Section 10: Intelligent Detectors, Intelligent Detector Bases, And Wireless Gateway; Description; 1: Intelligent Detector Bases; 2: Intelligent Aspiration Detectors - Honeywell NOTIFIER SLC Wiring Manual

Intelligent control panel
Table of Contents

Advertisement

Section 10: Intelligent Detectors, Intelligent Detector Bases, and Wireless

10.1 Description

For Class A power-supervision requirements, refer to Appendix A.2, "Supervising 24 VDC Power", on page 66.
10.1.1 Intelligent Detector Bases
B501 Series: 4-inch flangeless plug-in detector base. (FlashScan/CLIP; Figure 10.1) For white order B501-WHITE. For ivory,
order B501-IV. For black, order B501-BL.
B300-6: 6-inch plug-in detector base. White. For ivory, order B300-6-IV. Replacement model for B210LP. (FlashScan/CLIP;
Figure 10.1)
B210LP: 6-inch flanged plug-in detector base. (FlashScan/CLIP; Figure 10.1)
B710HD Detector Base - used with all HARSH™ detectors. See Sections 10.2 – 10.5. (Discontinued)
B224BI-WH, B224BI-IV Isolator base (Figure 10.3). (-WH is white; -IV is ivory). (Replaces B224BI, legacy ivory)
B224RB-WH, B224RB-IV (FlashScan/CLIP, plug-in relay detector base; Figure 10.4). (-WH is white; -IV is ivory).
B200S-WH, B200S-IV: Intelligent sounder base (See Figure 10.5). (-WH is white; -IV is ivory).
B200S-LF-WH, B200S-LF-IV: Intelligent low-frequency sounder base (See Figure 10.5). (-WH is white; -IV is ivory).
B200SR-WH, B200SR-IV: Intelligent programmable sounder base (See Figure 10.6). (-WH is white; -IV is ivory).
B200SR-LF-WH, B200SR-LF-IV: Intelligent programmable low-frequency sounder base (See Figure 10.6). (-WH is white; -IV is
ivory).
B501BH Standard sounder base. (Discontinued)
B501BH-2 UL 864 9th edition compliant standard sounder base. (Discontinued)
B501BHT-2 UL 864 9th edition compliant temporal sounder base, replaces B501BHT. (Discontinued)
For more information refer to the Installation Instructions documents provided with these devices.
NOTE: White/Ivory/Black bases are color variations only and use the wiring diagrams provided in the SLC Wiring Manual.
10.1.2 Intelligent Aspiration Detectors
VESDA-E series aspiration smoke detectors provide fire protection for NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030 in Flash-
Scan mode. Address using VSC software.
VESDA-E, UL 268 6th edition/ULC:
VEP-A00-P-NTF Addressable VESDA-E VEP with LEDs, UL 268 6th edition/ULC
VEP-A10-P-NTF Addressable VESDA-E VEP with 3.5" Display, UL 268 6th edition/ULC
VEP-A00-1P-NTF Addressable VESDA-E VEP 1 Pipe with LEDs, UL 268 6th edition/ULC
VEU-A00-NTF Addressable VESDA-E VEU with LEDs, UL 268 6th edition/ULC
VEU-A10-NTF Addressable VESDA-E VEU with 3.5" Display, UL 268 6th edition/ULC
VEA-040-A00-NTF Addressable VESDA-E VEA-40 point with LEDs, UL 268 6th edition/ULC
VEA-040-A10-NTF Addressable VESDA-E VEA-40 point with 3.5" Display, UL 268 6th edition/ULC
VESDA-E, UL 268 7th edition:
VEP-A00-P-NTF-UL Addressable VESDA-E VEP with LEDs, UL 268 7th edition
VEP-A10-P-NTF-UL Addressable VESDA-E VEP with 3.5" Display, UL 268 7th edition
VEP-A00-1P-NTF-UL Addressable VESDA-E VEP 1 Pipe with LEDs, UL 268 7th edition
VEU-A00-NTF-UL Addressable VESDA-E VEU with LEDs, UL 268 7th edition
VEU-A10-NTF-UL Addressable VESDA-E VEU with 3.5" Display, UL 268 7th edition
VEA-040-A00-NTF-UL Addressable VESDA-E VEA-40 point with LEDs, UL 268 7th edition
VEA-040-A10-NTF-UL Addressable VESDA-E VEA-40 point with 3.5" Display, UL 268 7th edition
VES-A00-P-NTF-UL Addressable VESDA-E VES scanning detector with LEDs, FlashScan, UL 268 7th edition
VES-A10-P-NTF-UL Addressable VESDA-E VES scanning detector with 3.5" Display, FlashScan, UL 268 7th edition
The FSA-5000 Intelligent FAAST XS, FSA-8000 Intelligent FAAST XM, FSA-20000 Intelligent FAAST XT, and FSA-20000P Intelli-
gent FAAST XT PRO aspiration smoke detectors may be used to provide early warning fire protection using aspiration sensing technol-
ogy.
FSA-5000 covers 5,000 square feet through one pipe.
FSA-8000 covers 8000 square feet through one pipe.
FSA-20000 covers 28,800 square feet through one to four pipes
FSA-20000P covers 28,800 square feet through one to four addressable pipes
These detectors are listed with UL for use with the NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030. They support FlashScan mode
only (an early version of FSA-8000 supported CLIP only). See Section 10.6.