USER MANUAL 1.2 | B-FORTIS CC-LITE SERIES
7.
Fig. 13: Set file loading
8.
Fig. 14: Name of configuration file
9.
10.
11.
Fig. 15: Subdirectory with configuration file
12.
13.
14.
26
Under [sysconfig], set "do_sysconfig_from_file" to "yes".
In [sysconfig], enter the name of the configuration file in "sysconfig_ini_name".
Standard: "configuration.ini"
Make sure that all other entries in the "usbupdate.ini" file are set to "no" so that no other actions are
performed.
Save the file "usbupdate.ini" and close the text editor.
Open the "sysconfig" subdirectory in the "usbupdate-mx6" folder.
Open "configuration.ini" file (or the configuration file entered above) with a text editor that supports
the Linux text format.
Search for section [network].
In [network], enter the new IP address of the controller, for example:
eth0.mode="static"
eth0.ip="10.1.101.175"
Eth0.netmask="255.255.0.0"
default_gateway="0.0.0.0"
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen | www.berghof.com
B-Fortis CC-Lite_EN_1.2