Relion
615 series
Motor Protection and Control
REM615
DNP3 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB REM615

  • Page 1 ® Relion 615 series Motor Protection and Control REM615 DNP3 Point List Manual...
  • Page 3 Document ID: 1MRS756880 Issued: 2012-05-11 Revision: C Product version: 4.0 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Document conventions..............7 Functions, codes and symbols............8 Section 2 DNP3 data mappings.............11 Overview...................11 Supported functions................11 Point list for REM615 Ver.4.0 ME01-03..........13 Binary inputs................13 LD0.ARCSARC1 Fault arc protection stage 1......13 LD0.ARCSARC2 Fault arc protection stage 2......13 LD0.ARCSARC3 Fault arc protection stage 3......14 CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure...
  • Page 8 LD0.RESCMMXU1 Residual current limit supervision...23 LD0.RESVMMXU1 Residual voltage limit supervision...23 LD0.SEQRFUF1 Fuse failure protection........24 LD0.SPCGGIO2 Multipurpose binary outputs - status (2)...................24 LD0.SSCBR1 Circuit-breaker condition monitoring....24 LD0.STTPMSU1 Motor startup supervision......25 LD0.TCSSCBR1 Trip circuit supervision (1)......25 LD0.TCSSCBR2 Trip circuit supervision (2)......25 REM615 Point List Manual...
  • Page 9 CTRL.DCXSWI2 Controllable disconnector 2, 4-pole (2 bit) position values..............34 CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values..................34 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values..................34 CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position values..............34 REM615 Point List Manual...
  • Page 10 DR.RDRE1 Disturbance recorder values.......36 LD0.RESCMMXU1 Residual current (1)........36 LD0.RESVMMXU1 Residual voltage (1)........36 LD0.VMMXU1 Voltage measurement ........37 LD0.VSMSQI1 Sequence of voltage measurement....37 LD0.XRGGIO130 RTD inputs..........37 Section 3 DNP3 protocol implementation........39 DNP3 device profile................39 DNP3 implementation table..............41 Section 4 Glossary.................45 REM615 Point List Manual...
  • Page 11: Section 1 Introduction

    The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also REM615 Point List Manual...
  • Page 12: Document Revision History

    B/2010-06-11 Content updated to correspond to the product version C/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual...
  • Page 13: Symbols And Conventions

    Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. REM615 Point List Manual...
  • Page 14: Functions, Codes And Symbols

    Section 1 1MRS756880 C Introduction 1.4.3 Functions, codes and symbols Table 1: REM615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1) protection, low stage Three-phase non-directional overcurrent PHIPTOC1 3I>>> (1)
  • Page 15 Three-phase voltage measurement VMMXU1 Residual voltage measurement RESVMMXU1 Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0 Three-phase power and energy measurement PEMMXU1 P, E P, E RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD) Frequency measurement FMMXU1 REM615 Point List Manual...
  • Page 17: Section 2 Dnp3 Data Mappings

    DNP3 data mappings Overview This document describes the DNP3 data points and structures available in REM615 Ver.4.0. The data points are unmapped as a default on the DNP3 level.The point lists describe a superset of all data available through the standard configuration A, B, and C including the optional functionalities.
  • Page 18 SEQRFUF1 ● ● MDSOPT1 ● ● ● RDRE1 ● ● ● CMMXU1 ● ● ● CSMSQI1 ● ● ● RESCMMXU1 ● ● ● VMMXU1 ● ● RESVMMXU1 ● VSMSQI1 ● ● Table continues on next page REM615 Point List Manual...
  • Page 19: Point List For Rem615 Ver.4.0 Me01-03

    ● XRGGIO130 FMMXU1 ● ● ● = available in the device variant, o = optionally available in the device variant Point list for REM615 Ver.4.0 ME01-03 2.3.1 Binary inputs Table 3: Explanations of the binary input table columns Column name...
  • Page 20: Ld0.Arcsarc3 Fault Arc Protection Stage 3

    SA name Description Values CTRL.DCCILO1 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled .ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed CTRL.DCCSWI1 .Pos.stSeld SELECTED CB selected 1=Selected CTRL.DCXSWI1 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked REM615 Point List Manual...
  • Page 21: Ctrl.dxxxxx2 Controllable Disconnector (2)

    .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked 2.3.1.8 CTRL.CCRDIF1 Current circuit failure protection Table 11: CTRL.CCRDIF1 Current circuit failure protection IEC 61850 name SA name Description Values CTRL.CCRDIF1 .Alm.stVal FAIL Fail Alarm 1=Alarm .Op.general ALARM Fail Operate 1=Operate REM615 Point List Manual...
  • Page 22: Ld0.Cmmxu1 Phase Currents (1) Limit Supervision

    - low stage 1 Table 15: LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1 IEC 61850 name SA name Description Values LD0.EFLPTOC1 Low stage (1) .Op.general OPERATE -Operate 1=Operate .Str.general START -Start 1=Start REM615 Point List Manual...
  • Page 23: Ld0.Emsgapc1 Emergency Start

    Underfrequency .Op.general OPR_UFRQ -Operate 1=Operate LD0.FRPFRC2 Frequency gradient .Op.general OPR_FRG -Operate 1=Operate 2.3.1.16 LD0.JAMPTOC1 Stalled motor protection Table 19: LD0.JAMPTOC1 Stalled motor protection IEC 61850 name SA name Description Values LD0.JAMPTOC1 .Op.general OPERATE Stage operate 1=Operate REM615 Point List Manual...
  • Page 24: Ld0.Ledggio1 Lhmi Led Indications

    1=Start .Str.phsC -phsC Start 1=Start 2.3.1.19 CTRL.LLN0 Local/remote state (also present in DNP IIN-bits) Table 22: CTRL.LLN0 Local/remote state (also present in DNP IIN-bits) IEC 61850 name SA name Description Values CTRL.LLN0 .Loc.stVal Remote/Local state 0/1=Rem/Loc REM615 Point List Manual...
  • Page 25: Ld0.Lln0 Settings Supervision

    LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 27: LD0.MAPGAPC3 Multipurpose analog protection function (3) IEC 61850 name SA name Description Values LD0.MAPGAPC3 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REM615 Point List Manual...
  • Page 26: Ld0.Mapgapc4 Multipurpose Analog Protection Function (4)

    1=Warning 2.3.1.29 LD0.MNSPTOC1 Negative-sequence overcurrent protection for motors (1) Table 32: LD0.MNSPTOC1 Negative-sequence overcurrent protection for motors (1) IEC 61850 name SA name Description Values LD0.MNSPTOC1 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start REM615 Point List Manual...
  • Page 27: Ld0.Mnsptoc2 Negative-Sequence Overcurrent Protection For Motors (2)

    LD0.MVGAPC2 Multipurpose binary inputs (2) Table 36: LD0.MVGAPC2 Multipurpose binary inputs (2) IEC 61850 name SA name Description Values LD0.MVGAPC2 .Q1.stVal Input 1 signal 0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On Table continues on next page REM615 Point List Manual...
  • Page 28: Ld0.Nsptov1 Negative-Sequence Overvoltage Protection - Stage 1

    1=Start 2.3.1.37 LD0.PHPTUV1 Phase undervoltage protection - stage 1 Table 40: LD0.PHPTUV1 Phase undervoltage protection - stage 1 IEC 61850 name SA name Description Values LD0.PHPTUV1 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start REM615 Point List Manual...
  • Page 29: Ld0.Psptuv1 Positive-Sequence Undervoltage Protection - Stage 1

    .HiWrn.stVal HIGH_WARN High warning 1=Warning 2.3.1.42 LD0.RESVMMXU1 Residual voltage limit supervision Table 45: LD0.RESVMMXU1 Residual voltage limit supervision IEC 61850 name SA name Description Values LD0.RESVMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning REM615 Point List Manual...
  • Page 30: Ld0.Seqrfuf1 Fuse Failure Protection

    .APwrLO.stVal IPOW_LO Iyt lockout 1=Lockout .CBLifAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm .LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm .OpnAlm.stVal TRV_T_OP_ALM Cls travel time alarm 1=Alarm Table continues on next page REM615 Point List Manual...
  • Page 31: Ld0.Sttpmsu1 Motor Startup Supervision

    Values LD0.TCSSCBR2 .CirAlm.stVal ALARM Supervision alarm 1=Alarm 2.3.1.49 LD0.TRPPTRC1 Global conditioning (1) Table 52: LD0.TRPPTRC1 Global conditioning (1) IEC 61850 name SA name Description Values LD0.TRPPTRC1 .Op.general Operate input signal 1=Operate .Tr.general Trip output signal 1=Trip REM615 Point List Manual...
  • Page 32: Ld0.Trpptrc2 Global Conditioning (2)

    XRGGIO130 Warning 1=Warning 2.3.1.53 LD0.XAGGIO130 Physical I/O Table 56: LD0.XAGGIO130 Physical I/O IEC 61850 name SA name Description Values LD0.XAGGIO130 .Ind1.stVal X130-Input 1 1/0=ON/OFF .Ind2.stVal X130-Input 2 1/0=ON/OFF .Ind3.stVal X130-Input 3 1/0=ON/OFF .Ind4.stVal X130-Input 4 1/0=ON/OFF REM615 Point List Manual...
  • Page 33: Ld0.Xggio100 Physical I/O

    X110-Output 4 1/0=ON/OFF 2.3.1.56 LD0.XGGIO120 Physical I/O Table 59: LD0.XGGIO120 Physical I/O IEC 61850 name SA name Description Values LD0.XGGIO120 .Ind1.stVal X120-Input 1 1/0=ON/OFF .Ind2.stVal X120-Input 2 1/0=ON/OFF .Ind3.stVal X120-Input 3 1/0=ON/OFF .Ind4.stVal X120-Input 4 1/0=ON/OFF REM615 Point List Manual...
  • Page 34: Binary Outputs

    SA name Description Type CTRL.DCCSWI2 .Pos.Oper.ctlVal Disconnector control On/Off 2.3.2.4 CTRL.ESCSWI2 Controllable earth switch (1) control Table 64: CTRL.ESCSWI2 Controllable earth switch (1) control IEC 61850 name SA name Description Type CTRL.ESCSWI1 .Pos.Oper.ctlVal Earth switch control On/Off REM615 Point List Manual...
  • Page 35: Ld0.Dnpggio1 Parameter Setting Group Control

    IEC 61850 name SA name Description Type LD0.PEMMXU1 .SupDmdRs.Oper.ctlVal RSTACM Reset accum. energy 2.3.2.8 DR.RDRE1 Disturbance recorder Table 68: DR.RDRE1 Disturbance recorder IEC 61850 name SA name Description Type DR.RDRE1 .MemClr.Oper.ctlVal Clear all records .RcdTrg.Oper.ctlVal Trig recording REM615 Point List Manual...
  • Page 36: Ld0.Spcggio1 Multipurpose Binary Outputs (1)

    IEC 61850 name SA name Description Type LD0.SPCGGIO2 .SPCS01.ctlVal Output 1 control On/Off .SPCS02.ctlVal Output 2 control On/Off .SPCS03.ctlVal Output 3 control On/Off .SPCS04.ctlVal Output 4 control On/Off .SPCS05.ctlVal Output 5 control On/Off Table continues on next page REM615 Point List Manual...
  • Page 37: Ld0.Srgapc1 Multipurpose Binary Outputs - Flip-Flop Resets (1)

    SA name Description Type LD0.SRGAPC1 .Rs1.ctlVal Reset flip-flop 1 .Rs2.ctlVal Reset flip-flop 2 .Rs3.ctlVal Reset flip-flop 3 .Rs4.ctlVal Reset flip-flop 4 .Rs5.ctlVal Reset flip-flop 5 .Rs6.ctlVal Reset flip-flop 6 .Rs7.ctlVal Reset flip-flop 7 .Rs8.ctlVal Reset flip-flop 8 REM615 Point List Manual...
  • Page 38: Ld0.Sscbr1 Reset Signals Of Cb Condition Monitoring

    LD0.CMMXU1 Phase currents (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.CMMXU1 Phase-to-ground current .A.phsA.instCVal.mag I_INST_A -phsA magnitude 0.00..40.0 [xIn] 0,40,0,4000 .A.phsB.instCVal.mag I_INST_B -phsB magnitude 0.00..40.0 [xIn] 0,40,0,4000 .A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] 0,40,0,4000 REM615 Point List Manual...
  • Page 39: Ld0.Csmsqi1 Sequence Of Currents

    CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position values Table 81: CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.DCXSWI1 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REM615 Point List Manual...
  • Page 40: Ctrl.dcxswi2 Controllable Disconnector 2, 4-Pole (2 Bit) Position Values

    Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 2.3.3.12 LD0.DNPGGIO1 Active parameter setting group Table 86: LD0.DNPGGIO1 Active parameter setting group IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.DNPGGIO1 .ActSG.stVal Active setting group 1…6 1,6,1,6 REM615 Point List Manual...
  • Page 41: Ld0.Fmmxu1 Frequency Measurement

    Num.of watchdog resets 0…65535 0,65535,0,65535 .WrmStr.stVal Num.of warm starts 0…65535 0,65535,0,65535 2.3.3.16 LD0.MPTTR1 Thermal protection Table 90: LD0.MPTTR1 Thermal protection IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.MPTTR1 .TmpRl THERM_LEVEL Thermal level -99….999 -99,999,-99,999 REM615 Point List Manual...
  • Page 42: Ld0.Pemmtr1 Power Measurement And Accumulated Power Values

    LD0.RESCMMXU1 .A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] 0,40,0,4000 2.3.3.20 LD0.RESVMMXU1 Residual voltage (1) Table 94: LD0.RESVMMXU1 Residual voltage (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESVMMXU1 0.00..4.00 .PhV.res.instCVal.mag U0_INST Residual voltage [xUn] 0,4,0,400 REM615 Point List Manual...
  • Page 43: Ld0.Vmmxu1 Voltage Measurement

    .AnIn2.instMag AI_VAL2 RTD input 2 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn3.instMag AI_VAL3 RTD input 3 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn4.instMag AI_VAL4 RTD input 4 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn5.instMag AI_VAL5 RTD input 5 10000 -1E4,1E4,-1E4,1E4 Table continues on next page REM615 Point List Manual...
  • Page 44 DNP3 data mappings IEC 61850 name SA name Description Values Arg 1,2,3,4 -10000… .AnIn6.instMag AI_VAL6 RTD input 6 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn7.instMag AI_VAL7 RTD input 7 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn8.instMag AI_VAL8 RTD input 8 10000 -1E4,1E4,-1E4,1E4 REM615 Point List Manual...
  • Page 45: Section 3 Dnp3 Protocol Implementation

    Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 98: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: REM615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
  • Page 46 Only non-time-tagged ○ Binary input change with relative time ● Configurable to send one or the other ● Configurable Sends unsolicited responses: Sends static data in unsolicited responses: ● Never ● Never Table continues on next page REM615 Point List Manual...
  • Page 47: Dnp3 Implementation Table

    (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08 are responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 are responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. REM615 Point List Manual...
  • Page 48 17, 28 (index) 32-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) Table continues on next page REM615 Point List Manual...
  • Page 49 Time and 129 (response) 07 (limited qty) date CTO 130 (unsol. resp) (qty = 1) Unsynchro 129 (response) 07 (limited qty) nized time 130 (unsol. resp) (qty = 1) and date Table continues on next page REM615 Point List Manual...
  • Page 50 17 or 28 are always responded.) 3) Writes of internal indications are only supported for index 7 (Restart IIN1-7) 4) Cold and warm restarts return an application layer acknowledge, but no restart action is taken. REM615 Point List Manual...
  • Page 51: Section 4 Glossary

    Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LHMI Local human-machine interface PCM600 Protection and Control IED Manager Select-before-operate REM615 Point List Manual...
  • Page 56 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...