15.13 Temperature and Resistance Relationship Tables (for T5)

TEMP F
TEMP C
-5
-20.6
0
-17.8
5
-15.0
10
-12.2
15
-9.4
20
-6.7
25
-3.9
30
-1.1
35
1.7
40
4.4
45
7.2
50
10.0
55
12.8
60
15.6
65
18.3
70
21.1
75
23.9
80
26.7
85
29.4
90
32.2
95
35.0
100
37.8
105
40.6
110
43.3
115
46.1
120
48.9
125
51.7
130
54.4
135
57.2
Table 26
for T5
Data subject to change
RESISTANCE kΩ
VOLTS DC
600.134
4.93
505.551
4.92
427.463
4.91
362.739
4.89
308.891
4.87
265.398
4.85
227.481
4.83
195.601
4.80
168.707
4.77
146.695
4.74
127.258
4.70
110.707
4.66
96.572
4.61
84.465
4.56
74.411
4.51
65.408
4.45
57.634
4.39
50.904
4.32
45.258
4.24
40.152
4.16
35.699
4.08
31.807
3.99
28.398
3.89
25.506
3.80
22.861
3.70
20.529
3.59
18.47
3.48
16.708
3.37
15.085
3.26
TEMP F
TEMP C
RESISTANCE kΩ
140
60.0
145
62.8
150
65.6
155
68.3
160
71.1
165
73.9
170
76.7
175
79.4
180
82.2
185
85.0
190
87.8
195
90.6
200
93.3
205
96.1
210
98.9
215
101.7
220
104.4
225
107.2
230
110
235
112.8
240
115.6
245
118.3
250
121.1
255
123.9
260
126.7
265
129.4
270
132.2
275
135.0
280
137.8
Installation Instructions
VOLTS DC
13.643
3.14
12.359
3.03
11.214
2.91
10.227
2.80
9.308
2.68
8.485
2.56
7.746
2.45
7.105
2.34
6.504
2.23
5.963
2.13
5.474
2.02
5.032
1.92
4.645
1.83
4.28
1.73
3.949
1.64
3.648
1.56
3.383
1.48
3.133
1.40
2.904
1.32
2.694
1.25
2.503
1.18
2.334
1.12
2.172
1.06
2.024
1.00
1.888
0.95
1.767
0.90
1.651
0.85
1.544
0.80
1.446
0.76
10.2020 | Bosch Thermotechnology Corp.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bovb36-18Bovb60-18