Section 11
Testing functionality by secondary injection
11.19

Exit test mode

The following procedure is used to return to normal operation.
1.
Navigate to the test mode folder.
2.
Change the On setting to Off. Press the 'E' key and the left arrow key.
3.
Answer YES, press the 'E' key and exit the menus.
278
After exiting the IED test mode, make sure that the MU is returned to normal mode.
© 2017 - 2022 Hitachi Energy. All rights reserved
1MRK 504 165-UEN Rev. K
SEMOD53244-3 v6
Transformer protection RET670
Commissioning manual