IMPORTANT WARNINGS AND SAFETY PRECAUTIONS
For units intended for use in other than single-family dwellings, a clearly labeled emergency switch shall
be provided as part of the installation. The switch shall be readily accessible to the occupants and shall
be installed at least 10 feet (3.05 m) away, adjacent to, and within sight of, the unit.
Except for listed spa-side remote controls, install a minimum of five (5) feet from the inside wall of the
pool and spa.
TO PREVENT ELECTROCUTION: INSTALL THE POWER CENTER OR LOAD CENTER AT LEAST
FIVE (5) FEET (1.2M) FROM INSIDE WALL OF POOL OR SPA.
Two Speed Pump Controls Notice (Title 20 Compliance)
Please read the following important Safety Instructions (See page 42 for pump speed setup)
When using two-speed pumps manufactured on or after January 1, 2008, the pump's default circulation speed MUST be
set to the LOWEST SPEED, with a high speed overide capability being for a temporary period not to exceed one normal
cycle, or two hours, whichever is less.
Important Installation Information
. All work must be performed by a licensed electrician, and must conform to all national, state,
1
and local codes. The electrical supply for this product must include a suitably rated switch or
circuit breaker to open all ungrounded supply conductors to comply with National Electrical
Code (NEC), NFPA 70 (including Artical 680) or the Canadian Electrical Code (CEC), CSA
C22.1. The disconnecting means must be readily accessible to the tub occupant but
installed at least 5 ft. (1.52 m) from the inside wall of the Pool, Spa, or Hot Tub.
2. Install to provide drainage of compartment for electrical components.
3. Install enclosure with conduit holes down.
4. If this system is used to control underwater lighting fixtures, a ground-fault circuit interrupter
(GFCI) must be provided for these fixtures. Conductors on the load side of the ground-fault
circuit-interrupter shall not occupy conduit, junction boxes or enclosures containing other
conductors unless such conductors are also protected by a ground-fault circuit-interrupter.
Refer to local codes for details.
5. A terminal bar stamped
electric shock, this terminal must be connected to the grounding means provided in the
electric supply service panel with a continuous copper wire equivalent in size to the circuit
conductors supplying this equipment (no smaller than 12 AWG or 3.3 mm). The bonding
lug(s) provided on this unit are intended to connect a minimum of one No. 8 AWG for US
installation and two No. 6 AWG for Canadian installations solid copper conductor between
this unit and any metal equipment, metal enclosures or electrical equipment, metal water
pipe, or conduit within 5 feet (1.5 m) of the unit.
6. Use 14 AWG to 6 AWG, 60° / 75° C Copper conductors for all field wiring.
7. Electrical rating: 120/240 VAC 150 AMP Single Phase (3 wire).
8. The input line to the control panel should be protected by a 240 VAC CIRCUIT BREAKER
rated at NO MORE then 150 Amperes maximum.
is located inside the supply terminal box. To reduce the risk of
Compool/EasyTouch Pool and Spa Control System Upgrade Installation and User's Guide
v