Epi2809 - Technical Data - Beckhoff EPI2 Series Documentation

Io-link-box modules with digital inputs
Hide thumbs Also See for EPI2 Series:
Table of Contents

Advertisement

The signal state is indicated by means of light emitting diodes. The signals are connected via M8 connectors
(EPI2809-0021) or M12 connectors (EPI2809-0022). All outputs are short-circuit-proof and protected against
inverse connection.
Quick links
Installation
2.3.2

EPI2809 - Technical data

Technical data
Communication
Data transfer rate
IO-Link connection
Specification version
Requirements IO-Link Master
Number of outputs
Output connections
Load type
Rated output voltage
Output current
Short circuit current
Module electronic current
consumption
Output driver current
consumption
Module electronic supply
Output driver supply
Process image
Electrical isolation
Permissible ambient temperature
during operation
Permissible ambient temperature
during storage
Vibration / shock resistance
EMC resistance / emission
Protection class
Installation position
Approvals
EPI2xxx
EPI2809-0021
IO-Link
230,4 kBaud (COM 3)
1 x M12 connector, a-coded
IO-Link V1.1, Class B
V1.1
16
M8
ohmic, inductive, lamp load
24 V
(-15%/+20%)
DC
max. 0.5 A each channel, total current of all outputs max. 4 A
max. 4.0 A
typically 100 mA from L
+
typically 20 mA
L
+
2L
+
16 output bits
Control voltage / communication: yes
-25°C ... +60°C
-40°C ... +85°C
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP65, IP66, IP67 (conforms to EN 60529)
variable
CE
Version: 1.1.0
Product overview
EPI2809-0022
M12
-25°C ... +60°C
CE
13

Advertisement

Table of Contents
loading

Table of Contents