Tests carried out on drives
This documentation pertains to
GL150 luftgekühlt
F03 F70 F98 E11
Reference Manual
Medium-Voltage Drive
SINAMICS GL150
Type 6SL3850
Edition
02/2019
www.siemens.com/drives

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS GL150

  • Page 1 Tests carried out on drives This documentation pertains to GL150 luftgekühlt F03 F70 F98 E11 Reference Manual Medium-Voltage Drive SINAMICS GL150 Type 6SL3850 Edition 02/2019 www.siemens.com/drives...
  • Page 2 14.02.2019 14:20 V8.00...
  • Page 3 Introduction General scope of services Tests Medium-Voltage Drive SINAMICS GL150 Type 6SL3850 Reference Manual This documentation pertains to GL150 luftgekühlt F03 F70 F98 E11 Edition 02/2019...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Insulation test .........................27 3.4.1 High-voltage test ........................27 3.4.2 Measuring the insulation resistance..................28 Interface test ..........................29 3.5.1 PROFIBUS communication....................29 3.5.2 Signals to the customer's system...................29 3.5.3 Additional interfaces.......................30 Index................................31 SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 6 Table of contents SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 7: Introduction

    ● Tests that are offered as standard Note If the scope of testing and inspection cannot fulfill all customer requirements, please consult your Siemens sales advisor at head office. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 8 Introduction SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 9: General Scope Of Services

    5. Preparation of test documentation for the customer. The test documentation is created before or after the customer leaves depending on the scope of testing and the time schedule. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 10 PD LD scope of supply. This also applies to components ordered from other Siemens' Groups. The technical data for these components is required at the latest eight weeks before the start of the acceptance test, e.g.: ●...
  • Page 11: Routine Test

    General scope of services 2.1 Routine test Routine test During production, the drive is subject to an internal routine test. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 12: Visual Inspection

    ● Housing degree of protection ● Electrical cabinet components ● Cable installation ● Cable markings ● Setting values of circuit breakers, if used ● Dimensions See also Visual inspection (Page 18) SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 13: Function Tests

    Siemens directives within the scope of quality assurance. The function tests are performed and documented in the Siemens test field by internal test field personnel. For the function test, the drive is in the test mode with restricted monitoring functions.
  • Page 14: Insulation Test

    3.2 certificate. See also Insulation test (Page 27) The insulation test is performed on a separate acceptance day prior to the function test. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 15: Interface Test

    ● Additional interfaces The test is confirmed in a 3.1 certificate – or in the case that the customer has ordered the acceptance test, in a 3.2 certificate. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 16 General scope of services 2.5 Interface test SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 17: Tests

    Tests The tests that have been expressly ordered for the drive with serial number 12345670001001 are listed in the following. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 18: Visual Inspection

    – Fittings and rubber seals in the doors and between the cabinet units – Cable entries – Openings for water pipes, if available – Additional components, if available SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 19: Electrical Cabinet Components

    – Are the cables routed according to the circuit diagram? Result The inspection is passed if the cable installation does not exhibit any deficiencies and matches the information in the circuit diagram. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 20: Cable Markings

    The drive dimensions are measured. The basis for the visual inspection is the order-specific dimension drawing. Test procedure 1. The external dimensions, length, width and height of the drive are measured. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 21 Tests 3.1 Visual inspection Result The test is passed if the dimensions match with what is specified in the dimension drawing. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 22: Function Test

    A message is displayed on the test station computer. Result The test is passed if the drive responds as described when it reaches the switching threshold. The tolerance range is ±5 K. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 23: Redundant 230 V Or 24 V Auxiliary Voltage Supply

    At a DC-link pulsed operation of 2 Hz, all of the inverter thyristors are controlled. The test is performed with reduced DC-link current with a short-circuited drive output on the motor side. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 24: Line Undervoltage

    Test procedure 1. The auxiliary voltage is present. All drive doors are closed. 2. One door of the drive power section is opened. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 25: Safety Shutdown

    2. The drive is in operation. 3. The button is pressed. Result The test is passed if the drive is shut down and the appropriate message is displayed on the test station computer. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 26: Cooling System Test

    4. If no fan is switched in again within 10 s, the drive switches off. A fault is displayed on the test station computer. Result The test is passed if the drive responds as described. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 27: Insulation Test

    5. The test is repeated with 80% test voltage. Result The test is passed if the test instrument is not switched off (tripped) during the test as a result of flashover. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 28: Measuring The Insulation Resistance

    4. The circuits are tested with respect to one another and with respect to the PE protective conductor at the electrical cabinet. Result The test is passed if the insulation resistances lie within the tolerance specified by the standard. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 29: Interface Test

    Test procedure 1. The auxiliary voltage is present. 2. The connection is established via the test station computer. 3. The signals are simulated. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 30: Additional Interfaces

    3. The customer establishes the software connection to the drive. 4. The customer parameterizes and tests the communication of selected interfaces. Result The interface test has been completed after four hours. SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 31: Index

    Temperature monitoring in the control cabinet, 22 G20, 30 G21, 30 G22, 30 G23, 30 G24, 30 G25, 30 G26, 30 G28, 30 G30, 30 G34, 30 G35, 30 SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 32 Index SINAMICS GL150 6SL3850 F03 F70 F98 E11 Reference Manual Rev.201902141420 GL150 luftgekühlt...
  • Page 34 8888888888 000088 01 EN 01 Further Information www.siemens.com/drives Siemens AG Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY *888888888800008801EN01* 888888888800008801EN01...
  • Page 35 Process Industries and Drives Department PD LD P MF-NMA EN Siemens AG, PD LD P MF-NMA EN, Postfach 47 43, 90025 Nürnberg Tel. +49 (911) 433-6422 +49 (911) 433-6921 Email motoren.doku.aud@internal.siemens.co Our ref. 8888888888000088 Date 14.02.2019 Documentation for 6SL3850 Your order no. - 000010...
  • Page 37 Spine label for binder 50 mm (120 g/m2) SINAMICS GL150 6SL3850 GL150 luftgekühlt F03 F70 F98 E11 Tests carried out on drives Spine label for binder 162 mm (120 g/m2) SINAMICS GL150 6SL3850 GL150 luftgekühlt F03 F70 F98 E11 Tests carried out on drives...

Table of Contents