Residential sprinklers 4.2k horizontal and recessed horizontal sidewall wet pipe and dry pipe systems
Hide thumbs Also See for rapidresponse LFII Series:

Advertisement

Quick Links

Technical Services 800-381-9312 | +1-401-781-8220
Series LFII Residential Sprinklers
4.2K Horizontal and Recessed Horizontal Sidewall
Wet Pipe and Dry Pipe Systems
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Horizontal Sidewall
Sprinklers (TY1334) are decorative,
fast response, frangible bulb sprin-
klers designed for use in residential
occupancies such as homes, apart-
ments, dormitories, and hotels. When
aesthetics and optimized flow charac-
teristics are the major consideration,
the Series LFII Residential Sidewall
Sprinklers should be the first choice.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
• wet and dry pipe residential sprinkler
systems for one- and two-family
dwellings and mobile homes per
NFPA 13D
• wet and dry pipe residential sprinkler
systems for residential occupancies
up to and including four stories in
height per NFPA 13R
• wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
Historically
residential
based on their Listing, have been
limited to wet pipe sprinkler systems
to assure speed of water delivery for a
given prescribed design area (number
of design sprinklers).
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate
prematurely.
Page 1 of 10
www.tyco-fire.com
The Listing for the Series LFII
Residential Horizontal and Recessed
Horizontal Sidewall Sprinklers now
offers the laboratory approved option
of designing dry pipe residential
sprinkler systems.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for the
Series LFII Residential Sprinklers need
not be increased over the number of
design sprinklers (hydraulic design
area) as specified for wet pipe sprinkler
systems, as is accustomed for density/
area sprinkler systems designed per
NFPA 13.
Consequently,
Residential Sprinklers offer the features
of non-water filled pipe in addition to
not having to increase the number of
design sprinklers (hydraulic design
area) for systems designed to NFPA
13, 13D, or 13R. Non-water filled pipe
will permit options for areas sensitive
to freezing
The Series LFII Residential Sprinklers
has a 4.2 (60,5) K-Factor that provides
the required residential flow rates
at
reduced
smaller pipe sizes and water supply
sprinklers,
requirements.
The recessed version of the Series
LFII Residential Sprinklers is intended
for use in areas with finished walls.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 inch (6,4
mm) of recessed adjustment or up
to 1/2 inch (12,7 mm) of total adjust-
ment from the flush mounting surface
position. The adjustment provided by
the Recessed Escutcheon reduces the
accuracy to which the pipe nipples to
the sprinklers must be cut.
The Series LFII Residential Sprinklers
has been designed with heat sensitivity
and water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
SEPTEMBER 2010
the
Series
LFII
pressures,
enabling
NOTICE
The Series LFII Residential Horizontal
Sidewall Sprinklers described herein
must be installed and maintained in
compliance with this document and
the applicable standards of the National
Fire Protection Association, in addition
to the standards of any authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The
installing contractor or sprinkler manu-
facturer should be contacted with any
questions.
Model/Sprinkler
Identification
Number (SIN)
TY1334
TFP410

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the rapidresponse LFII Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco rapidresponse LFII Series

  • Page 1 The Listing for the Series LFII Residential Horizontal and Recessed Description Horizontal Sidewall Sprinklers now offers the laboratory approved option The TYCO RAPID RESPONSE Series of designing dry pipe residential LFII Residential Horizontal Sidewall sprinkler systems. Sprinklers (TY1334) are decorative,...
  • Page 2 TFP410 Page 2 of 10 Components: Frame WRENCH Button Assembly FLATS Sealing Assembly Bulb Compression Screw De ector TOP-OF- 7/16" (11,1 mm) 2-7/8" DIA. DEFLECTOR NOMINAL (73,0 mm) Temperature rating MAKE-IN is indicated on top of De ector. CENTERLINE OF WATERWAY 7/16"...
  • Page 3: Operation

    TFP410 Page 3 of 10 Technical System Types Hydraulic Design Per the UL Listing, wet pipe and dry (NFPA 13) Data pipe systems may be utilized. Per the For systems designed to NFPA 13, C-UL Listing, only wet pipe systems the number of design sprinklers is may be utilized.
  • Page 4 TFP410 Page 4 of 10 ELEVATION WET PIPE SYSTEM Minimum Flow and Residual Pressure Maximum Maximum Coverage Area Spacing Top-of-Deflector-to-Ceiling: Top-of-Deflector-to-Ceiling: 4 to 6 Inches (100 to 150 mm) 6 to 12 Inches (150 to 300 mm) Width x Length Ft.
  • Page 5 TFP410 Page 5 of 10 ELEVATION DRY PIPE SYSTEM Minimum Flow and Residual Pressure Maximum Maximum Coverage Area Spacing Top-of-Deflector-to-Ceiling: Top-of-Deflector-to-Ceiling: Ft. (m) Width x Length 4 to 6 Inches (100 to 150 mm) 6 to 12 Inches (100 to 150 mm) Ft.
  • Page 6 TFP410 Page 6 of 10 12" 8" MAXIMUM ELEVATION WET PIPE SYSTEM Minimum Flow and Residual Pressure Maximum Maximum ( I ) Two sprinkler design with the sprinklers at the high point of the slope and positioned Coverage Area Spacing to discharge down the slope.
  • Page 7 TFP410 Page 7 of 10 12" 4" MAXIMUM ELEVATION WET PIPE SYSTEM Minimum Flow and Residual Pressure Maximum Maximum ( II ) Two sprinkler design with the sprinklers located along the slope and positioned Coverage Area Spacing to discharge across the slope. Width x Length Ft.
  • Page 8 TFP410 Page 8 of 10 12" 8" MAXIMUM ELEVATION WET PIPE SYSTEM Minimum Flow and Residual Pressure Maximum Maximum ( III ) Three sprinkler design when there are more than two sprinklers in a compartment and Coverage Area Spacing with the sprinklers located along the slope and positioned to discharge across the slope. Width x Length Ft.
  • Page 9: Installation

    TFP410 Page 9 of 10 Installation 2. After installing Style • were exposed to corrosive products Mounting Plate over the sprin- of combustion but have not operated, kler threads and with pipe-thread if you cannot easily remove combus- The RAPID RESPONSE Series LFII sealant applied to the pipe threads, tion by-products with a cloth.
  • Page 10: Limited Warranty

    This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Copyright © 2006-2010 Tyco Fire Suppression & Building Products. All rights reserved.