Page 1
ROBOT CONTROLLER RC700 Series Manual Rev.3 ENM226C5414F Original instructions Control Unit RC700 RC700-A Drive Unit RC700DU RC700DU-A...
Page 3
ROBOT CONTROLLER RC700 Series Manual Rev.3 Seiko Epson Corporation 2021-2022 RC700 Series Rev.3...
Page 4
Please notify us if you should find any errors in this manual or if you have any comments regarding its contents. MANUFACTURER CONTACT INFORMATION Contact information is described in “SUPPLIERS” in the first pages of the following manual: Robot System Safety Manual Read this manual first RC700 Series Rev.3...
Page 5
For more details on available collection facilities please contact your local government office or the retailer where you purchased this product. For California customers only The lithium batteries in this product contain Perchlorate Material - special handling may apply, See www.dtsc.ca.gov/hazardouswaste/perchlorate RC700 Series Rev.3...
Page 6
Jog Pad JP500 Teaching Pendant TP-3** Operator Panel OP1 For RC700 / RC700-A, be sure to install the EPSON RC+7.0 to the development PC first, then NOTE connect the development PC and RC700 / RC700-A with the USB cable.
Page 7
Structure of Robot System The Drive Unit RC700DU can be used with the following version. EPSON RC+ 7.0 Ver.7.1.0 or later Control Unit RC700-A Drive Unit RC700DU-A can be used with the following version. EPSON RC+ 7.0 Ver.7.1.2 or later Each manipulator can be used with the following version.
Page 8
This manual contains a list of code numbers displayed on the controller and messages displayed in the software message area. The manual is primarily intended for people who design robot systems or do programming. RC700 series Maintenance Manual (PDF) xx series Maintenance Manual (PDF) (xx: Manipulator series name) This manual describes the details of maintenance etc.
Page 9
EPSON RC+ 7.0 User’s Guide (PDF) This manual describes general information about program development software. EPSON RC+ 7.0 SPEL+ Language Reference (PDF) This manual describes the robot programming language “SPEL+”. Other Manual (PDF) Manuals for each option are available. RC700 Series Rev.3...
2.6.11 Robot Operation Panel ............. 37 2.7 Connecting ....................37 2.7.1 Connection to EMERGENCY Connector ........37 2.7.2 Power Supply ................48 2.7.3 Connecting Control Unit and Drive Unit ........51 2.7.4 Drive Unit Setup ................52 RC700 Series Rev.3...
Page 12
3.1 Power-ON Precautions ................56 3.2 Power ON Procedure ................58 4. First Step 4.1 Installing EPSON RC+ 7.0 Software ............59 4.2 Development PC and Controller Connection ......... 61 4.2.1 About Development PC Connection USB Port ......62 4.2.2 Precaution ................... 62 4.2.3 Software Setup and Connection Check........
Page 13
6.2 Switch Operation Mode ................ 116 6.3 Program Mode (AUTO) ................. 117 6.3.1 What is Program Mode (AUTO)? ..........117 6.3.2 Setup from EPSON RC+ ............117 6.4 Auto Mode (AUTO) ................118 6.4.1 What is Auto mode (AUTO)? ............ 118...
Page 14
8.2.2 Adoptable USB Memory ............123 8.3 Backup Controller Function ..............124 8.3.1 Backup Controller with Trigger Button ........124 8.3.2 Load Data with EPSON RC+ 7.0 ..........124 8.3.3 Transfer with E-mail ..............124 8.4 Details of Data ..................125 9.
Page 15
11.4.2 Circuit and Wiring for Drive Unit..........139 12. Standard RS-232C Port 12.1 RS-232C Port..................143 12.2 Confirmation with EPSON RC+ 7.0 (RS-232C) ......... 143 12.3 RS-232C Software Communication Setup (RS-232C) ...... 144 12.4 Communication Cable (RS-232C) ............144 13. I/O Connector 13.1 Input Circuit ..................
WARNING not followed properly. This symbol indicates that a danger of possible harm to people or physical damage to equipment and facilities exists if the associated CAUTION instructions are not followed properly. RC700 Series Rev.3...
RS-232C Board USB2.0 or Ethernet RC700DU/ Standard RC700DU-A Standard I/O Remote I/O Ethernet RS-232C C4 series C8 series C12 series Windows *1 series TP1 (Option) series EPSON RC+ 7.0 software Option Requires preparation by uses (Option) TP3 (Option) RC700 Series Rev.3...
Installation 2. Installation *1 EPSON RC+ 7.0 supports the following OS. Windows 8.1 Pro (EPSON RC+ 7.0 Ver.7.1.0 or later Windows 10 Pro (EPSON RC+ 7.0 Ver.7.2.0 or later *2 Up to three drive unit can be connected. *3 Any one of the manipulators can be controlled.
: Under the arm 1 and bottom of the base *(shade part) * When hold bottom of the base, be careful not caught your hands or fingers. Minimum number of people : 2 people Do not hold RC700 Series Rev.3...
Page 25
Where to hold : Under the arm 1 and bottom of the base *(shade part) When hold bottom of the base, be careful not caught your hands or fingers. Minimum number of people : 2 people Do not hold RC700 Series Rev.3...
Page 26
: Bottom of the base (slashed part) Where to hold : The part other than the part that is should not touch Minimum number of people : 2 people Do not hold : Bottom of the base (slashed part) Figure: C8-A901* (C8L) RC700 Series Rev.3...
Page 27
Where to hold : Under the arm and bottom of the base * * When hold bottom of the base, be careful not caught your hands or fingers. Minimum number of people : 2 people Do not hold RC700 Series Rev.3...
10 minutes. NOTE Manipulators are not suitable for operation in harsh environments such as painting areas, etc. When using Manipulators in inadequate environments that do not meet the above conditions, please contact the supplier of your region. RC700 Series Rev.3...
When using a leveler to adjust the height of the base table, use a screw with M16 diameter. The torque and reaction force produced by Manipulator motion are as follows: RC700 Series Rev.3...
Page 30
The surface roughness of the steel plate should be 25 μm or less. C12 Series C12-A1401** Max. Reaction torque on 2600 the horizontal plate (N·m) Max. Horizontal reaction 1000 force (N) Max. Vertical reaction 3400 force (N) Threaded holes for 7900 Mounting screw RC700 Series Rev.3...
Page 31
(N·m) The plate for the Manipulator mounting face should be 30 mm thick or more and made of steel to reduce vibration. The surface roughness of the steel plate should be 25 μm or less. RC700 Series Rev.3...
Use M6 mounting bolts (screw hole depth: 25 mm + Spring washer + Plane washer) conforming to the strength, ISO898-1 property class: 6.9. Tightening torque: 13 N·m (133 kgf·cm) G1-177* 8kg: 18 lbs. G1-221* 8kg: 18 lbs. RC700 Series Rev.3...
Page 33
(2) Using nippers, cut off the wire tie binding the shaft and arm retaining bracket on the base. (3) Remove the bolts securing the wire ties removed in step (2). Wire tie (4) Remove the shipping bolt and jigs. Bolt: M4×15 Sheet RC700 Series Rev.3...
Page 34
(depth 20 mm or more) Use bolts with specifications conforming to NOTE ISO898-1 Property Class: 10.9 or 12.9. Tightening torque : 32.0 N·m (326 kgf·cm) Pane Washer Spring Washer 4-M8×30 (3) Remove the shipping bolt and jigs. RC700 Series Rev.3...
Page 35
(2) Using nippers, cut off the wire tie binding the shaft and arm retaining bracket on the base. (3) Remove the bolts securing the wire ties Bolt : M4×15 removed in step (2). Sheet Wire tie (4) Remove the shipping bolt and jigs. Bolt : M5×15 RC700 Series Rev.3...
Page 36
Use bolts with specifications conforming to NOTE (depth 20 mm or more) ISO898-1 Property Class: 10.9 or 12.9. Tightening torque : 32.0 N·m (326 kgf·cm) Pane Washer (3) Remove the shipping bolt and jigs. Spring Washer 6-M8×4 RC700 Series Rev.3...
Page 37
(depth 20 mm or more) NOTE Use bolts with specifications conforming to ISO898-1 Property Class: 10.9 or 12.9. Pane Washer Tightening torque Spring Washer : 32.0 N·m (326 kgf·cm) 4-M8×4 (3) Remove the shipping bolt and jigs. RC700 Series Rev.3...
Page 38
Washer : M6 base. Wire tie (3) Remove the bolts securing the wire ties removed in step (2). Arm mounting bolt : M12×20 (4) Remove the shipping bolt and jigs. Eyebolt (Attached at shipment) RC700 Series Rev.3...
Page 39
Use bolts with specifications conforming to NOTE ISO898-1 Property Class: 10.9 or 12.9. Tightening torque Screw Hole : 32.0 N·m (326 kgf·cm) (depth 20 mm or more) Pane washer (3) Remove the shipping bolt and jigs. 6-M12×40 Spring Washer RC700 Series Rev.3...
Page 40
(depth 20 mm or more) Use bolts with specifications conforming to NOTE ISO898-1 Property Class: 10.9 or 12.9. Pane Washer Spring Washer Tightening torque 4-M12×40 : 32.0 N·m (326 kgf·cm) (3) Remove the shipping bolt and jigs. RC700 Series Rev.3...
Page 41
Screw Hole NOTE Intensity of the bolts should be equivalent to (depth 12 mm ISO898-1 Property Class 10.9 or 12.9. or more) Tightening torque : 13.0 N·m (133 kgf·cm) (3) Remove the shipping bolt and jigs. 6-M6×20 RC700 Series Rev.3...
Page 42
It is recommended that the core size of the grounding wire be 5.5 mm2 or more. Directly connect the ground line to the Manipulator as shown in the figure below. Bolt hole M5 (for grounding) 5.5 mm or more Detail of A RC700 Series Rev.3...
Page 43
(depth 25 mm or more) 100 N·m (1020 kgf·cm) After installing the robot, make sure 4-M4×8 to remove the fixing jig that fix the base and the Arm #1. Hexagon socket head screws: 4-M4×8 Fixing jig for transportation RC700 Series Rev.3...
Page 44
It is recommended that the core size of the grounding wire be 5.5 mm2 or more. Directly connect the ground line to the Manipulator as shown in the figure below. N6-A1000** Bolt hole M5 (for grounding) N6-A850**R Bolt hole M5 (for grounding) RC700 Series Rev.3...
- Keep away from dust, oily mist, oil, salinity, metal powder or other contaminants. - Keep away from water. - Keep away from shocks or vibrations. - Keep away from sources of electronic noise - Keep away from strong electric or magnetic fields. RC700 Series Rev.3...
M4×8. (C) Rack mounting * A plate for rack mounting is required. NOTE For Control Unit and Drive Unit installation to the Controller box or the base table, process screw hole drilling as follows. RC700 Series Rev.3...
Page 47
- Hot air with higher temperature than the ambient temperature (about 10 °C) comes out from the Controller. Make sure that heat sensitive devices are not placed near the outlet. - Arrange the cables in front of the Controller so that you can pull the Controller forward. RC700 Series Rev.3...
2.5.3 Wall Mounting Option The control unit and drive unit have a wall mounting option. For the procedure about installation, refer to RC700 Series Maintenance Manual. Controller outer dimensions when using the wall mounting option Dimensions of the mounting holes for the wall...
This section summarizes the minimum conditions that should be observed when using EPSON robots in your robot systems. Please design and manufacture robot systems in accordance with the principles described in this and the following sections.
In many cases, the stop position will not exceed the target position for the operation prior the emergency stop. Depending on the robot’s loading condition and operation speed, overruns are inevitable. Taking this into consideration, be sure the layout for the peripheral equipment includes extra space. RC700 Series Rev.3...
Page 52
Pause and STOP commands do not turn OFF the motors. Therefore, the brake does not function. For the Safeguard system, do not use the circuit for E-STOP. To check brake problems, refer to the following manuals. Manipulator Manual Inspection Point 1.1.2 Inspection Item RC700 Series Rev.3...
It is dangerous to allow someone else to release the safeguard interlock by mistake while the operator is working inside the safeguarded area. To protect the operator working inside the safeguarded area, take measures to lock out and tag out the latch-release switch. RC700 Series Rev.3...
If the robot stops operating when the presence sensing device is activated, it is necessary to ensure that it does not start again until the detected object has been removed. Make sure that the robot cannot automatically restart. RC700 Series Rev.3...
The EMERGENCY connector has input terminals for the Safety Door switch and the Emergency Stop switch. Be sure to use these input terminals to keep the system safe. Connector Standard EMERGENCY connector D-sub25 Pin (male) (Controller side) Screwlock #4-40 RC700 Series Rev.3...
Page 56
When the latched TEACH mode is released while the safety door is open, the status of NOTE Manipulator power is operation-prohibited because the safety door is open at that time. To execute a Manipulator operation, close the safety door again, and then close the latch release input. RC700 Series Rev.3...
Page 57
(1) Turn ON the Controller while the safety door is open in order to boot the Controller software. (2) Make sure that “Safety” is displayed on the EPSON RC+ 7.0 status bar. (3) Close the safety door, and turn ON the switch connecting to the latch release input.
Page 58
(1) Turn ON the Controller to boot the software while pressing the Emergency Stop switch. (2) Make sure that “ERROR/E-STOP” LED on Drive Unit has been turned ON. (3) Make sure that “EStop” is displayed on the status bar on the EPSON RC+ main window. (4) Release the Emergency Stop Switch.
Page 59
The 24 V output is for emergency stop. Do not use it for other purposes. Doing so may result in system malfunction. ■ Do not apply reverse voltage to the Emergency Stop circuit. CAUTION Doing so may result in system malfunction. RC700 Series Rev.3...
Page 60
Motor Driver ESTOP1− AC Input ESTOP2− Emergency Stop detection External +24V Safety Door input 1 Safety Door input 2 Latch release input NOTE:+24V GND + 5V GND Latch release input External Close: Latch off +24V Open: Latch on RC700 Series Rev.3...
Page 61
- 0.4A or less AC Input Emergency Stop detection Exeterks+24V External +24V Safety Door input 1 Safety Door input 2 Latch Release input External Latch release input +24V NOTE:+24V GND + 5V GND Close: Latch off Open: Latch on RC700 Series Rev.3...
Page 62
Circuit Diagrams – Drive unit Circuit Diagram Drive unit ESTOP1+ ESTOP2+ Main Circuit Control Be careful of the direction of voltage application ESTOP1− ESTOP2− Emergency Stop detection Safety Door input 1 Safety Door input 2 Latch release input RC700 Series Rev.3...
Page 63
Emergency stop switch of an Operation Unit (TP) Terminal block NOTE The Emergency cable, Emergency cable kit, and Terminal block are offered as options. Design the cables connecting the units within 20 m long. RC700 Series Rev.3...
Page 64
+24V External +24V External +24V External +24V Terminal block * Fuse For the protection of the emergency stop circuit, the fuse’s capacity should be as follows: - Meets the capacity of the external - 0.4A or less RC700 Series Rev.3...
Page 65
Latch release input Safety Door input 1 Safety Door input 2 Latch release input Safety Door input 1 Safety Door input 2 Latch release input External NOTE Design the cables connecting the units within 20 m long. RC700 Series Rev.3...
RC700DU / RC700DU-A : 8.5 A : 12.5 A : 11.0 A : 2.5 A : 5.5 A : 7.5 A G10 : 12.0 A G20 : 12.0 A RS3 : 6.0 A RS4 : 7.0 A RC700 Series Rev.3...
Page 67
10 kHz or more leakage current. If you install a circuit breaker, please select one that will handle the above mentioned “inrush current”. The power receptacle should be installed near the equipment and should be easily accessible. RC700 Series Rev.3...
Page 68
Following shows specification of power connection side. Mount to the plug like following below. Item Specification AC power wire Black, Black (2 cables) Ground wire Green / Yellow Cable length M4 round solderless Terminal terminal RC700 Series Rev.3...
Do not use any LAN cables on the market. Otherwise, it results in the Robot Controller malfunction. How to turn ON the power switch: Check the connection first. Then, make sure to turn ON the power switch of Drive Unit before turning ON the power switch of Control Unit. RC700 Series Rev.3...
1 2 3 4 (3) Attach the DU number label on Drive Unit. DU1 : 1 Drive Unit DU2 : 2 Drive Unit DU3 : 3 Drive Unit (4) Plug in the power connector. Turn ON the Drive Unit. RC700 Series Rev.3...
Page 71
The Manipulator without connecting them may result in electric shock and/or malfunction of the robot system as it cannot ensure IP65. Connect the power connector and the signal connector of the M/C cables to the Controller. RC700 Series Rev.3...
Page 72
Install the Control Unit and Drive Unit, and then turn ON the robot system. After turning ON the system, add information of the additional system. (1) Select the EPSON RC+ 7.0-[Setup]-[System Configuration]. [System Configuration] dialog box will appear. (2) Click [Controller]-[Robots] in the tree on the left.
Page 73
All Manipulators available for the motor driver currently installed in the Controller will be displayed. (5) Click the <OK> button. The EPSON RC+ will restart. (6) Click [Controller]-[Robots]-[Robot **]-[Calibration] in the tree on the left. Following dialog box will appear.
Page 74
1. Brake release unit (option) 2. External short connector When operating the Manipulator, be sure to connect either of the parts to the position indicated below. C4, C8, C12 (Figure: The external short connector is connected C4) RC700 Series Rev.3...
Page 75
■ When connecting or replacing the parts, turn OFF the power to the Controller and the brake release unit. Inserting and removing the WARNING connector while the power is ON may result in electrical shock. RC700 Series Rev.3...
Page 76
Control unit starts up normally. If an error is displayed, check connection in step (1) to (5) and turn ON the power again. If an error is displayed after checking the connection, contact the supplier in your region. RC700 Series Rev.3...
Page 77
Installation 4. First Step 4. First Step This section indicates the procedure to install the development PC EPSON RC+, and execute simple program after connecting the development PC and Controller with a USB. Make sure that the Robot system is installed safely by following the description in “Safety”...
Page 78
Installation 4. First Step (4) Select the drive where you want to install EPSON RC+ 7.0 and click <Next>. The installation directory is called EpsonRC70. This cannot be changed. (5) The dialog box for selecting the options to be installed will be displayed. Check the options you want to install and click <Next>.
Page 79
- For other details of development PC and Controller connection, refer to EPSON RC+7.0 User’s Guide: [PC to Controller Communications] Command (Setup Menu). - For RC700 / RC700-A, be sure to install the EPSON RC+7.0 to the development PC first, then connect the development PC and RC700 / RC700-A with the USB cable.
Page 80
(USB Ver.1.1 upward compatible) Connect the Controller and development PC by a USB cable to develop the robot system or set the Controller configuration with the EPSON RC+ 7.0 software installed in the development PC. Development PC connection port supports hot plugging. Insertion and removal of the cables while the power of the development PC and the Controller are ON is available.
Page 81
4.2.3 Software Setup and Connection Check The following is the steps of connecting the development PC and the Controller. (1) Make sure that EPSON RC+ 7.0 is installed on the Controller connected to the development PC. (Install the software when it is not installed.) (2) Connect the development PC and the Controller by the USB cable.
Page 82
4.2.5 Disconnection of Development PC and Controller Disconnection of the development PC and the Controller is indicated. (1) Select the EPSON RC+ 7.0 menu-[Setup]-[PC to Controller Communications] to display the [PC to Controller Communications] dialog box. (2) Click the <Disconnect> button.
Page 83
The arm falling may cause equipment damage to and/or malfunction of the Manipulator. (1) Start the EPSON RC+ 7.0. Double click the <EPSON RC+ 7.0> icon on the desktop. (2) Open the command window. EPSON RC+ 7.0 menu-[Tool]-[Command Window] (3) Execute the following command in [Command Window].
Page 84
(1) Start EPSON RC+ 7.0. Double click the <EPSON RC+ 7.0> icon on the desktop. (2) Create a new project. 1. EPSON RC+ 7.0 menu-[Project]-[New Project]. [New Project] dialog box will be displayed. 2. Enter the project name in [Project Name] box. (Ex: FirstApp) 3.
Page 85
(5) Move the Manipulator with Jog motion. Select [Jog & Teach] tab. Select “Joint” in [Jogging]-<Mode>. Move the Manipulator by joint by clicking J1-J6 jog keys. Manipulator can be moved by setting to other modes or setting the jog distance. RC700 Series Rev.3...
Page 86
Installation 4. First Step 4.3 Writing your first program After installing the Controller, Manipulator, and EPSON RC+ 7.0 software on your PC, follow the instructions below to create a simple application program so that you will become more familiar with EPSON RC+ 7.0 development environment.
Page 87
(3) Click the Start button on the Run window to run the program. (4) The texts like the following will be displayed in the status window. 19:32:45 Task main started 19:32:45 All tasks stopped On the Run window, you will see the output of the print statement. RC700 Series Rev.3...
Page 88
(7) Click the <-Z> button to lower the Z axis of the robot. (8) Select “P1” in the [Point (P)] dropdown list which is next to the <Teach> button. The current point is set to P1. RC700 Series Rev.3...
Page 89
(3) Click the <Start> button to execute the program. (4) The robot will move to each of the points you taught at 20% speed, acceleration, and deceleration. The Power High statement executes the program to operate the robot with increased speed and acceleration. RC700 Series Rev.3...
Page 90
Even though this is only a sample project, we will backup the project and Controller configuration. Backup can be done easily with EPSON RC+ 7.0. It is important that you keep regular backups of your applications on an external media such as a USB memory key.
Page 92
Installation 5. Second Step 5.2 Ethernet Connection of Development PC and Controller EPSON RC+ 7.0 User’s Guide “1.9 Security for Controller Ethernet Connection” “1.10 Security for Compact Vision CV2-A Ethernet Connection” “1.11 Security for Feeder Ethernet Connection” “4.3.3 Ethernet Communication”...
Page 93
Functions required for designing This section contains information for setup and operation of the Robot Controller and Drive Unit.
Page 95
RS-232C Board USB2.0 or Ethernet RC700DU/ Standard RC700DU-A Standard I/O Remote I/O Ethernet RS-232C C4 series C8 series C12 series Windows *1 series TP1 (Option) series EPSON RC+ 7.0 software Option Requires preparation by uses (Option) TP3 (Option) RC700 Series Rev.3...
Page 96
Functions 1. Specifications *1 EPSON RC+ 7.0 supports the following OS. Windows 8.1 Pro (EPSON RC+ 7.0 Ver.7.1.0 or later Windows 10 Pro (EPSON RC+ 7.0 Ver.7.2.0 or later *2 Up to three drive unit can be connected. *3 Any one of the manipulators can be controlled.
Page 97
Output : 16 Unit Output : 16 input/output Assignment signals (standard) change allowed Input : 2 R I/O Output : 2 Communication Ethernet 1 channel interface (standard) Drive Unit connect 2 channel interface (standard) RS-232C port 1 port RC700 Series Rev.3...
Page 98
- Overheat detection at the Motor Driver Module - Relay welding detection - Over-voltage detection - AC power supply voltage reduction detection - Temperature error detection - Fan error detection 200 VAC to 240 VAC Power Source Single phase 50/60 Hz RC700 Series Rev.3...
Page 99
*2 When using the Force Sensor I/F board, a maximum of one board/two ports expansion is available for RS-232C board. NOTE Use this product under the condition of overvoltage category 2, degree of stain category 2. RC700 Series Rev.3...
Page 100
Functions 1. Specifications 1.3 Outer Dimensions Outer Dimensions of Control Unit [Unit: mm] (Figure: RC700) RC700 Series Rev.3...
Page 101
Functions 1. Specifications Outer Dimensions of Drive Unit [Unit: mm] RC700 Series Rev.3...
Page 102
Check the condition of the filter regularly and clean it when necessary. A dirty filter may result in malfunction of the robot system due to temperature rise of the Drive Unit. For inspection, cleaning, and replacement, refer to the Maintenance 4.1 Fan Filter, 4.2 Fan. RC700 Series Rev.3...
Page 103
(14) M/C SIGNAL connector This connector is used for signals such as the Manipulator’s motor encoders, etc. Connect the Manipulator’s dedicated signal cable. (15) R-I/O connector This connector is for the input signals used for the real time I/O function. RC700 Series Rev.3...
Page 104
For details, refer to Setup & Operation 13. I/O Connector. (22) AC IN The connector for 200VAC power input. For details, refer to 3.3.2 AC Power Cable. (23) Control Unit Signature label The serial number of the Control Unit and other information are shown. RC700 Series Rev.3...
Page 105
(3) Set the screw removed in the step (1) to the lockout bracket B so as not to lose it. (4) Put a padlock through the holes of the lockout brackets A and B to lock. Padlock RC700 Series Rev.3...
Page 106
Check the condition of the filter regularly and clean it when necessary. A dirty filter may result in malfunction of the robot system due to temperature rise of the Drive Unit. For inspection, cleaning, and replacement, refer to RC700 series Maintenance Manual 4.1 Fan Filter, 4.2 Fan.
Page 107
For details, refer to 13. I/O Connector. (15) AC IN The cable for 200VAC power input. For details, refer to 3.3.2 AC Power Cable. (16) Drive Unit Number label The serial number of the Drive Unit is indicated. RC700 Series Rev.3...
Page 108
PAUSE Blink line number *1 For error numbers, refer to EPSON RC+ 7.0 SPEL+ Language Reference, or Online Help. *2 In initial status, execution line of task number 1 is displayed in three-digit. Use Ton statement to change the displayed task number.
Page 109
Teach mode Robot error Flashing Flashing rapidly Emergency stop Flashing rapidly The error information is displayed on the seven-segment display of the Control Unit. NOTE For details, refer to the 2.1 LED and Seven-segment LED Controller. RC700 Series Rev.3...
Page 110
Controller status Controller startup failure *1 Controller startup failure Indicate:9999 Controller in Recovery mode Refer to RC700 series Maintenance Manual 4. Backup and Restore. Indicate:9998 AC power supply drop is detected and software shut down. Indicate:9997 Software shut down is specified from the EPSON RC+ 7.0 (software) or the Teach Pendant (option).
Page 111
CPU and the motor controlling CPU inside the Drive Unit are also designed to constantly check each other for any discrepancies. If a discrepancy is detected, the dynamic brake circuit is activated. Memory Check-sum Error Detection The dynamic brake circuit is activated when a memory check-sum error is detected. RC700 Series Rev.3...
Page 112
AC Power Supply Voltage Drop Detection The dynamic brake circuit is activated when the drop of the power supply voltage is detected. Temperature Anomaly Detection The temperature anomaly is detected. Fan Malfunction Detection Malfunction of the fan rotation speed is detected. RC700 Series Rev.3...
Page 113
Rack-Mount Plate 1 set Power Cable 1 cable USB Cable Clamp 1 set Drive Unit EMERGENCY port connector 1 set I/O Connector 1 set Rack-Mount Plate 1 set Power Cable 1 cable Connecting cable for RC700DU 1 cable RC700 Series Rev.3...
Page 114
- Keep away from dust, oily mist, oil, salinity, metal powder or other contaminants. - Keep away from water. - Keep away from shocks or vibrations. - Keep away from sources of electronic noise - Keep away from strong electric or magnetic fields. RC700 Series Rev.3...
Page 115
Ensure the air flow around the supply and exhaust ports, and install the Controller while leaving space from other equipment or walls as below. * Keep the space about 200 mm or more on the top to maintenance. RC700 Series Rev.3...
Page 116
- Hot air with higher temperature than the ambient temperature (about 10 °C) comes out from the Controller. Make sure that heat sensitive devices are not placed near the outlet. - Arrange the cables in front of the Controller so that you can pull the Controller forward. RC700 Series Rev.3...
Page 117
Functions 3. Installation 3.2.3 Wall Mounting Option The controller has a wall mounting option. For the procedure about installation, refer to RC700 Series Maintenance Manual. Controller outer dimensions when using the wall mounting option Dimensions of the mounting holes for the wall...
Page 118
: 2.5 kVA : 2.2 kVA : 0.5 kVA : 1.1 kVA : 1.5 kVA : 2.4 kVA : 2.4 kVA : 1.2 kVA : 1.4 kVA Refer to the Manipulator manual for rated capacity of the Manipulator motor. RC700 Series Rev.3...
Page 119
10 kHz or more leakage current. If you install a circuit breaker, please select one that will handle the above mentioned “inrush current”. The power receptacle shall be installed near the equipment and shall be easily accessible. RC700 Series Rev.3...
Page 120
Make sure to insert the plug of the AC power cable firmly when connecting to the Controller. Following shows specification of power connection side. Mount to the plug like following below. Item Specification AC power wire Black, Black (2 cables) Ground wire Green / Yellow Cable length M4 round solderless Terminal terminal RC700 Series Rev.3...
Page 121
Manipulator may cause not only improper function of the robot system but also safety problems. CAUTION Before connecting the connector, make sure that the pins are not bent. Connecting with the pins bent may damage the connector and result in malfunction of the robot system. RC700 Series Rev.3...
Page 122
Connect the Manipulator and the M/C SIGNAL connector on the Controller. (4) EMERGENCY The EMERGENCY connector has inputs to connect the Emergency Stop switch and the Safety Door switch. For safety reasons, connect proper switches for these input devices. For details, refer to the 11. EMERGENCY. RC700 Series Rev.3...
Page 123
This connector is used for connecting with input signals necessary for real time I/O function. For details, refer to the 15. R-I/O Connector. (12) Fieldbus I/O If necessary, take EMC countermeasures for the Fieldbus I/O cable. For details, refer to 3.5 Noise Countermeasures. RC700 Series Rev.3...
Page 124
(2) M/C Power Cable Manipulator (3) M/C Signal Cable (4) EMERGENCY Emergency Stop Safety Door, etc. Drive Unit (5) I/O connector Input/Output (6) R-I/O connector Input/Output (7) DU IN connector Drive Unit (8) DU OUT connector (Do not connect anything.) RC700 Series Rev.3...
Page 125
Drive Unit. * Be sure not to connect anything to this connector when using only one Drive Unit. Also, when using the 3 Drive Unit, do not connect anything to this connector on the 2 Drive Unit. RC700 Series Rev.3...
Page 126
Therefore, the Controller should be connected to the Manipulator whose serial number is specified in the Connection Check label attached on the front of the Controller. NOTE The Manipulator’s serial number is indicated on the signature label on the back of the Manipulator. RC700 Series Rev.3...
Page 127
The spark suppressor is more effective when placed closer to the motor. - As they are easily influenced by noise, keep cable such as USB, Ethernet, RS-232C, or fieldbus away from peripheral noise sources. RC700 Series Rev.3...
Page 128
- Put together the cable shield side. Remove the outer cover and fix with the FG clamp. Secure the clamps to the Controller with screws to ground the shield. - Mount Ferrite core to the cable. Ferrite core RC700 Series Rev.3...
Page 129
Do not use any LAN cables on the market. Otherwise, it results in the Robot Controller malfunction. How to turn ON the power switch: Check the connection first. Then, make sure to turn ON the power switch of Drive Unit before turning ON the power switch of Control Unit. RC700 Series Rev.3...
Page 130
1 2 3 4 (3) Attach the DU number label on Drive Unit. DU1 : 1 Drive Unit DU2 : 2 Drive Unit DU3 : 3 Drive Unit Plug in the power connector. Turn ON the Drive Unit. RC700 Series Rev.3...
Page 131
Set up the Control Unit and Drive Unit and turn on the robot system. If information of the new system was not added, follow the steps below to add information. (1) Select the EPSON RC+ 7.0-[Setup]-[System Configuration]. [System Configuration] dialog box will appear.
Page 132
All Manipulators available for the motor driver currently installed in the Drive Unit will be displayed. (5) Click <OK> button. The EPSON RC+ will restart. (6) Click [Controller]-[Robots]-[Robot **]-[Calibration] in the tree on the left. Following dialog box will appear.
Page 133
To use a low speed program verification function (T1: manual deceleration mode) or a high speed program verification function (T2: manual deceleration mode) which is defined in Safety Standards, you will need a Teach Pendant that supported for the function. RC700 Series Rev.3...
Page 134
If you switch the mode with the mode selector key switch and turn on the motor while the enable switch is ON, an error will occur. Turn the Enable Switch off and then on again, and then turn on the motor. RC700 Series Rev.3...
Page 135
Follow the procedures below to switch to the Program mode. 6.3.2 Setup from EPSON RC+ Switch the mode to Program mode from the EPSON RC+. (1) Select EPSON RC+ menu-[Setup]-[System Configuration] to display the [System Configuration] dialog. (2) Select [Startup]-[Start mode].
Auto mode (AUTO) is for automatic operation of the Robot system. Procedures for switching to the Auto mode (AUTO) are the followings. A : Set the start mode of the EPSON RC+ to “Auto” and start the EPSON RC+. (Refer to 6.4.2 Setup from EPSON RC+.) B : Offline the EPSON RC+.
Functions 6. Operation Mode (TEACH/AUTO/TEST) 6.4.3 Setup from Control Device Set the control device from EPSON RC+. (1) Select EPSON RC+ menu-[Setup]-[System Configuration] to display the [System Configuration] dialog. (2) Select [Controller]-[Configuration]. (3) Select [Setup Controller]-[Control Device] to select the control device from the following two types.
7.0 User’s Guide 5.12.1 PC to Controller Communications Command. For RC700 / RC700-A, be sure to install the EPSON RC+ 7.0 to the development PC first, then connect the development PC and RC700 / RC700-A with the USB cable.
Development PC Connection USB Port Connection of the development PC and the Controller is indicated. (1) Make sure that software EPSON RC+ 7.0 is installed to the Controller connected to the development PC. (Install the software when it is not installed.) (2) Connect the development PC and the Controller using a USB cable.
7.4 Disconnection of Development PC and Controller This section describes how to disconnect the development PC and the Controller communication. (1) Select the EPSON RC+ 7.0 menu-[Setup]-[PC to Controller Communications] to display the [PC to Controller Communications] dialog. (2) Click the <Disconnect> button.
This function saves various kinds of Controller data to the USB memory with one push. Data saved in the USB memory is loaded to EPSON RC+ 7.0 to get the status of the Controller and the program simply and accurately.
(3) Compress the folders checked in Step (2), then send them by e-mail. - Delete files that do not relate to the project before transfer. NOTE - This function is used to send the data to the system director and EPSON from the end users for problem analysis. RC700 Series Rev.3...
VXDWORK.bin Saves information of Queues information of WorkQueues.dat WorkQue information the WorkQue. Project Select EPSON RC+ 7.0 menu-[Setup]- All files related to project except [System Configuration] to display the ProjectName.obj *1 [System Configuration] dialog. When [Include project files when status...
Functions 9. LAN (Ethernet Communication) Port 9. LAN (Ethernet Communication) Port - Refer to EPSON RC+ 7.0 User’s Guide 5.12.1 PC to Controller Communications NOTE Command (Setup Menu) for other details for the development PC and Controller connection. - For Ethernet (TCP/IP) communication with robot application software, refer to EPSON RC+ 7.0 Online Help or User’s Guide 14.
(1) Connect between the development PC and the Controller using the USB cable by referring to 7. Development PC Connection USB Port. (2) Select the EPSON RC+ 7.0 menu-[Setup]-[Controller] to display the following dialog. (3) Select [Controller]-[Configuration]. (4) Enter the proper IP address and subnet mask and click the <Apply> button.
(1) Connect the development PC and the Controller using the Ethernet cable. (2) Turn ON the Controller. (3) Start EPSON RC+ 7.0. (4) Display the [PC to Controller Communication] dialog from [Setup] in EPSON RC+ 7.0 menu. (5) Click the <Add> button.
<Close> button to close the [PC to Controller Communications] dialog. Connection between the development PC and the Controller is complete. Now the robot system can be used via an Ethernet connection from EPSON RC+ 7.0. 9.5 Disconnection of Development PC and Controller with Ethernet Disconnection of the development PC and the Controller is shown below.
OPTIONAL DEVICE dummy plug Operation Pendant OP500 Operator Pendant OP500RC Jog Pad JP500 Teaching Pendant TP-3** Operator Panel OP1 Extended Enable cannot be connected. Use the Enable comes with the TP. RC700 Series Rev.3...
For details, refer to the following manuals: Robot Controller Option Teach Pendant TP1 Robot Controller Option Teach Pendant TP2 Robot Controller Option Teach Pendant TP3 External enable switch cannot be connected to the TP port. Use the enable switch provided with the TP. RC700 Series Rev.3...
Before connecting the connector, make sure that the pins are not bent. Connecting with the pins bent may damage the connector and result in malfunction of the robot system. CAUTION Control Unit EMERGENCY Connector (Figure: RC700) Drive Unit EMERGENCY Connector RC700 Series Rev.3...
The latch release input also functions to acknowledge the change of to TEACH mode. NOTE In order to change the latched condition of TEACH mode, turn the mode selector key switch on the Teach Pendant to “Auto”. Then, close the latch release input. RC700 Series Rev.3...
To recover from the emergency stop condition, follow the procedure of safety check as required by the system. After safety check, the operations below are required to recover from the emergency stop condition. - Release the Emergency Stop Switch - Execute the RESET command RC700 Series Rev.3...
The 24 V output is for emergency stop. Do not use it for other purposes. Doing so may result in system malfunction. Do not apply reverse voltage to the Emergency Stop circuit. Doing so may result CAUTION in system malfunction. RC700 Series Rev.3...
Motor Driver ESTOP1− AC Input ESTOP2− Emergency Stop detection External +24V Safety Door input 1 Safety Door input 2 Latch release input External +24V Latch release input Close :Latch off NOTE:+24V GND Open :Latch on + 5V GND RC700 Series Rev.3...
Page 156
- 0.4A or less AC Input Emergency Stop detection External +24V External +24V Safety Door input 1 Safety Door input 2 Latch Release input External +24V Latch release input Close :Latch off NOTE:+24V GND Open :Latch on + 5V GND RC700 Series Rev.3...
11.4.2 Circuit and Wiring for Drive Unit Circuit Diagram Drive Unit ESTOP1+ ESTOP2+ Main Circuit Control Be careful of the direction of voltage application ESTOP1− ESTOP2− Emergency Stop detection Safety Door input 1 Safety Door input 2 Latch release input RC700 Series Rev.3...
Page 158
Emergency stop switch Emergency Stop switch of an Operation Unit (TP) Terminal block NOTE The Emergency cable, Emergency cable kit, and Terminal block are offered as options. Design the cables connecting the units within 20 m long. RC700 Series Rev.3...
Page 159
+24V External +24V External +24V External +24V Terminal block * Fuse For the protection of the emergency stop circuit, the fuse’s capacity should be as follows: - Meets the capacity of the external - 0.4A or less RC700 Series Rev.3...
Page 160
Latch release input Safety Door input 1 Safety Door input 2 Latch release input Safety Door input 1 Safety Door input 2 Latch release input External NOTE sign the cables connecting the units within 20 m long. RC700 Series Rev.3...
When an RS-232C board is mounted in as option unit, the Controller software automatically identifies the RS-232C board. Therefore, no software configuration is needed. Correct identification can be confirmed from EPSON RC+ 7.0. (1) Select the EPSON RC+ 7.0 menu-[Setup]-[System Configuration] to display the [System Configuration] dialog. Select the [RS232]-[CU].
Odd, even, NA Terminator CR, LF, CRLF Refer to EPSON RC+ 7.0 Online Help or Users Guide – 13. RS-232C Communications for RS-232C communication from the Robot application. 12.4 Communication Cable (RS-232C) Prepare a communication cable as described in this section.
: +10.8 V (min.) OFF Voltage : +5 V (max.) Input Current : 10 mA (TYP) at +24 V input Two types of wiring are available for use with the two-way photo coupler in the input circuit. RC700 Series Rev.3...
European Machinery Directives. Plus Common (PNP) connection I/O Connector Output No.0 Load CAUTION Ground Fault occurred same Output common (+DC) If there is ground fault, it does not flow to the load and does not start operate. RC700 Series Rev.3...
* I/O connector is included with shipment. Drive Unit: Connector Standard D-sub 50 male pin I/O Connector (Drive Unit side) Screwlock #4 - 40 * The I/O connector, I/O connector cable, terminal block, and I/O connector kit are offered as options. RC700 Series Rev.3...
The user defines the I/O number that a remote function is assigned to using software configuration. For details about communication with external equipment, refer to EPSON RC+ 7.0 User’s Guide – 12. Remote Control. ■ When using remote I/O, always make sure of the followings. Using the robot system under unsatisfactory conditions may cause malfunction of the system and/or safety problems.
The remote function is initially assigned to the input 0 to 7 and output 0 to 8. To change the function assignment from the initial setting, use EPSON RC+ 7.0. To use all signals, you will need to add Expansion I/O or Fieldbus I/O board(s).
Page 171
EStopOff output ON open. RecoverReqd output ON Pause input OFF Stop input OFF ResetAlarm Not Set Cancel the alarm (*11) SelAlarm1 SelAlarm2 Specify the alarm number to cancel Not Set SelAlarm4 (*10) SelAlarm8 RC700 Series Rev.3...
Page 172
For details, refer to EPSON RC+ 7.0 Online Help or Motor in SPEL+ Language Reference. (*7) For details, refer to EPSON RC+ 7.0 Online Help or MCal in SPEL+ Language Reference. (*8) This is for experienced users only. Make sure that you fully understand the input specification before using.
Page 173
Preferences (1): “Motor power low when ForcePowerLow signal OFF” Preferences (2): “ForcePowerLow signal change pauses all tasks” For details of the Controller preferences, refer to EPSON RC+ 7.0 User’s Guide [Setup]-[System Configuration]-[Controller]-[Preferences] in 5.12.2 [System Configuration] Command (Setup Menu).
Turns ON in TEST mode. Not set EnableOn Turns ON when enable switch is ON. Not set ErrorCode1 Not set Indicates the error number. ErrorCode8192 InsideBox1 Turns ON when the robot is in the approach check area. (*3) Not set InsideBox15 RC700 Series Rev.3...
Page 175
ExtResp_16-31 Not set For details, refer to the following manual. ExtResp_32-47 Not set Remote Control Reference 4. Remote I/O to Be Used ExtResp_48-63 Not set ExtResp_64-79 Not set ExtResp_80-95 Not set ExtResp_96-111 Not set ExtResp_112-127 Not set RC700 Series Rev.3...
Page 176
- The setting is Auto mode and the control device is remote. - The setting is Program mode and Remote I/O is enabled. (*3) For details, refer to EPSON RC+ 7.0 Online Help or Box in SPEL Language Reference. (*4) For details, refer to EPSON RC+ 7.0 Online Help or Plane in SPEL Language Reference.
Page 177
For more information of status number/error number, refer to “Status Code / Error Code List” manual. “Alarm” will on when battery alarm or grease alarm of Controller or Manipulator occurs with “Robot maintenance” enabled. For details of Robot maintenance, refer to “Alarm” section of each Controller maintenance manual. RC700 Series Rev.3...
* Paused Output SelProg1 Input Start Input Pause Input Continue Input Stop Input * The duration varies depending on the Quick Pause (QP) setting and the program’s operating status at the time of Pause input [Unit: msec] RC700 Series Rev.3...
ESW Signal (*1) Reset Signal Input [Unit: msec] (*1) A logical signal to explain the timing of internal processing of the controller. For details about input signals name and operating conditions, refer to the 11.3 Pin Assignments. RC700 Series Rev.3...
If you use this function with Vision, you can create an application of parts pickup, alignment, and assembly by robots without stopping. For details, refer to EPSON RC+7.0 Users Guide – 20. Real time I/O. 15.1 Input Circuit Input Voltage Range : +24 V ±10%...
The following two types of wiring are available in the input circuit for Control Unit. Typical Input Circuit Application 1 R-I/O GND +24V INPUT No.24-1 INPUT No.24-2 INPUT No.25-1 INPUT No.25-2 Typical Input Circuit Application 2 R-I/O GND +24V INPUT No.24-1 INPUT No.24-2 INPUT No.25-1 INPUT No.25-2 RC700 Series Rev.3...
The following two types of wiring are available in the input circuit for Drive Unit. Typical Input Circuit Application 1 R-I/O GND +24V Input No.56-1 Input No.56-2 Input No.57-1 Input No.57-2 Typical Input Circuit Application 2 R-I/O GND +24V Input No.56-1 Input No.56-2 Input No.57-1 Input No.57-2 RC700 Series Rev.3...
INPUT No.313-1 INPUT No.57-2 INPUT No.281-2 INPUT No.313-2 5~15 Not Used * For the pins 5 to 15 , do not connect anything. Connector Standard R-I/O Connector D-sub 15 male pin (Drive Unit side) Screwlock #4 - 40 RC700 Series Rev.3...
The 1 Expansion I/O board 96 to 119 96 to 111 The 2 Expansion I/O board 128 to 151 128 to 143 The 3rd Expansion I/O board 160 to 183 160 to 175 The 4th Expansion I/O board RC700 Series Rev.3...
I/O board. Therefore, no software configuration is needed. Correct identification can be confirmed from EPSON RC+ 7.0. (1) Select the EPSON RC+ 7.0 menu-[Setup]-[System Configuration] to display the [System Configuration] dialog. (2) Select [Controller]-[Inputs / Outputs].
Be sure to wire the output circuit properly because it has no protection circuitry ■ for short-circuit and reverse-connection. Improper wiring may cause malfunction of the parts on the board and then improper function of the robot system. RC700 Series Rev.3...
Output common No.64 to 71 Not Used Connector Standard D-sub 50 male pin I/O Connector (Controller side) Screwlock #4 - 40 * The I/O connector, I/O connector cable, terminal block, and I/O connector kit are offered as options. RC700 Series Rev.3...
Page 192
Output common No.96 to Not Used Connector Standard D-sub 50 male pin I/O Connector (Controller side) Screwlock #4 - 40 * The I/O connector, I/O connector cable, terminal block, and I/O connector kit are offered as options. RC700 Series Rev.3...
Page 193
Output common No.128 to Not Used Connector Standard D-sub 50 male pin I/O Connector (Controller side) Screwlock #4 - 40 * The I/O connector, I/O connector cable, terminal block, and I/O connector kit are offered as options. RC700 Series Rev.3...
Page 194
Output common No.160 to Not Used Connector Standard D-sub 50 male pin I/O Connector (Controller side) Screwlock #4 - 40 * The I/O connector, I/O connector cable, terminal block, and I/O connector kit are offered as options. RC700 Series Rev.3...
- PROFINET - CC-LINK - EtherNet/IP™ - EtherCAT® - Modbus (This is not optional but a standard feature.) Refer to the following manuals. Robot Controller option Fieldbus I/O EPSON RC+ 7.0 User’s Guide 11.7 Fieldbus Slave I/O RC700 Series Rev.3...
Data bit length 7, 8 Stop bit length 1, 2 Parity Odd, even, NA Terminator CR, LF, CRLF Refer to EPSON RC+ 7.0 Online Help or Users Guide – 13. RS-232C Communications for RS-232C communication from the Robot application. RC700 Series Rev.3...
Pin assign of the RS-232C connector is as follows. Pin No Signal Function Signal Direction Data carrier detect Input Receive data Input Send data Output Terminal ready Output Signal ground Data set ready Input Request to send Output Clear to send Input Ring indicator Input RC700 Series Rev.3...
For details, refer to the related manuals. When using as the conveyor encoder: Refer to EPSON RC+ 7.0 User’s Guide 16. Conveyor Tracking When using as a PG motion system: Refer to Robot Controller option PG Motion System 16.6 Analog I/O Board 16.6.1 About Analog I/O Board...
Functions 16. Option Slots Overview of Analog I/O Board Circuit Rv: Voltage Input Terminating Resistance (100kΩ), Rc: Current Input Terminating Resistance 16.6.2 Board Configuration (Analog I/O Board) RC700 Series Rev.3...
Page 201
±5V Voltage ±10V output mode 0~5V DAC 2ch Not Use Not Use Not Use Not Use Not Use 0~10V * 0~20mA Current output mode 4~20mA *: Default: DAC default configuration (voltage output: 0 to 10V) SWD1 SWD2 RC700 Series Rev.3...
Page 202
Input Mode 0 to 5.12V ADC 2ch 0 to 10.24V * Current 0 to 24mA Input Mode SWD4: Not used. Please turn them OFF. *: Default: ADC default configuration (voltage input: 0 to 10.24V) SWD1 SWD3 SWD4 RC700 Series Rev.3...
I/O board to the optional unit of the Controller. Therefore, no software configuration is needed. Correct identification can be confirmed from EPSON RC+. Select the EPSON RC+ 7.0 menu-[Setup]-[System Configuration] to display the [System Configuration] dialog. (2) Select [Controller]-[Inputs / Outputs]-[Analog I/O]. RC700 Series Rev.3...
Applying a voltage more than ±11V may result in malfunction of the board. Improper wiring or short circuit may cause malfunction of the parts on the board and then improper function of the robot system. RC700 Series Rev.3...
COM (DAC 2ch) IOUT (DAC 2ch) Shield (DAC 2ch) COM (DAC 2ch) Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used VIN (ADC 2ch) Shield (ADC 2ch) COM (ADC 2ch) RC700 Series Rev.3...
Force Sensor can connect to all S250 series. 16.7.2 Board Configuration (Force Sensor I/F Board) Board Appearance Switch and Jumper Configuration Do not change the following DSW1, DSW2, and JMP1 configurations. IRQ5 (Sensor1) IRQ7 IRQ10 JMP1 IRQ11 IRQ15 DSW1 DSW2 CN3 is all open. RC700 Series Rev.3...
The Controller software automatically identifies the Force Sensor I/F board when mounting Force Sensor I/F board to the optional slot of the Controller. Correct identification can be confirmed from EPSON RC+. Select the EPSON RC+ 7.0 menu-[Setup]-[System Configuration] to display the [System Configuration] dialog. (2) Select [Force Sensing]-[Force Sensor I/F Unit].
Reference: 11.3 Pin Assignments The connector signal placement is described below. Reference: 16.8.11 Emergency stop connecter Pin Assignments List of connectors used Connecter No. Manufacturer Model DD-50PF-N 10126-3000PE, 10326-52K0-008 CN3 (accessory) 10136-3000PE, 10336-52K0-008 T1319320125-000 / T2020252201-000 / Tyco T2020252101-000 RC700 Series Rev.3...
Page 209
Functions 16. Option Slots Connection outline (IMM: Injection Molding Machine) One EUROMAP67 board: Two EUROMAP67 boards: RC700 Series Rev.3...
Reserved for future use by EUROMAP I/O Input (*1) Not fixed by EUROMAP, manufacturer I/O Input (*1) dependent Supply from handling device / robot 0V (Robot → IMM) Emergency stop of robot channel1 Emergency stop of robot channel2 Mold area free RC700 Series Rev.3...
Configure DIP-Switch (SW1) to enable the robot Controller to recognize the EUROMAP67 board. Board Appearance Switch setting: Setup the DSW1 board board 16.8.3 Installation (EUROMAP67 Board) For the install procedure, refer to the RC700 series Maintenance Manual. RC700 Series Rev.3...
You can check whether the software has correctly recognized the EUROMAP67 board on the EPSON RC+ 7.0 screen. (1) Select EPSON RC+ 7.0 menu - [Setup] - [System Configuration] to display the [System Configuration] dialog box. (2) Select [Controller] - [Input/Output].
Doing so may damage board parts and prevent the robot system from functioning properly. Note that the I/O logic for controlling the IMM will vary depending on the molding machine. Confirm the proper logic to use before creating programs. RC700 Series Rev.3...
When the safety door has been opened on the IMM side: A function is used to communicate the open safeguard instruction to the robot Controller. EUROMAP67 Board: Overview of Emergency stop circuit EUROMAP67 Board: Overview of Safety Door circuit RC700 Series Rev.3...
Emergency2 (IMM) 21/20 ZA2/ZC2 Safety1 (IMM) ZA3/ZC3 Safety2 (IMM) 23/22 ZA4/ZC4 24V (Robot) GND (Robot) Emergency1 (Robot) 35/34 A1/C1 Emergency2 (Robot) 19/18 A2/C2 *1: DO NOT input a voltage which exceeds 24V. Board may get damage and burnout. RC700 Series Rev.3...
Page 217
Emergency2 (IMM) 21/20 ZA2/ZC2 Safety1 (IMM) ZA3/ZC3 Safety2 (IMM) 23/22 ZA4/ZC4 24V (Robot) GND (Robot) Emergency1 (Robot) 35/34 A1/C1 Emergency2 (Robot) 19/18 A2/C2 *1: DO NOT input a voltage which exceeds 24V. Board may get damage and burnout. RC700 Series Rev.3...
19 SDLATCH2 Safety Door Latch Release 20 SD21 Safety Door input 2 21 SD22 Safety Door input 2 22 24V 24V output 23 24V 24V output 24 24VGND 24VGND output 25 24VGND 24VGND output 26 Not Used RC700 Series Rev.3...
Page 219
25 24VGND 24VGND output 26 Not Used 27 Not Used 28 Not Used 29 Not Used 30 Not Used 31 Not Used 32 Not Used 33 Not Used 34 Not Used 35 Not Used 36 Not Used RC700 Series Rev.3...
Page 220
Functions 16. Option Slots RC700 Series Rev.3...
Regular Inspection Performing inspection properly is essential to prevent trouble and ensure safety. This volume describes the inspection schedule and contents. Inspect according to the schedule.
Visual inspection and cleaning No stain Fan (Front) 1 months Checking the operating sound No noise Fan (Rear) 1 months Checking the operating sound No noise Battery 12 months Visual inspection of seven- No alarm occurred segment and LED RC700 Series Rev.3...
Turns off the motor Safeguard 12 months turn on the safeguard Fan (Front) 1 months Visual inspection and No stain cleaning Fan (Rear) 1 months Checking the operating No noise sound Battery 1 months Checking the operating No noise sound RC700 Series Rev.3...
Appendix A: Open Source Software License Appendix A: Open Source Software License (for RC700 Series) (1) This product includes open source software programs listed below according to the license terms of each open source software program. (2) We provide the source code of the Open Source Programs (each is defined below) until five (5) years after the discontinuation of same model of this option product.
Page 228
Appendix A: Open Source Software License RC700 Series Rev.3...