ON THE FLOOR INSTALLATION
Special Precautions
1
ODOR ALERT!
Do not install air
gap on outlet side
of interceptor.
2
Install interceptor as close as possible to
fixtures being served
1
Test Tank for Water Tightness
1a
Cap all
connection
points with 4"
cleanout plugs using
pipe thread sealant or tape approved for
use with plastics.
2
Set Up Outlet Diffuser and Install Cleanout Plugs
Choose outlet location.
2a
Side outlet
Straight-through
page 5 of 10
3
trap. All upstream fixtures must be
Remove cover and fill with
1b
water to just above the
highest connection. For riser
system testing (if required) fill to
finished grade level. CAUTION:
Support risers before filling to
prevent tipping. Inspect unit, connections and gaskets
for leaks. Check water level at specific time intervals
per local code.
2b
Unscrew diffuser retaining
nut and remove outlet
diffuser.
2e
Insert diffuser into chosen outlet and
hand tighten retaining nut.
ODOR ALERT!
Interceptor is not a sewer gas
trapped
2c
Unscrew diffuser foot
retaining nut and remove
outlet diffuser foot.
2f
4
Provide at least 5-1/2" clearance
above unit for routine
maintenance.
Leak?
Call customer
care at 913-951-3300
8a – 5p M – F CST
2d
Rotate diffuser
toward chosen
outlet, replace foot
ensuring it will point
to the back wall of
the unit and hand
tighten foot retaining
nut.
Cap all unused
connection points with
4" cleanout plugs using
pipe thread sealant or
tape approved for use
with plastics.
Schier | GB-2 Installation Guide
5-1/2" min.
5-1/2" min.