DMS-R-IM
4.7.1

View and Change Tank Temperature Settings

Follow instruction below to view and change tank temperature settings:
Step
1
2
3
April 7, 2021
Description
Log into Engineer or
Maintenance level. Refer
section 4.5 Login & Logout for
procedure.
At Main Menu screen, press on
[Temperature Control] button.
Temperature Control screen as
shown will prompt.
These screen will displays:
 Present Value – real time
display current temperature.
 Temp. Set Point (F) –
optimum operating
temperature. Temperature
setting range is 70°F to 175°F
(20°C to 80°C).
 Temp. Low Alarm (F) –
lowest operating
temperature. Temperature
setting range 45°F to 200°F
(5°C to 95°C).
 Temp. High Alarm (F) –
highest operating
temperature. Temperature
setting range is 45°F to 200°F
(5°C to 95°C).