BACnet
®
Gateway for VRF System
5.3.52 OU_rr_uu_CapacitySave_Setting (Multistate Output Object Type)
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Priority_Array
Relinquish_Default
Time_Delay
Notification_Class
Alarm_Values
Fault_Values
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Capacity Save setting table
Capacity Save can be set using the values in the following correspondence table.
Pesent_Value Contents displayed in State_Text
1
Not set
2
100%
3
90%
4
80%
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Unsigned
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetArray[N] of
CharacterString
BACnetPriorityArray
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
Value
(Multistate Output, 32rruu)
"OU_rr_uu_CapacitySave_Setting"
MULTISTATE_OUTPUT (14)
1 ~ 8
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
FALSE
8
Check Capacity Save setting below
-
-
-
-
-
-
-
-
-
-
Pesent_Value
5
6
7
8
ASHRAE
R
R
R
W
O
R
R
O
R
R
O
R
R
O
O
O
O
O
O
O
O
O
Contents displayed in State_Text
70%
60%
50%
40%
UTY-
VBGX
R
R
R
W
-
R
R
R
R
R
R
R
R
R*
R*
R*
R*
R*
R*
R*
R*
-
75/103