Technical Data - Bosch Stora SWDP 200-2 Installation And Service Instructions Manual

Dhw tank
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 23
2.5

Technical data

Dimensions and specifications
Pressure drop diagram
Cylinder capacity
Useful capacity (overall)
Equivalent volume of "mixed water" available at 40 °C
Maximum flow rate
Maximum DHW temperature
Maximum operating pressure, potable water
Heat exchanger
Content
Surface area
Heat-up time at rated output (15 °C cold water temperature, 55 °C
cylinder temperature) with dT of 5K
4 kW
6 kW
8 kW
10 kW
12 kW
14 kW
16 kW
18 kW
20 kW
Maximum heating water temperature
Maximum heating water operating pressure
Heat exchanger, solar
Content
Surface area
Technical data in combination with boiler
2)
Rating code N
L
Maximum continuous output at:
80 °C flow temperature, 45 °C DHW outlet temperature and 10 °C
cold water temperature
Included heating water quantity
1) Applies only to DHW tank, buffer module is described in separate IM.
2) According to DIN 4708, at the following temperatures: cold water 10 °C, cylinder charging temperature 60 °C, heat generator flow 80°C, minimum draw-off temperature
45 °C.
Table 29 Technical data
Stora – 6721847474 (2023/02)
1)
Unit
SWDP 200-2
 Fig. 5, Page 67
-
 Fig. 9, Page 69
-
l
183
l
292
L/min
18
°C
95
bar
10
l
8
2
m
1.46
min
144
min
99
min
76
min
62
min
52
min
45
min
40
min
36
min
32
°C
95
bar
6
l
-
2
m
-
N
5.5
L
kW
56.9
L/min
28
l/h
2600
Product information
SWDP 300-2
SWDPS 300-2
 Fig. 6, Page 67
 Fig. 7, Page 68
 Fig. 9, Page 69
 Fig. 9, Page 69
291
287
437
431
29
29
95
95
10
10
10.3
10.3
1.88
1.88
312
312
211
211
160
160
129
129
108
108
93
93
82
82
73
73
66
66
95
95
6
-
3.6
-
0.76
10.6
10.6
69.4
69.4
28
28
2600
2600
6
25