REFRIGERANT AND WATER PIPING
The minimum volume of a closed room where the system is installed to avoid suffocation in case of leakage is:
The formula used for the calculation of the maximum allowed refrigerant concentration in cases of refrigerant leakage is the
following:
R
— = C
V
If the room volume is below the minimum value some effective measure must be taken into account after installing to prevent
suffocation is case of leakage.
Countermeasure in the event of possible refrigerant leakage
The room must have the following features to prevent suffocation in case a refrigerant leakage occurs:
1 Provide a shutterless opening which will allow fresh air to circulate into the room.
2 Provide a doorless opening of 0.15% or more of the floor area.
3 There must be a ventilator fan connected to a gas leak detector, with a ventilator capacity of 0.4 m
refrigeration ton (= compressor displacement volume / (5.7 m
using the refrigerant.
?
N O T E
Always take the maximum value between the R410A and R134a.
4 Pay special attention to the place, such as a basement, etc., where the refrigerant can stay, since refrigerant is heavier than air.
Example:
Outdoor unit (RAS-5WHVNPE)
Opening (m
)
2
Fan (m
55
PMML0575 rev.2 - 03/2022
System combination
YUTAKI S / SCOMBI
YUTAKI S
YUTAKI S80
R: Total quantity of refrigerant charged (kg)
V: Room volume (m³)
C: Refrigerant concentration
Model
RAS-(4-6)WH(V)NPE
RAS-8WHNPE
RAS-10WHNPE
Model
Outdoor unit
RAS-(4-6)WH(V)NPE
Indoor unit
RWH-(4.0-6.0)(V)NF(W)E
Refrigerant (R410A): 3.4 kg
Floor 3.0 m
2
(RWM-5.0NE(-W))
R (kg)
Gas leak detector
/min)
3
Minimum volume (m
4HP
5/6HP
8HP
10HP
4-6HP
/h (R410A) or 14.4 m
/h (R134a)) of the air conditioning system
3
3
Tonnes
2.27
3.16
4.11
R410A
2.27
-
Indoor unit
V (m³)
C (kg/m
)
3
3.4
7.5
0.46
)
3
7.5
7.8
11.4
12.1
7.6
/min or higher per Japanese
3
Tonnes
R134a
-
1.61
Countermeasure
1.0 m
/min fan linked with gas leak
3
detector or 0.5 m
opening
2