Piping Connection - Haier AB092ACERA Operation And Installation Manual

Cassette type air conditioner dc inverter
Table of Contents

Advertisement

Installation Procedures

Piping Connection

Flare connection
Indoor
Unit
(1) Dimension of connecting pipe
Gas pipe
Liquid pipe
Fit the nut on and fasten
(2) The maximum length and drop height of connecting pipe
The maximum length is 20m
The maximum drop height is 10m.
To ensure the efficiency ,Pipes shall be as short as possible.
Cautions for piping connection
Do not twist or deform the connecting pipe.
Do not mix dusts.
The bending radius shall be as large as possible.
Both gas pipe and liquid pipe shall be heat insulation.
No leakage in the flare.
(3) Piping connection
Connecting method
Smear refrigerant oil on the joints of piping and flare.
The bending radius shall be as large as possible.
Align the pipe center when fastening, and tighten the
nut, as shown in the figure.
Pay attention to not mix foreign matters such as sands
in.
Gas pipe
Liquid
pipe
Flare connection
12.7mm
6.35mm
18
3-way valve
Outdoor
unit
2-way valve
Spanner
Spanner
Diameter of Pipe
Liquid Pipe 6.35mm
Gas Pipe 12.7mm
If not aligned ,tighten the nut by force will
damage the nut that result in gas leakage
Joint
N u t
Tighten Torque
(N. m)
11.8
49.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ab142aceraAb182acera

Table of Contents