ABB DCS 500 Series Service Manual
ABB DCS 500 Series Service Manual

ABB DCS 500 Series Service Manual

Dcs thyristor power converters for dc drive systems 25 to 5150 a
Hide thumbs Also See for DCS 500 Series:
Table of Contents

Advertisement

Quick Links

DCS Thyristor Power Converters
4
2
3
1
for DC Drive Systems
25 to 5150 A
Service Manual
DCS 500
DCS 600

Advertisement

Table of Contents
loading

Summary of Contents for ABB DCS 500 Series

  • Page 1 DCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A Service Manual DCS 500 DCS 600...
  • Page 2 How to use the DCS Documentation System The matrix below indicates all available product documentation and its corresponding order numbers on its left columns as well as all existing DC Drive systems on its top rows. System descriptions, Technical data and Operating instructions (as far as they are available for the corresponding drive) are the basic documents and will be delivered together with each drive.
  • Page 3 DCS 500 / DCS 500B DCS 600 25 to 5150 A Service Manual Code: 3ADW 000 093 R0601 Rev F S_M_E_F.DOC EFFECTIVE: Jul. 4th, 2002 SUPERSEDES: Rev E Oct. 26th, 2001  2002 ABB Automation Products GmbH. All rights reserved. 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 4 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 5: Safety Instructions

    Safety Instructions Overview This chapter contains safety instructions which must be complied with during installation, operation and maintenance of the power converters series DCS 500 or DCS 600. If these instructions are not complied with, this may result in injuries (perhaps even with fa- tal) or in damage to the power converter, the motor and the driven machine.
  • Page 6 Safety Instructions General warning: this symbol warns you of non- electrical risks and dangers which may result in seri- ous or even fatal injury to persons and/or in damage to equipment. Where appropriate, the text printed ad- jacent to this symbol describes how risks of this kind may be avoided.
  • Page 7 Safety Instructions Notes Notes supply information on states requiring particular attention, or indicate that additional information is available on a specific topic. For this purpose, the following symbols are used: CAUTION! Cautions are designed to draw your attention to a particular state of affairs.
  • Page 8 Safety Instructions DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 9: Table Of Contents

    Contents VI A S ERVICE ANUAL Safety Instructions Chapter 1 - Introduction How to use this manual......................1-1 Contents of this manual ......................1-1 Target group ......................... 1-2 Associated publications......................1-2 Storage and transport ......................1-2 Rating plate and type code ....................1-2 Chapter 2 - Fault Tracing Thyristors How to detect, if a thyristor is faulty..................
  • Page 10 Contents Install new thyristor....................6-3 Fasten the clamp ....................... 6-3 Chapter 7 - Exchange of Thyristors for Size C4 Installation of "Disc Type" thyristor in converters size C4 (2050...5150 A) ......7-1 Required Tools ......................7-1 Find faulty thyristor ....................7-2 Install new thyristor....................
  • Page 11: Chapter 1 - Introduction

    Chapter 1 - Introduction How to use this manual The purpose of this service manual is to provide detailed informa- tion on how to service power converters from the DCS 500 or DCS 600 series. Note: If it is not mentioned explicitly all details given in this Service Manual will be valid for both,series DCS 500 and series DCS 600! Contents of this manual...
  • Page 12: Target Group

    Chapter 1 - Introduction Target group This manual is designed to help those responsible for planning, in- stalling, starting up and servicing the thyristor power converter. These people should possess • basic knowledge of physics and electrical engineering, electrical wiring principles, components and symbols used in electrical en- gineering, and •...
  • Page 13 D = PIN-51 modified for 40V X = Galvanic Isolation Special Customer Software 000= Standard Design revision Thyristor type (only for disc types) 1 = ABB Lenzburg 2 = Eupec Design rev. index only used for internal informations Figure 1-2 Type code...
  • Page 14 Chapter 1 - Introduction The technical data and specifications are valid as of going to press. ABB reserves the right to make subsequent alterations. If you have any questions concerning your drive system, please contact your local ABB agent. VI A...
  • Page 15: Chapter 2 - Fault Tracing Thyristors

    Chapter 2 - Fault Tracing Thyristors How to detect, if a thy- Thyristor problems can be noticed by two ways: ristor is faulty A fuse is blown This is an indication, that a strong overcurrent has happened due to one of the following reasons: - An internal short circuit between the phases (line side) because of a defect thyristor (short circuit inside a thyristor from anode to cathode).
  • Page 16: How To Find A Faulty Thyristor

    Chapter 2 - Fault Tracing Thyristors How to find a faulty thy- If a blown fuse is suspected in the converter, the problem is caused most often by a faulty thyistor. To make sure, that a thyristor is the ristor reason and needs to be exchanged fault tracing must be done in two different ways, depending on the size of the converter.
  • Page 17: Converters Size A5, C3 And C4 (900

    Chapter 2 - Fault Tracing Thyristors Converters size A5, These converters are equipped with fuses in the branches of the C3 and C4 power part. (900...5150 A) - The converter must be disconnected from the mains. Blown fuses - In case of a blown fuse, the faulty thyristor or the faulty pair of thyristors are already isolated at one side from the others and therefor the faulty branch is known (see Figure 4-4 ).
  • Page 18 Chapter 2 - Fault Tracing Thyristors VI A 2 - 4 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 19: Chapter 3 - Handling The Semiconductors

    Chapter 3 - Handling the Semiconductors General Instruction how Thyristor modules, busbars and fuses have to be mounted with the correct torque using a torque screw driver or torque wrench. to handle the Semicon- Disc type thyristors in converters size C3 (900...2000 A DC) are ductors normally mounted using a dial gauge, for repair reasons, they can be mounted using a torque wrench.
  • Page 20 Chapter 3 - Handling the Semicinductors VI A 3 - 2 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 21: Chapter 4 - Exchange Of Thyristors For Sizes C1/C2/C2B

    BERULUB FZ1 E3 (grease) Manufacturer: Carl Bechem GmbH, 58089 Hagen ABB Service: GHSN 390 011 P 0051 Before the work is started, disconnect the con- verter from the power supply completely, then check the voltage free condition and make sure,...
  • Page 22: Install New Thyristor Modules

    Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b Install new thyristor - Remove old thermal joint compound (grease) from the heat sink. modules Preparation of the heat sink: if the area is clean, spread out the heat-conducting compound with a rubber spatula or by hand. If the area is dirty, clean the heat sink surface with tissue paper.
  • Page 23: Thyristor Module Location

    Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b Thyristor module lo- cation for: DCS 501 0100 to 0140 for: DCS 501 0200 to 0520 V14/V11 V16/V13 V12/V15 V13/V16 V12/V15 V11/V14 for: DCS 501 0700 for: DCS 501 0680 ... 1000 V14/V11 V16/V13 V12/V15...
  • Page 24 Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b for: DCS 50x 0025 to 0075 and for: DCS 502 0200 to 0520 DCS 502 0100 to 0140 V11/V24 V14/V21 V14/V21 V16/V23 V12/V25 V15/V22 V12/V25 V13/V26 V16/V23 V11/V24 V13/V26 V15/V22 for: DCS 502 0680 ... 1000 for: DCS 502 0700 V24/V11 V26/V13...
  • Page 25 Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b Units with 0100 to 0350 ADC Units with 0450 to 0520 ADC Units with POWER INTERFACE BOARD 0025 to * 2330/1 for units with 0700 ADC SDCS-PIN-1x / -2x 0075 ADC T51 S1 T51 K (S1) 1000/1...
  • Page 26 Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b POWER INTERFACE BOARD Units with 0100 to 0350 ADC Units with 0450 to 0520 ADC Units with SDCS-PIN-1x / -2x 0025 to * 2330/1 for units with 0700 ADC 0075 ADC T51 S1 T51 K (S1) 1000/1...
  • Page 27 Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b Figure 4-5 Typical armature circuit of DCS 50x/60x with SDCS- PIN-20xB DCS 500 / DCS 600 Service Manual VI A 4 - 7 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 28: Module Terminals

    Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b Module terminals The next figures show a few examples and terminals of thyristor modules. The terminals of modules are also stamped or marked by a sticker. K1 G1 K2 G2 SKKT27...SKKT106 Note: This drawing is not valid for the types SKKT.…B…...
  • Page 29 Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b TZ425 or SKET 400 Figure 4-9 Terminals of single thyristor modules (AK) TT425, 570 Figure 4-10 Terminals of half bridge thyristor modules DCS 500 / DCS 600 Service Manual VI A 4 - 9 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 30 Chapter 4 - Exchange of Thyristors for Sizes C1/C2/C2b VI A 4 - 10 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 31: Chapter 5 - Exchange Of Thyristors For Size A5

    - Tissue paper / solvent (e.g. ethanol). - Thermal joint compound: type BECHEM-RHUS SU 2 (grease) Manufacturer: Carl Bechem GmbH, 58089 Hagen ABB Service: GHSN 390 001 P 0001 - Disassembly tool 3ADT 621 023 P1 Note: For more detailed information about the wiring of the power part, see manual Technical Data .
  • Page 32: Find Faulty Thyristor

    Chapter 5 - Exchange of Thyristors for Size A5 Find faulty thyristor 1. Find the defective branches by performing an OHM test (both polarities) between U1, V1, W1 and C1, D1 (see figure 5-1 ) C1 (+) branching fuse branch D1 (-) Figure 5-1 Basic B6-bridge with branching fuses...
  • Page 33: Remove Faulty Thyristor

    Chapter 5 - Exchange of Thyristors for Size A5 Remove faulty thyris- 1. Remove the screws of the DC – busbars and branch fuses pre- venting the stack to be prized open. Note: It depends on the location of the defective thyristor which DC –...
  • Page 34: Install New Thyristor

    Chapter 5 - Exchange of Thyristors for Size A5 Install new thyristor 1. Ensure that the new thyristor is of the correct type (see Appen- dix A ). Keep the semiconductor and its surroundings clean. If necessary clean them with a piece of tissue paper moistened with solvent.
  • Page 35 Chapter 5 - Exchange of Thyristors for Size A5 7. Tighten the nuts of the mounting clamp by hand so that the clamp is in parallel with the contact surface of the heat sinks. Note: The indicating spring is a very sensitive instrument and must be handled with care.
  • Page 36 Chapter 5 - Exchange of Thyristors for Size A5 left stack right stack rear front front rear View from the left Front view View from the right Figure 5-5 Location of thyristors in frame A5 (2-Q bridge) VI A 5 - 6 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 37 Chapter 5 - Exchange of Thyristors for Size A5 D1 (-) C1 (+) Figure 5-6 Location of branch fuses frame A5 DCS 500 / DCS 600 Service Manual VI A 5 - 7 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 38 Chapter 5 - Exchange of Thyristors for Size A5 VI A 5 - 8 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 39: Chapter 6 - Exchange Of Thyristors For Size C3

    - Thermal joint compound: type BECHEM-RHUS SU 2 (grease) Manufacturer: Carl Bechem GmbH, 58089 Hagen ABB Service: GHSN 390 001 P 0001 Note: For more detailed information about the wiring of the power part, see publication Technical Data . Therefore strict observance of the build in instructions given below is of utmost importance.
  • Page 40: Remove Faulty Thyristor

    Chapter 6 - Exchange of Thyristors for Size C3 Remove faulty thyris- - Remove the plastic cover in front of the heat sinks; the screws are accessible, if the SDCS-PIN-x1 boards will be unfastened; there is no need to disconnect the electrical connections at the PIN-x1 boards.
  • Page 41 Chapter 6 - Exchange of Thyristors for Size C3 Install new thyristor - Ensure that the new thyristor is of the correct type (see Appen- dix A ). Keep the semiconductor and its surroundings clean. If necessary clean them with a piece of tissue paper moistened with solvent.
  • Page 42 Chapter 6 - Exchange of Thyristors for Size C3 - Find the required torque from the table below. Tighten the screws alternatively 1/4 turn at a time until the correct torque is reached. Converter type Torque / Nm Force / kN Press clamp 400 V - 500 V...
  • Page 43 Chapter 6 - Exchange of Thyristors for Size C3 Connect wiring of snubber circuits !! Front view View from the left Figure 6-1 Location of thyristors in modules size C3 DCS 500 / DCS 600 Service Manual VI A 6 - 5 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 44 Chapter 6 - Exchange of Thyristors for Size C3 Thyristors only in the case of 4-Q converters Figure 6-2 Location of thyristors in modules size C3 Note: Removed fuses, busbars and upper parts of heat sinks VI A 6 - 6 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 45 - Tissue paper / solvent (e.g. ethanol). - Thermal joint compound: type BECHEM-RHUS SU 2 (grease) Manufacturer: Carl Bechem GmbH, 58089 Hagen ABB Service: GHSN 390 001 P 0001 - Disassembly tool: DCF 1066721 P1 Note: For more detailed information about the wiring of the power part, see publication Technical Data .
  • Page 46 Chapter 7 - Exchange of Thyristors for Size C4 Find faulty thyristor - Find the defective branch(es) by performing an OHM test (both polarities) between U1, V1, W1 and C1, D1 (see Figure 5-1 ). - Remove the screws of the left and right branch fuses. Remove the busbar, leading to the AC connection, too (not necessary at 2-quadrant converters, left version!).
  • Page 47 Chapter 7 - Exchange of Thyristors for Size C4 Mounting clamp View from View from the right the left Disassembly tool Front view Figure 7-1 How to use the disassembly tool (at a left thyristor stack of a converter) Install new thyristor - Ensure that the new thyristor is of the correct type (see Appen- dix A ).
  • Page 48 Chapter 7 - Exchange of Thyristors for Size C4 Loose condition TORQUE INDICATING SPRING Insulating plate Heatsink Correct torque Figure 7-2 Aluminium spring with welded indicating spring - Tighten the nuts of the mounting clamp by hand so that the clamp is in parallel with the contact surface of the heat sinks.
  • Page 49 Chapter 7 - Exchange of Thyristors for Size C4 V 24 V 23 V 13 Assemb ly C4 A ssembly C4 Busba rs o n th e ri ght B usbars on the left (fr ont o f the module) ( front of th e mod ule ) Figure 7-3 Location of thyristors in size C4 (4-Q bridge)
  • Page 50 Chapter 7 - Exchange of Thyristors for Size C4 VI A 7 - 6 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 51: Chapter 8 - Compatibility Of Sdcs-Pin-2 Boards

    Chapter 8 - Compatibility of SDCS-PIN-2 boards Description of SDCS- - In general the SDCS-PIN-20xB board has the same features as its predecessors (SDCS-PIN-20xA/20x or SDCS-PIN-2x). PIN-20xB boards - It is used for all DCS converters Module sizes C1 (≥ 100A), C2 and C2b regardless of software version and function (armature or field supply).
  • Page 52: Compatibility Of Sdcs-Pin-20X Boards

    Chapter 8 - Compatibility of SDCS-PIN-2 boards Compatibility of The SDCS-PIN-20xB boards replaces SDCS-PIN-20xA and SDCS- SDCS-PIN-20x PIN-20x boards, but not vice versa. boards Note: SDCS-PIN-20xA replaces SDCS-PIN-20x, but not vice versa. 400V/500V 600V 100A-350A 405A-520A 700A 610A-1000A 100A-270A 405A/450A Type C1/C2 C1/C2...
  • Page 53: Change Sdcs-Pin-2X Boards

    Chapter 8 - Compatibility of SDCS-PIN-2 boards Change SDCS-PIN-2x The converter is equipped with a SDCD-PIN-21/22/23/24 board: boards - Make sure, electrical and mechanical safety is obtained! - Mark the cables connected to U1, V1, W1 and C1, D1. Mark the plugs connected to X22, X3 and X4.
  • Page 54 Chapter 8 - Compatibility of SDCS-PIN-2 boards VI A 8 - 4 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 55: Chapter 9 - Preventive Maintainance

    Chapter 9 - Preventive Maintainance WARNING! Before performing any maintenance the chapter ‘Safety Instructions’ at the beginning of this manual and within the corresponding Operating Instructions must be followed. Negli- gence of these instructions can cause injury or death. Recommended The DCS requires very little maintenance if installed in an appro- priate environment.
  • Page 56: Internal High Current Connections In Converters Type C4

    Chapter 9 - Preventive Maintainance Internal high cur- The thyristors together with the heatsinks are stacked. Every sin- rent connections gle thyristor is connected to the DC+ and DC- busbars via flexible in converters copper busbars. These busbars consist of 10 layers of preshaped type C4 sheet copper.
  • Page 57 Chapter 9 - Exchange of Thyristors 25 - 700 A Screws to be checked: Screws to be checked: Screws to be checked: Screws to be checked (located behind the bus- bar): Figure 9-1: Power part of a converter module type C4 DCS 500 / DCS 600 Service Manual VI A 9 - 3...
  • Page 58 Chapter 9 - Preventive Maintainance VI A 9 - 4 DCS 500 / DCS 600 Service Manual 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...
  • Page 59 Appendix A - Spare Parts List Item 2.10 to Item 3.60 Common Electronic Parts 2.10 COMMON PARTS FOR CONV. DCS500B/DCF500Bxxxx-xx-21..(CON-2) DESCRIPTION CODE TYPE/DATA NOTES Control board DCS500 B 3ADT220072R4 SDCS-CON - 2 with actual software21.xxx Power supply board 3ADT220090R3 SDCS-POW-1 COAT 2.20 COMMON PARTS FOR CONV.
  • Page 60 Appendix A- Spare Parts List 2.50 2-PHASE FIELD EXCITERS DESCRIPTION CODE TYPE/DATA NOTES Integrated uncontr. 6 A; FEX-1 DCA0012317R1 SDCS-FEX-1 Sep. compl. Unit; incl. Diode M. Integrated single 16 A; FEX-2 DCA0012325R1 SDCS-FEX-2 A Sep. compl. Unit; incl. Thyristor M. Control Board DCF503A0050 3ADT312400R2 SDCS-FEX-32A...
  • Page 61 Appendix A - Spare Parts List 3.60 Coated Boards for 25A - 5150A Modules Power interface board 3ADT220090R27 SDCS-PIN-11-coat 25A; 50A and 75A Mod. Power interface board 3ADT220090R35 SDCS-PIN 205B-Coat 100A - 1000A/400/500V Mod. Power interface board 3ADT220090R38 SDCS-PIN 206B-Coat 110A,270A and 450A/600V M. Power interface board 3ADT220090R6 SDCS-PIN-51-coat...
  • Page 62 Appendix A- Spare Parts List Item 4.00 to 10.00 Modules DCS500B / DCS600 Size C1 25A----140A 4.00 Common Parts for C1, C2, C2b and C3 Modules DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Temperature Sensor (R57) DCA0012139P1 KTY 10-6 M4 (C1-C3 / 550mm cable) Fuse F101;...
  • Page 63 Appendix A - Spare Parts List Module contains: 2Q 4Q 8.00 100 A (400V-500V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor modules DCA0011931P1 SKKT 106/16E * Power interface board 3ADT312500R1 SDCS-PIN 205B Repl. SDCS PIN-21 and PIN205 Fuse F101- F103 on PIN205B 3BSC770010R0101 KTK-R6A/660V...
  • Page 64 Appendix A- Spare Parts List Item 11.00 to 17.10 Modules DCS500B / DCS600 Size C2 200A----520A Module contains: 2Q 4Q 11.00 200 A (400V-500V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor modules DCA0011931P1 SKKT 106/16E * Power interface board 3ADT312500R1 SDCS-PIN 205B Repl.
  • Page 65 Appendix A - Spare Parts List Module contains: 2Q 4Q 16.00 450 A (600V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor modules DCA0011981P1 SKKT210/20E alt.TT250N18KOF Power interface board 3ADT312500R2 SDCS-PIN 206B Repl. SDCS PIN-23 and PIN206 Fuse F101- F103 on PIN206B 3BSC770010R0101 KTK-R6A/660V for PIN206B;...
  • Page 66 Appendix A- Spare Parts List Item 18.10 to 18.30 Modules DCS500B / DCS600 Size C2b 680A----1000A Module contains: 2Q 4Q 18.10 680 A (400V-500V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor modules 3ADC340032P1 TT 425 N16KOF Power interface board 3ADT312500R1 SDCS-PIN 205B Repl.
  • Page 67 Appendix A - Spare Parts List Item 19.00 to 24.00 Modules DCS500B / DCS600 Size A5 900A----2000A 19.01 Common Parts for A5 Modules DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Temperature Sensor (R57) 3ADT710003P1 KTY 2K-M4-800 Module contains: 2Q 4Q 19.00 900 A (600V-690V) CONVERTER DESCRIPTION...
  • Page 68 Appendix A- Spare Parts List Module contains: 2Q 4Q 23.00 2000 A (400V-500V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor 3ADC340074P1 5STP1818F0003 Puls transformer board 3BSE004939R1 SDCS-PIN-41 A Power interface board 3BSE004940R1 SDCS-PIN-51 Semiconductor fuses 3ADC770010P12 170M6169 Cooling fan 3ADT754018P1 D2E 160-AH02-15...
  • Page 69 Appendix A - Spare Parts List Module contains: 2Q 4Q 22.10 1500 A (400V-500V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor DCA0012031P1 5STP18F1800 Puls transformer board 3BSE004939R1 SDCS-PIN-41 A Power interface board 3BSE004940R1 SDCS-PIN-51 Semiconductor fuses 3ADC770010P9 170M6166 former Id.
  • Page 70 Appendix A- Spare Parts List Item 25.00 to 38.00 Modules DCS500B / DCS600 Size C4 2050A----5150A 25.00 Common Parts for C4 Modules DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Air Flow detector ( P1) DCF1066659P1 P 33 AB Temperature Sensor (R57) DCA0012139P3 KTY 10-6 M4 (C4 / 950mm cable )
  • Page 71 Appendix A - Spare Parts List Module contains: 2Q 4Q 28.00 2500 A (600V-690V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor DCA0016169P1 5STP24L2800 Puls transformer board 3BSE004939R1 SDCS-PIN-41 A Power interface board 3BSE004940R1 SDCS-PIN-51 Semiconductor fuses DCA0012848P1 170M7034 *)Cooling fan (Bus Bars"Left side") 1 e.g.
  • Page 72 Appendix A- Spare Parts List Module contains: 2Q 4Q 32.00 3300 A (400V-500V) CONVERTER DESCRIPTION 2 Q 4 Q CODE TYPE/DATA NOTES Thyristor DCA0016169P1 5STP24L2800 Puls transformer board 3BSE004939R1 SDCS-PIN-41 A Power interface board 3BSE004940R1 SDCS-PIN-51 Semiconductor fuses DCA0017271P1 170M7035 *)Cooling fan (Bus Bars"Left side") 1 e.g.
  • Page 73 DCSxxx-5150-x1R21P.. DCA0012660P1 RG35P-4DK.7M.1L *) Select only one Cooling Fan for this C4 Modules If you have any questions concerning spare parts, please contact your local ABB-agent! DCS 500 / DCS 600 Service Manual VI A A - 15 3ADW000093R0601_DCS500B/DCS600_Service Manual_e_f...