Radio frequency interface
RF thermostat
About the operation method, refer to the operation manual that comes
with each remote controller.
Cool/DRY/Fan/Heat/Automatic (cool/heat)/Ventilation modes are available.
• According to a set temperature, cooling operation starts if the room
temperature is too hot and heating operation starts if the room tem-
perature is too cold.
• During automatic operation, if the room temperature changes and
remains 4 °F [2 °C] or more above the set temperature for 15 minutes,
the air conditioner switches to cooling mode. If the room temperature
remains 4 °F [2 °C] or more below the set temperature for 15 minutes,
the air conditioner switches to heating mode.
Cooling mode
15 minutes (switches from
heating to cooling)
15 minutes (switches
from cooling to heating)
Wired remote controller
Set temperature +4 °F [2 °C]
Set temperature
Set temperature -4 °F [-2 °C]
The following 2 patterns of operation are available.
• Run the ventilator together with the indoor unit.
• Run the ventilator independently.
3