Standard features

Drive type
Frames
ACS800-07
R5, R6, R7, R8
(45 to 560 kW)
ACS800-U7
R5, R6, R7, R8
(50 to 600 hp)
ACS800-07
n×R8i
(500 to 2800 kW)
ACS800-17
R6
(55 to 2500 kW)
R7i, R8i
n×R8i
ACS800-37
R6
(55 to 2700 kW)
R7i, R8i
n×R8i
Note: The codes of the options included in the standard unit (when no options are
selected on ordering) are not printed on the type designation label.
Features when no options are selected
IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC control voltage, control
panel CDP312R, no EMC filter, standard control program, bottom entry and exit of
cables, cable lead through entry, boards without coating, one set of default
language documents
UL type 1 (IP21), US type main switch fuse with Class T or L fuses, 115 V AC
control voltage, control panel CDP312R, no EMC filter, standard control program
(US), common mode filter in frame R8 (+E208), top entry and exit of cables, cable
conduit entry, one set of default language documents
IP21 (UL type 1), main switch inside the diode supply module, no AC fuses,
230 V AC auxiliary control voltage, control panel CDP312R, standard control
program, du/dt filtering (+E205), common mode filtering (+E208), EMC filtering
(Category 3, TN or IT systems, +E210), bottom entry and exit of cables, cable lead
through entry, coated boards, one set of default language documents
IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC auxiliary control
voltage, no EMC filter, standard control program, bottom entry and exit of cables,
cable lead through entry, coated boards, one set of default language documents
IP21 (UL type 1), main switch fuse with aR fuses, line contactor, 230 V AC auxiliary
control voltage, control panel CDP312R, standard control program, EMC filtering
(Category 3, TN or IT systems, +E210), du/dt filtering in 690 V R8i (+E205),
common mode filtering (+E208), bottom entry and exit of cables, cable lead
through entry, coated boards, one set of default language documents
IP21 (UL type 1), air circuit breaker, aR fuses, 230 V AC auxiliary control voltage,
control panel CDP312R, RDCO-03, EMC filtering (Category 3, TN systems,
+E200), du/dt filtering (+E205), common mode filtering (+E208), standard control
program, bottom entry and exit of cables, cable lead through entry, coated boards,
one set of default language documents
IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC auxiliary control
voltage, RDCO-03, control panel CDP312R, no EMC filter, standard control
program, bottom entry and exit of cables, cable lead through entry, coated boards,
one set of default language documents
IP21 (UL type 1), main switch fuse with aR fuses, line contactor, 230 V AC auxiliary
control voltage, RDCO-03, control panel CDP312R, EMC filtering (Category 3, TN
or IT systems, +E210), du/dt filtering in 690 V R8i (+E205), common mode filtering
(+E208), standard control program, bottom entry and exit of cables, cable lead
through entry, coated boards, one set of default language documents
IP21 (UL type 1), air circuit breaker, aR fuses, 230 V AC auxiliary control voltage,
RDCO-03, control panel CDP312R, EMC filtering (Category 3 in TN systems,
+E200), du/dt filtering (+E205), common mode filtering (+E208), standard control
program, bottom entry and exit of cables, cable lead through entry, coated boards,
one set of default language documents