4.2 Setting of controlling frequency and start/stop commands
The SJ700/SJ300/L300P inverters can be configured to take reference set-points and commands from several
different locations. Refer to the table below for information of how to configure the inverter so that the fieldbus
controls frequency and the commands.
SJ-PB2/SJ-PBT2 controls frequency and commands
SJ-PB2/SJ-PBT2 controls frequency only
SJ-PB2/SJ-PBT2 controls commands only
SJ-PB2/SJ-PBT2 has no control.
However, since the SJ-PB2/SJ-PBT2 module uses the "Terminal" to give commands and "Operator" to give
references to the inverter certain steps must be taken in order to be able to control the inverter manually (not
from fieldbus). Study the table below to see how the control word bits shall be set to accomplish control from
fieldbus and from the user.
Controlling the inverter with
A001 = 2 (Operator),
A002 = 1 (Terminal).
SJ-PB2/SJ-PBT2 controls frequency and commands
SJ-PB2/SJ-PBT2 controls frequency only*
SJ-PB2/SJ-PBT2 controls commands only
SJ-PB2/SJ-PBT2 has no control.
from the "Terminal" input when a SJ-PB2/SJ-PBT2 is present in the option slot. In order to do this, bit ten in the
Control Word shall be set to zero. That is, by setting A001=2, A002=1, and control word bit 10=0 it is possible to
control the inverter with the terminal while giving frequency reference from the fieldbus.
*Please note that when frequency reference is controlled from the fieldbus and commands from another location
(such as "Terminal") the direction of the motor must be controlled from the command source (Reverse/Forward
command). In this case changing the sign of reference value cannot control the direction of the motor.
4.3 Action at communication error
In case of occurring transmission errors (communication cut-off with the master), the following actions can be
selected.
Depending on what option slot the option module is connected to, P001 (Option 1) or P002 (Option 2) is
changed.
P001/P002
0
Inverter will trip.
Continue
1
according to the last
received command.
Control
Action at error detection
Option trip E6x or E7x.
operation
Frequency Setting
Selection - A001
2
2
Not equal to 2.
Not equal to 2.
Control word bit settings
10
12
1
0
1
1
1
0
1
1
0
-
Fault can be reset either from
fieldbus or from keypad.
-
9
CHAPTER 4
SETTING
Operation Setting
Selection - A002
1
Not equal to 1.
1
Not equal to 1.
13
0
0
1
1
-
Remarks
-