Panasonic Web-server II Operating Instructions Manual page 50

Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01228 Rev: 1
5.3.2.1.2
5.3.2.1.3
5.3.2.1.4
Operating Instructions Web512 V2.6.x for Web-server II 1598
Fault
Fault e-mail.
Receiver(s), Subject and Body data shall be typed.
The following parameters can be used in the "Body" text:
{1}
The custom text string that contains data about the system,
according to chapter "Text", page 45.
{4}
The fault message shown in the fire alarm system.
{6}
The actual EBL512 c.i.e. number, i.e. the c.i.e. in which the
fault is generated (00-29).
{8}
Date & time, i.e. MM-DD hh:mm:ss (month-day hour :
minute : second), e.g. 11-24 12:34:56
NOTE! In the fault form there is the option: Send e-mail when no
connection to EBL512. When this option is selected (default)
and in case of no connection between the Web-server II and the
EBL512 c.i.e. an e-mail will be sent to the same e-mail
address(es) as for a fault e-mail and with the same body text. In
this case the parameter {4} will be replaced with:
FAULT: No connection between web-server and EBL512.
Disablement
Disablement e-mail.
Receiver(s), Subject and Body data shall be typed.
The following parameters can be used in the "Body" text:
{1}
The custom text string that contains data about the system,
according to chapter "Text", page 45.
{5}
The disablement text shown in the fire alarm system (i.e. the
disabled alarm point, zone, loop, output, interlocking output,
routing equipment, alarm device or control output).
{6}
The actual EBL512 c.i.e. number, i.e. the c.i.e. in which the
disabled unit etc. is connected to (00-29).
{8}
Date & time, i.e. MM-DD hh:mm:ss (month-day hour :
minute : second), e.g. 11-24 12:34:56
Service
Service signal e-mail.
Receiver(s), Subject and Body text shall be typed.
The following parameters can be used in the "Body" text:
{1}
The custom text string that contains data about the system,
according to chapter "Text", page 45.
{6}
The actual EBL512 c.i.e. number, i.e. the c.i.e. in which the
service signal is generated, i.e. where the dirty detector is
connected (00-29).