5.6 and 8.0 k-factor upright and pendent intermediate level sprinklers quick response

Advertisement

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRL — 5.6 and 8.0 K-factor
Upright and Pendent Intermediate Level Sprinklers
Quick Response
General
Description
The Series TY-FRL, 5.6 and 8.0 K-fac-
tor Upright and Pendent Intermediate
Level Sprinklers described in this data
sheet are automatic sprinklers of the
"quick response" solder type. They are
"standard spray" sprinklers intended
for use in fire sprinkler systems de-
signed in accordance with the stand-
ard installation rules recognized by the
applicable Listing or Approval agency
(e.g., UL Listing is based on NFPA
requirements). Both the Pendent and
Upright Sprinklers produce a hemi-
spherical water distribution pattern be-
low the deflector.
Intermediate Level Sprinklers are pri-
marily designed for use in rack storage
sprinkler systems where their ther-
mally sensitive elements must be
shielded from the water spray of higher
elevation sprinklers that could operate
earlier during a fire. Intermediate Level
Sprinklers are also used in other appli-
cations such as beneath open gridded
catwalks.
WARNINGS
The Series TY-FRL Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3123 -
Upright 5.6K, 1/2"NPT
TY3221 -
Pendent 5.6K, 1/2"NPT
TY4123 -
Upright 8.0K, 3/4"NPT
TY4221 -
Pendent 8.0K, 3/4"NPT
TY3123 is a redesignation for S1991
and G8986.
TY3221 is a redesignation for S1865
and G8972.
TY4123 is a redesignation for S1993
and G8153.
TY4221 is a redesignation for S1867
and G8172.
Technical
Data
Approvals
UL and C-UL Listed.
FM and NYC Approved.
(Refer to Table A for complete ap-
proval information.)
Maximum Working Pressure
175 psi (12,1 bar)
JULY, 2005
Discharge Coefficient
1/2
K = 5.6 GPM/psi
(80,6 LPM/bar
1/2
K = 8.0 GPM/psi
(115,2 LPM/bar
Temperature Ratings
Refer to Table A
Finishes
Natural Brass, Chrome Plated
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Strut . . . . . . . . . . . . . . Monel
Deflector . . . . . . . . . . . Bronze
Hook . . . . . . . . . . . . . . Monel
Link Assembly . . . . . . . . . Nickel
Ejection Spring
. . . . . . . Inconel
Button . . . . . . . . . . . . Bronze
Seal
. . . . . . . . . . . . . Teflon†
Shield
. . . . . . . . . . . . . Brass
† DuPont Registered Trademark
1/2
)
1/2
)
TFP355

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TY-FRL Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco TY-FRL Series

  • Page 1 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-FRL — 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Quick Response ble standards of the National Fire Pro- General tection Association, in addition to the standards of any other authorities hav- Description ing jurisdiction.
  • Page 2 Page 2 of 6 TFP355 SEPERATELY ORDERED 1/2" 4-1/8" (104,8 mm) DIA. PENDENT SERIES TY-FRL & MODEL S4 SHIELD PACKAGE O-RING COMPRISE PENDENT ASSEMBLY (SEE ODERING PROCEDURE) FACTORY 2-3/4" ASSEMBLED (69,9 mm) SPEEDNUT UPRIGHT FIELD ASSEMBLED SHIELD 7/16" 2-11/16" MODEL S4 SHIELD (11,1 mm) (68,3 mm) (SEE INSTALLATION...
  • Page 3: Operation

    TFP355 Page 3 of 6 SPRINKLER FINISH K = 5.6, UPRIGHT TY3123 K = 8.0, UPRIGHT TY4123 K = 5.6, PENDENT TY3221 K = 8.0, PENDENT TY4221 TEMP. FRAME NATURAL CHROME NATURAL CHROME RATING COLOR BRASS PLATED BRASS PLATED CODE 165°F/74°C Unpainted 1, 2, 3, 4...
  • Page 4: Care And Maintenance

    (10) years from date of ship- it controls, permission to shut down the ment by Tyco Fire & Building Products. affected fire protection system must be No warranty is given for products or...
  • Page 5: Ordering Procedure

    TFP355 Page 5 of 6 P/N 58 — XXX — X — XXX TEMPERATURE RATING SPRINKLER MODEL/SIN 165°F/74°C 5.6K UPRIGHT (1/2"NPT) TY3123 NATURAL BRASS 8.0K UPRIGHT (3/4"NPT) TY4123 CHROME PLATED TABLE B PART NUMBER SELECTION SERIES TY-FRL UPRIGHT INTERMEDIATE LEVEL SPRINKLERS (UPRIGHT SHIELD INCLUDED WITH SPRINKLER) P/N 58 —...
  • Page 6 Page 6 of 6 TFP355 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446...