[sc_devdia_01, 1, en_US]
Figure 8-30
NOTE
i
i
The device-diagnosis log cannot be deleted!
The logged indications are preconfigured and cannot be changed!

Communication Log

8.5.10
The logging of the respective status such as ensuing faults, test and diagnosis operation, and communication
capacity utilizations is done for all hardware-based configured communication interfaces. Up to 500 indica-
tions can be stored in the communication log. Logging occurs separately for each communication port of the
configured communication modules.
Reading from the PC with DIGSI 5
Use the project-tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → Device → Test suite → Communication module
Then select:
J:Onboard Ethernet → Communication log
The communication log is shown to you in the state last loaded from the device.
Before this, refresh the contents by clicking the update arrows in the headline.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-J, Edition 07.2022