Table 3.4 Recommended cable size and torque requirements
kVA
Input
Capacity
Voltage
100kVA
208V
480V
600V
150kVA
208V
480V
600V
225kVA
208V
480V
600V
300kVA
208V
480V
600V
375kVA
208V
480V
600V
*1 - Voltage drop across power cables not to exceed 2% of nominal source voltage
*2 - Allowable ampacities based on 90 degree C insulation at an ambient temperature of 30 degree C
Not more than 3 conductors in a raceway without derating.
Get user manuals:
See SafeManuals.com
OWNERS / TECHNICAL MANUAL
Input Side * 1, 2
Output
Cable
Torque
Voltage
Size
in. lbs.
208V
300 MCM
347 - 469
or larger
in. lbs.
480V
1/0 AWG
200 - 269
or larger
in. lbs.
600V
3 AWG
200 - 269
or larger
in. lbs.
208V
600 MCM
347 - 469
or larger
in. lbs.
480V
3/0 AWG
347 - 469
or larger
in. lbs.
600V
1/0 AWG
347 - 469
or larger
in. lbs.
208V
3x250 MCM
347 - 469
or larger
in. lbs.
480V
300 MCM
347 - 469
or larger
in. lbs.
600V
4/0 AWG
347 - 469
or larger
in. lbs.
480V
3x350 MCM
347 - 469
or larger
in. lbs.
600 MCM
347 - 469
or larger
in. lbs.
600V
400 MCM
347 - 469
or larger
in. lbs.
480V
3x500 MCM
347 - 469
or larger
in. lbs.
2x250 MCM
347 - 469
or larger
in. lbs.
600V
600 MCM
347 - 469
or larger
in. lbs.
MITSUBISHI ELECTRIC 9700 SERIES UPS
9700 SERIES UPS
Output Side * 1, 2
Cable
Torque
Size
in. lbs.
300 MCM
347 - 469
300 MCM
or larger
in. lbs.
or larger
1/0 AWG
200 - 269
1/0 AWG
or larger
in. lbs.
or larger
3 AWG
200 - 269
or larger
in. lbs.
or larger
600 MCM
347 - 469
600 MCM
or larger
in. lbs.
or larger
3/0 AWG
347 - 469
3/0 AWG
or larger
in. lbs.
or larger
1/0 AWG
347 - 469
1/0 AWG
or larger
in. lbs.
or larger
3x250 MCM
347 - 469
3x250 MCM
or larger
in. lbs.
or larger
300 MCM
347 - 469
300 MCM
or larger
in. lbs.
or larger
4/0 AWG
347 - 469
4/0 AWG
or larger
in. lbs.
or larger
500 MCM
347 - 469
500 MCM
or larger
in. lbs.
or larger
500 MCM
347 - 469
500 MCM
or larger
in. lbs.
or larger
300 MCM
347 - 469
300 MCM
or larger
in. lbs.
or larger
700 MCM
347 - 469
700 MCM
or larger
in. lbs.
or larger
700 MCM
347 - 469
700 MCM
or larger
in. lbs.
or larger
500 MCM
347 - 469
500 MCM
or larger
in. lbs.
or larger
Page Number:
Bypass Side * 1, 2
DC Input Side * 1, 2
Cable
Torque
Cable
Size
in. lbs.
Size
347 - 469
250 MCM
in. lbs.
or larger
200 - 269
250 MCM
in. lbs.
or larger
3 AWG
200 - 269
250 M]
in. lbs.
or larger
347 - 469
500 MCM
in. lbs.
or larger
347 - 469
500 MCM
in. lbs.
or larger
347 - 469
500 MCM
in. lbs.
or larger
347 - 469
2x300 MCM
in. lbs.
or larger
347 - 469
2x300 MCM
in. lbs.
or larger
347 - 469
2x300 MCM
in. lbs.
or larger
347 - 469
2x600 MCM
in. lbs.
or larger
347 - 469
2x600 MCM
in. lbs.
or larger
347 - 469
2x600 MCM
in. lbs.
or larger
347 - 469
3x400 MCM
in. lbs.
or larger
347 - 469
3x400 MCM
in. lbs.
or larger
347 - 469
3x400 MCM
in. lbs.
or larger
3-5
Torque
in. lbs.
347 - 469
in. lbs.
200 - 269
in. lbs.
200 - 269
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.
347 - 469
in. lbs.

Advertisement

Table of Contents
loading

Table of Contents