Hitachi RET670 Commissioning Manual page 146

Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
The previous calculations are in primary values. They are transferred to secondary values to perform
injections by a test set. Primary values are transferred to secondary values by taking into account the
CT ratio and the VT ratio (respectively 9000/1 A and 13.8/0.1 kV in the example).
The magnitude of the secondary voltages, that are related to the points RE and SE of the R-X plane,
needs to be checked.
RE (R
FwdR
V
=
t FwdZs
,
EQUATION14054 V1 EN-US
SE (R
RvsR
V
V
=
t RvsZs
,
EQUATION14055 V1 EN-US
The tests, which are described in this section, may require voltages that have magnitude equal to
110% of the previous values. The continuous permissive overload voltage of the protection voltage
channels of the TRM module is 420 V; so the previous voltages may be applied to the analog
channels of the IED continuously. Limitations may be related to the available test set; the current I
was calculated by using a factor 2.5 (instead of the maximum value 4) in order to reduce the
magnitude of the test voltage for the points RE and SE.
Test sets usually do not have a feature to simulate a real network during a power swing and apply the
related analog quantities at the terminal of the generator. The scope of the present test is not a
simulation of a real network. Voltages and currents are supplied in order to measure an impedance
that changes in the time and traverses the plane R-X and, in particular, the area inside the lens
characteristic. The test may be performed by applying:
Symmetric three-phase voltage at 50 Hz. The magnitude depends on the point of the
characteristic that needs to be verified. The following three main points of the line segment SE-
RE need to be checked:
The phase angle of the test voltages is equal to:
arctan (ForwardX/ForwardR) for tests in the quadrant 1 and 2 of the R-X plane
arctan (ReverseX/ReverseR) -180° for tests in the quadrant 3 and 4 of the R-X plane
Symmetric three-phase current, where the current is the summation of two currents that have
the same magnitude, but different frequencies.
I
50
GUID-F02E8D18-FF87-45BE-8142-E8FA19F6966B V1 EN-US
The first current I
phase angle 0º.
The second current I
(at the starting time of the test) and frequency:
140
, X
):
FwdX
V
0 1
.
VT s
,
11931
V
×
=
×
t FwdZ
,
V
13 8
.
,
VT p
, X
):
RvsX
V
0 1
.
,
VT s
5899
×
=
×
t RvsZ
,
13 8
.
V
,
VT p
the point RE (R
, X
FwdR
a point which is related to the parameter ReachZ1 (boundary between zone 1 and zone 2)
the point SE (R
, X
RvsR
I
20918
t
I
10459
=
=
=
=
tf
2
2
has frequency 50 Hz, magnitude 10459 A (that is, 1.162 A secondary) and
50
has magnitude 10459 A (that is, 1.162 A secondary), phase angle 180º
tf
49.5 Hz for the test as generator in the quadrant 1 and 2 of the R-X plane
50.5 Hz for the test as generator in the quadrant 3 and 4 of the R-X plane
© 2017 - 2022 Hitachi Energy. All rights reserved
86 45
.
V
=
42 75
.
V
=
)
FwdX
)
RvsX
A
1MRK 504 165-UEN Rev. K
(Equation 18)
(Equation 19)
(Equation 20)
Transformer protection RET670
Commissioning manual
t

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents