Tyco LFII Series Design Manual

Tyco LFII Series Design Manual

Residential sprinkler
Hide thumbs Also See for LFII Series:

Advertisement

Quick Links

Series LFII Residential Sprinkler
Design Guide
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp490
Table of
Contents
Sections
General Description . . . . . . . . . . . . . . 1
Design: Background . . . . . . . . . . . . . 1
Design: Hydraulics . . . . . . . . . . . . . . . 2
Design: Sprinkler Location . . . . . . . 3-4
Installation . . . . . . . . . . . . . . . . . . . . . 4
Care and Maintenance . . . . . . . . . . . . 4
Limited Warranty . . . . . . . . . . . . . . . . 4
Tables
Degrees of Slope . . . . . . . . . . . . . . . . 3
Figures
Positioning of Sprinklers with
Respect to Obstructions . . . . . . . . . . 9
Page 1 of 10
General
Description
Johnson Controls Residential Sprin-
klers are a type of fast-response auto-
matic sprinklers . They are to be used
only in wet or dry pipe residential sprin-
kler systems for one-and two-family
dwellings and mobile homes per NFPA
13D; wet or dry pipe residential sprin-
kler systems for residential occupan-
cies up to and including four stories
in height per NFPA 13R; or, wet or dry
pipe sprinkler systems for the resi-
dential portions of any occupancy per
NFPA 13 .
This document provides design guid-
ance for the Series LFII Residential
Sprinklers outlined in Table A .
Residential fire sprinkler systems
should only be designed and installed
by those competent and completely
familiar with automatic sprinkler system
design, installation procedures, and
techniques . Several criteria may apply
AUGUST 2022
Worldwide
www.tyco-fire.com
Contacts
to a given installation and usage of
each sprinkler . Consequently, the sprin-
kler system designer is recommended
to review and develop a working under-
standing of the complete list of criteria
prior to initiating the design of a resi-
dential fire sprinkler system .
NOTICE
The Series LFII Residential Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the NATIONAL
FIRE PROTECTION ASSOCIATION, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
TFP490

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LFII Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco LFII Series

  • Page 1: Table Of Contents

    Worldwide www.tyco-fire.com Contacts Series LFII Residential Sprinkler Design Guide IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Scan the QR code or enter the URL in a web browser to access the most up-to-date electronic version of this document.
  • Page 2: Design: Background

    TFP490 Page 2 of 10 Example No . 2: Assuming the use of a Sprinkler Technical pendent sprinkler, the actual coverage Identification Type K-factor Data Sheet area being protected is 17 ft x 17 ft . Number (SIN) Number In this case the minimum flow require- ment for a 18 ft x 18 ft coverage area TY1234 3 .0...
  • Page 3: Design: Sprinkler Location

    TFP490 Page 3 of 10 Example 1: A corridor being protected is 8 ft wide; consequently, an actual 60° 56° 53° 50° 46° 45° coverage area of 8 ft x 20 ft is being 58° 54° 51° 48° 45° 42° contemplated .
  • Page 4: Installation

    Installation For warranty terms and conditions, visit obstructions to heat flow are present www .tyco-fire .com . (e .g .: beams, lintels, etc .) . The Series LFII Residential Sprinklers Under a sloped ceiling, the residential...
  • Page 5: Spacing Under Sloped Ceilings

    TFP490 Page 5 of 10 BACK WALL PENDENT SPRINKLERS SIDEWALL SPRINKLERS ELEVATION ELEVATION A - MAXIMUM: ONE HALF THE MAXIMUM SPRINKLER SPACING (SEE TECHNICAL DATA SHEETS REFERENCED IN TABLE A) FOR THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED MAXIMUM: THE MAXIMUM SPRINKLER SPACING (SEE TECHNICAL DATA SHEETS REFERENCED IN TABLE A) FOR THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED MINIMUM: 8'-0"...
  • Page 6 TFP490 Page 6 of 10 GRAPH GRAPH GRAPH GRAPH BACK WALL PENDENT SPRINKLERS SIDEWALL SPRINKLERS ELEVATION ELEVATION MAXIMUM: ONE HALF THE MAXIMUM SPRINKLER SPACING (SEE TECHNICAL DATA SHEETS REFERENCED IN TABLE A) FOR THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED. MAXIMUM: 3'-0"...
  • Page 7 TFP490 Page 7 of 10 GRAPH GRAPH BACK WALL PENDENT SPRINKLERS SIDEWALL SPRINKLERS ELEVATION ELEVATION MAXIMUM: ONE HALF THE MAXIMUM SPRINKLER SPACING (SEE TECHNICAL DATA SHEETS REFERENCED IN TABLE A) FOR THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED. MAXIMUM: 3'-0" RANGE: 10°...
  • Page 8 TFP490 Page 8 of 10 UNACCEPTABLE PENDENT SPRINKLERS ELEVATION A - MAXIMUM: ONE HALF THE MAXIMUM SPRINKLER ACCEPTABLE SPACING (SEE TECHNICAL DATA SHEETS REFERENCED IN TABLE A) FOR THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED B - MAXIMUM: THE MAXIMUM SPRINKLER SPACING (SEE TECHNICAL DATA SHEETS REFERENCED IN TABLE A) FOR THE COVERAGE AREA BEING...
  • Page 9: Respect To Obstructions

    TFP490 Page 9 of 10 OBSTRUCTION CEILING ELEVATION PENDENT SPRINKLERS MAY BE LOCATED ON OPPOSITE SIDES OF AN OBSTRUCTION NOT EXCEEDING 4 FEET IN WIDTH PROVIDING THE DISTANCE FROM THE CENTERLINE OF THE OBSTRUCTION TO THE SPRINKLERS DO NOT EXCEED ONE HALF THE MAXIMUM SPRINKLER SPACING "A"...
  • Page 10 TFP490 Page 10 of 10 1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...

Table of Contents