2.5.4
Applicable cables and wiring length
Select a recommended cable size to ensure that the voltage drop ratio is within 2%.
If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to
decrease especially at a low speed.
The following table shows a selection example for the wiring length of 20 m (575 V input power supply).
SLD rating (Pr.570 Multiple rating setting = "0")
• Converter unit (FR-CC2-C)
Converter
Terminal
Tightening
model
screw
torque
FR-CC2-[ ]
size
N·m

C355K
M12 (M10) 46
C450K
M12 (M10) 46
C560K
M12 (M10) 46
• Inverter
Inverter
Terminal
Tightening
model
screw
torque
FR-F862-[ ]
size
N·m

05450
M12 (M10) 46
06470
M12 (M10) 46
08500
M12 (M10) 46

It is the gauge of the cable with the continuous maximum permissible temperature of 90°C or higher (LMFC (heat resistant flexible cross-linked
polyethylene insulated cable), etc.). It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.

It is the gauge of the cable with continuous maximum permissible temperature of 90°C (THHN cable). It assumes a surrounding air temperature
of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to

The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, P/+, N/-, and a screw for earthing (grounding).
The screw size for earthing (grounding) terminal is indicated in parentheses.
LD rating (Pr.570 Multiple rating setting = "1")
• Converter unit (FR-CC2-C)
Converter
Terminal
Tightening
model
screw
torque
FR-CC2-[ ]
size
N·m

C355K
M12 (M10) 46
C450K
M12 (M10) 46
C560K
M12 (M10) 46
• Inverter
Inverter
Terminal
Tightening
model
screw
torque
FR-F862-[ ]
size
N·m

05450
M12 (M10) 46
06470
M12 (M10) 46
08500
M12 (M10) 46

It is the gauge of the cable with the continuous maximum permissible temperature of 90°C or higher (LMFC (heat resistant flexible cross-linked
polyethylene insulated cable), etc.). It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.

It is the gauge of the cable with continuous maximum permissible temperature of 90°C (THHN cable). It assumes a surrounding air temperature
of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to

The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, P/+, N/-, and a screw for earthing (grounding).
The screw size for earthing (grounding) terminal is indicated in parentheses.
Crimp terminal
R/L1,
Earthing
S/L2,
P/+, N/-
(grounding)
T/L3
cable
2×100-12 2×100-12 100-10
2×150-12 2×200-12 100-10
2×200-12 2×250-12 100-10
Crimp terminal
Earthing
U, V, W
P/+, N/-
(grounding)
cable
2×125-12 2×100-12 100-10
2×150-12 2×200-12 100-10
2×250-12 2×250-12 100-10
page
85.)
Crimp terminal
R/L1,
Earthing
S/L2,
P/+, N/-
(grounding)
T/L3
cable
2×100-12 2×100-12 100-10
2×150-12 2×200-12 100-10
2×200-12 2×250-12 100-10
Crimp terminal
Earthing
U, V, W
P/+, N/-
(grounding)
cable
2×125-12 2×100-12 100-10
2×150-12 2×200-12 100-10
2×200-12 2×250-12 100-10
page
85.)
Main circuit terminals
Cable gauge
2
HIV cables, etc. (mm
)

R/L1,
Earthing
P/+,
S/L2,
(grounding)
N/-
T/L3
cable
2×100 2×100 100
2×300 2×300 4/0
2×150 2×200 100
2×350 2×400 300
2×200 2×250 100
2×400 2×500 300
Cable gauge
2
HIV cables, etc. (mm
)

Earthing
U, V,
P/+,
(grounding)
W
N/-
cable
2×125 2×100 100
2×350 2×300 4/0
2×150 2×200 100
2×350 2×400 300
2×250 2×250 100
2×500 2×500 300
Cable gauge
2
HIV cables, etc. (mm
)

R/L1,
Earthing
P/+,
S/L2,
(grounding)
N/-
T/L3
cable
2×100 2×100 100
2×300 2×300 4/0
2×150 2×200 100
2×350 2×400 300
2×200 2×250 100
2×400 2×500 300
Cable gauge
2
HIV cables, etc. (mm
)

Earthing
U, V,
P/+,
(grounding)
W
N/-
cable
2×125 2×100 100
2×300 2×300 4/0
2×150 2×200 100
2×350 2×400 300
2×200 2×250 100
2×400 2×500 300
INSTALLATION AND WIRING
AWG/MCM

R/L1,
Earthing
P/+,
S/L2,
(grounding)
N/-
T/L3
cable
AWG/MCM

Earthing
U, V,
P/+,
(grounding)
W
N/-
cable
AWG/MCM

R/L1,
Earthing
P/+,
S/L2,
(grounding)
N/-
T/L3
cable
AWG/MCM

Earthing
U, V,
P/+,
(grounding)
W
N/-
cable
29
2

Advertisement