Huawei SUN2000-50KTL-ZHM3 User Manual page 75

Hide thumbs Also See for SUN2000-50KTL-ZHM3:
Table of Contents

Advertisement

SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
ID
Name
2036
Grid
overfreq
uency
2037
Grid
underfre
quency
Issue 03 (2022-08-30)
Severity
Cause
Major
Cause ID = 1
Power grid exception: The
actual power grid
frequency is higher than
the requirements for the
local power grid code.
Major
Cause ID = 1
Power grid exception: The
actual power grid
frequency is lower than the
requirements for the local
power grid code.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Solution
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm persists, check
whether the power grid
frequency is within the
acceptable range. If not,
contact the local power
operator. If yes, modify the
grid overfrequency protection
threshold through the app,
SmartLogger, or NMS with
the consent of the local
power operator.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm persists, check
whether the power grid
frequency is within the
acceptable range. If not,
contact the local power
operator. If yes, modify the
grid underfrequency
protection threshold through
the app, SmartLogger, or
NMS with the consent of the
local power operator.