Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also REM615 Point List Manual...
B/2010-06-11 Content updated to correspond to the product version C/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual...
Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. REM615 Point List Manual...
Page 15
Three-phase voltage measurement VMMXU1 Residual voltage measurement RESVMMXU1 Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0 Three-phase power and energy measurement PEMMXU1 P, E P, E RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD) Frequency measurement FMMXU1 REM615 Point List Manual...
DNP3 data mappings Overview This document describes the DNP3 data points and structures available in REM615 Ver.4.0. The data points are unmapped as a default on the DNP3 level.The point lists describe a superset of all data available through the standard configuration A, B, and C including the optional functionalities.
● XRGGIO130 FMMXU1 ● ● ● = available in the device variant, o = optionally available in the device variant Point list for REM615 Ver.4.0 ME01-03 2.3.1 Binary inputs Table 3: Explanations of the binary input table columns Column name...
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked 2.3.1.8 CTRL.CCRDIF1 Current circuit failure protection Table 11: CTRL.CCRDIF1 Current circuit failure protection IEC 61850 name SA name Description Values CTRL.CCRDIF1 .Alm.stVal FAIL Fail Alarm 1=Alarm .Op.general ALARM Fail Operate 1=Operate REM615 Point List Manual...
Underfrequency .Op.general OPR_UFRQ -Operate 1=Operate LD0.FRPFRC2 Frequency gradient .Op.general OPR_FRG -Operate 1=Operate 2.3.1.16 LD0.JAMPTOC1 Stalled motor protection Table 19: LD0.JAMPTOC1 Stalled motor protection IEC 61850 name SA name Description Values LD0.JAMPTOC1 .Op.general OPERATE Stage operate 1=Operate REM615 Point List Manual...
1=Start .Str.phsC -phsC Start 1=Start 2.3.1.19 CTRL.LLN0 Local/remote state (also present in DNP IIN-bits) Table 22: CTRL.LLN0 Local/remote state (also present in DNP IIN-bits) IEC 61850 name SA name Description Values CTRL.LLN0 .Loc.stVal Remote/Local state 0/1=Rem/Loc REM615 Point List Manual...
LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 27: LD0.MAPGAPC3 Multipurpose analog protection function (3) IEC 61850 name SA name Description Values LD0.MAPGAPC3 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REM615 Point List Manual...
LD0.MVGAPC2 Multipurpose binary inputs (2) Table 36: LD0.MVGAPC2 Multipurpose binary inputs (2) IEC 61850 name SA name Description Values LD0.MVGAPC2 .Q1.stVal Input 1 signal 0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On Table continues on next page REM615 Point List Manual...
.HiWrn.stVal HIGH_WARN High warning 1=Warning 2.3.1.42 LD0.RESVMMXU1 Residual voltage limit supervision Table 45: LD0.RESVMMXU1 Residual voltage limit supervision IEC 61850 name SA name Description Values LD0.RESVMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning REM615 Point List Manual...
Values LD0.TCSSCBR2 .CirAlm.stVal ALARM Supervision alarm 1=Alarm 2.3.1.49 LD0.TRPPTRC1 Global conditioning (1) Table 52: LD0.TRPPTRC1 Global conditioning (1) IEC 61850 name SA name Description Values LD0.TRPPTRC1 .Op.general Operate input signal 1=Operate .Tr.general Trip output signal 1=Trip REM615 Point List Manual...
SA name Description Type CTRL.DCCSWI2 .Pos.Oper.ctlVal Disconnector control On/Off 2.3.2.4 CTRL.ESCSWI2 Controllable earth switch (1) control Table 64: CTRL.ESCSWI2 Controllable earth switch (1) control IEC 61850 name SA name Description Type CTRL.ESCSWI1 .Pos.Oper.ctlVal Earth switch control On/Off REM615 Point List Manual...
IEC 61850 name SA name Description Type LD0.PEMMXU1 .SupDmdRs.Oper.ctlVal RSTACM Reset accum. energy 2.3.2.8 DR.RDRE1 Disturbance recorder Table 68: DR.RDRE1 Disturbance recorder IEC 61850 name SA name Description Type DR.RDRE1 .MemClr.Oper.ctlVal Clear all records .RcdTrg.Oper.ctlVal Trig recording REM615 Point List Manual...
IEC 61850 name SA name Description Type LD0.SPCGGIO2 .SPCS01.ctlVal Output 1 control On/Off .SPCS02.ctlVal Output 2 control On/Off .SPCS03.ctlVal Output 3 control On/Off .SPCS04.ctlVal Output 4 control On/Off .SPCS05.ctlVal Output 5 control On/Off Table continues on next page REM615 Point List Manual...
Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 2.3.3.12 LD0.DNPGGIO1 Active parameter setting group Table 86: LD0.DNPGGIO1 Active parameter setting group IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.DNPGGIO1 .ActSG.stVal Active setting group 1…6 1,6,1,6 REM615 Point List Manual...
LD0.RESCMMXU1 .A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] 0,40,0,4000 2.3.3.20 LD0.RESVMMXU1 Residual voltage (1) Table 94: LD0.RESVMMXU1 Residual voltage (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESVMMXU1 0.00..4.00 .PhV.res.instCVal.mag U0_INST Residual voltage [xUn] 0,4,0,400 REM615 Point List Manual...
Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 98: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: REM615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
Page 46
Only non-time-tagged ○ Binary input change with relative time ● Configurable to send one or the other ● Configurable Sends unsolicited responses: Sends static data in unsolicited responses: ● Never ● Never Table continues on next page REM615 Point List Manual...
(non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08 are responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 are responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. REM615 Point List Manual...
Page 48
17, 28 (index) 32-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) Table continues on next page REM615 Point List Manual...
Page 49
Time and 129 (response) 07 (limited qty) date CTO 130 (unsol. resp) (qty = 1) Unsynchro 129 (response) 07 (limited qty) nized time 130 (unsol. resp) (qty = 1) and date Table continues on next page REM615 Point List Manual...
Page 50
17 or 28 are always responded.) 3) Writes of internal indications are only supported for index 7 (Restart IIN1-7) 4) Cold and warm restarts return an application layer acknowledge, but no restart action is taken. REM615 Point List Manual...
Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LHMI Local human-machine interface PCM600 Protection and Control IED Manager Select-before-operate REM615 Point List Manual...
Page 56