Download Print this page
Tyco TY-FRB Series Instruction Manual

Tyco TY-FRB Series Instruction Manual

5.6 k-factor upright, pendent, and recessed pendent sprinklers quick response, standard coverage
Hide thumbs Also See for TY-FRB Series:

Advertisement

Quick Links

Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/
series-ty-frb-5-6K
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
Page 1 of 4
pendent sprinkler uses one of the
following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY313 . . . . Upright 5.6K, 1/2 in. NPT
TY323 . . . .Pendent 5.6K, 1/2 in. NPT
Technical
Data
Approvals
Refer to Table A
NOVEMBER 2021
Worldwide
www.tyco-fire.com
Contacts
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).
Discharge Coefficient
½
K=5.6 GPM/psi
(80,6 LPM/bar
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly . . . Stainless Steel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
½
)
TFP172

Advertisement

loading
Need help?

Need help?

Do you have a question about the TY-FRB Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco TY-FRB Series

  • Page 1 Sprinkler Sprinkler: Refer to Table B Description Identification Recessed Escutcheon: White Coated, Black Coated, Chrome Plated, or Brass The TYCO Series TY-FRB, 5.6 K-factor, Number (SIN) Plated Upright (TY313) and Pendent (TY323) Physical Characteristics Sprinklers described in this data sheet TY313 .
  • Page 2 TFP172 Page 2 of 4 Components: Temperature rating is Pipe thread connections per ISO 7-1 4 - Bulb Frame indicated on Deflector. can be provided on special request. Button Compression STYLE 15 or 20 Sealing Screw 7/16" (11,1 mm) ESCUTCHEON PLATE 1/2"...
  • Page 3 Installation applied to the pipe threads, hand- tighten the sprinkler into the sprinkler The glass bulb contains a fluid which The TYCO Series TY-FRB, 5.6 K-factor, fitting. expands when exposed to heat. When Upright (TY313) and Pendent (TY323) the rated temperature is reached, the Sprinklers must be installed in accor- Step 3.
  • Page 4 Sprin- Maintenance Warranty klers damaged by dropping, striking, wrench twist/slippage, or the like, must The TYCO Series TY-FRB, 5.6 K-factor, For warranty terms and conditions, visit be replaced. Also, replace any sprin- Upright (TY313) and Pendent (TY323) www.tyco-fire.com.

This manual is also suitable for:

Ty313Ty323