Diagnostics alarms
With the diagnostics alarms, a distinction is made between incoming and outgoing
diagnostics.
Incoming diagnostics
An event occurs and triggers a diagnostics alarm. Depending on the parameter assignment,
the "Ext_Diag" bit is set.
Outgoing diagnostics
The event is no longer pending and a diagnostics alarm is output without a set "Ext_Diag" bit.
In the case of events that are only pending for a moment, cancellation is delayed by 3
seconds.
The hard errors are supported by text messages stored in the GSD/GSDML file.
7.5

Diagnostics of the RF170C communications module

Diagnostics data of the RF170C is mapped to the channel-related diagnostics of the ET
200pro.
The data in the table below apply for the RF170C:
Table 7- 4
Content
Channel
assignment
Channel type
Channel resolution 101
Error type
SIMATIC RF170C
Operating Instructions, 02/2022, J31069-D0176-U001-A6-7618
Diagnostics of the RF170C
Value
Meaning
80h
Reader 1
81h
Reader 2
11
Input/output channel
B
Word
B
00001
Short-circuit
B
(voltage supply to the reader has a short circuit)
00110
Wire break
B
(connection to the reader is interrupted)
01001
Error
B
(internal module error has occurred on the RF170C)
10000
Parameter assignment error
B
(RF170C does not have parameters)
10001
No encoder voltage or load voltage
B
(supply voltages not present or too low)
7.5 Diagnostics of the RF170C communications module
Diagnostics and error messages