREACIÓN VERIFICADO GRADO PRECISIÓN ÚLTIMA REVISIÓN 01/03/2023 VICTORG P.IGLESIAS MEDIO 26/07/2022 62972100S SOLÉ, S.A.