Installer setup (ISU)
1 Press and hold CENTER and
approximately 3 seconds to enter advanced
menu.
2 Press Select to enter ISU.
3 Press Select to cycle through menu setup
options.
4 Press
or
from available options.
5 Press Select and confirm your settings or
press Back to ignore changes and return
to ISU menu screen to continue editing
another setup option.
6 To finish setup process and save your
setting, press Home and return to Home
screen.
NOTE: A complete list of all setup (ISU)
parameters and options starts below and
continues through page 16.
Advanced setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
# ISU
ISU Name
120
Scheduling Options
125
Temperature Indication Scale
200
Heating System Type
buttons for
to change values or select
ISU Options (factory default in bold)
0 = Non-Programmable
2 = 5-2 Programmable
3 = 5-1-1 Programmable
4 = 7-Day Programmable
Note: You can change default MO-FR, SA-SU schedule here.
To edit periods during days, temperature setpoints, or to turn
Schedule On/Off, touch MENU and go to SCHEDULE.
0 = Fahrenheit
1 = Celsius
1 = Conventional Forced Air Heat
2 = Heat Pump
3 = Radiant Heat
5 = None (Cool Only)
Note: This option selects the basic system type your thermostat
will control.
13
MCR36535
MCR36520

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the T4 Pro Series and is the answer not in the manual?

Questions and answers

Rod
February 7, 2025

How to turn system on

1 comments:
Mr. Anderson
February 11, 2025

The Honeywell Home T4 Pro Series thermostat system turns on automatically when properly wired and powered. Ensure the thermostat is installed correctly and connected to power. If the system does not turn on, check the wiring, power source, and ensure the C-wire (common wire) is connected if required. If the system is in a delay mode, wait for the built-in compressor protection time to elapse before it starts operating.

This answer is automatically generated

This manual is also suitable for:

Th4110u2005Th4210u2002

Table of Contents

Save PDF