Inverter Rating - Mitsubishi Electric FR-A806 Instruction Manual

Table of Contents

Advertisement

Inverter rating

6.1
Inverter rating
Model FR-A846-[]
0.75 1.5
Applicable
LD
motor capacity
ND
0.4
(kW)

(initial setting)
1.6
LD
Rated
capacity
ND
1.1
(kVA)

(initial setting)
2.1
LD
Rated
ND
current (A)
1.5
(initial setting)
120% 60 s, 150% 3 s (inverse-time characteristics) at ambient temperature of 40°C
LD
Overload
current
ND
150% 60 s, 200% 3 s (inverse-time characteristics) at ambient temperature of 40°C
rating

(initial setting)
Three-phase 380 to 500 V
Rated voltage

Maximum
Regenerative
10% torque/continuous
brake torque
braking

Rated input AC voltage/
Three-phase 380 to 500 V 50 Hz/60 Hz
frequency
Permissible AC voltage
323 to 550 V 50 Hz/60 Hz
fluctuation
Permissible frequency
±5%
fluctuation
2.1
LD
Rated input
ND
current (A)
1.5

(initial setting)
Power
1.6
LD
supply
capacity
ND
1.1
(kVA)
(initial setting)

Dust- and water-proof type (IP55)
IEC 60529
Protective
structure
UL Type12
UL50
Self cooling + internal fan
Cooling system
Built-in
DC reactor
15
Approx. mass (kg)

The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.

The rated output capacity indicated assumes that the output voltage is 440 V.

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about

Value for the ND rating.

The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor
and cables) affects the rated input current.

The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of
the input reactor and cables).

For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For the details, refer to the Instruction Manual (Detailed).)

UL Type 12 Enclosure-Suitable for Installation in a Compartment Handling Conditioned Air (Plenum)
 For compliance with IP55, remove the protective bushes and install the recommended cable glands.
128
SPECIFICATIONS
00023
00038
00052
00083
00126
(0.4K)
(0.75K)
(1.5K)
(2.2K)
(3.7K)
2.2
3.7
5.5
7.5
0.75 1.5
2.2
3.7
5.5
2.7
3.7
5.8
8.8
12
1.9
3
4.6
6.9
9.1
3.5
4.8
7.6
11.5 16
2.5
4
6
9
12
3.5
4.8
7.6
11.5 16
2.5
4
6
9
12
2.7
3.7
5.8
9
12
1.9
3
4.6
6.9
9

15
15
15
16
17
00170
00250
00310
00380
00470
(5.5K)
(7.5K)
(11K)
(15K)
(18.5K)
11
15
18.5 22
30
7.5
11
15
18.5 22
18
22
27
33
43
13
18
24
29
34
23
29
35
43
57
17
23
31
38
44

23
29
35
43
57
17
23
31
38
44
18
22
27
33
43
13
18
24
29
34

Forced-air-cooling + internal fan
26
26
27
27
59
00620
00770
00930
01160
01800
(22K)
(30K)
(37K)
(45K)
(55K)
37
45
55
75
90
30
37
45
55
75
53
65
81
110 137 165 198 248
43
54
66
84
110 137 165 198
70
85
106 144 180 216 260 325
57
71
86
110 144 180 216 260
70
85
106 144 180 216 260 325
57
71
86
110 144 180 216 260
53
65
81
110 137 165 198 248
43
54
66
102 110 137 165 198
60
63
64
147 150 153 189 193
02160
02600
03250
03610
(75K)
(90K)
(110K)
(132K)
110 132 160
90
110 132
.