▼ Minimum room volume
In accordance with EN 378-1 -2017 standard
(Refrigerating systems and heat pumps - Safety and
environmental requirements), the
unit and all refrigeration connections passing through
inhabited areas must comply with the minimum room
volume requirements shown hereafter (voir
The minimum volume of a room (in m3) is calculated
using the formula: "fl uid fi ll load" (in kg) / 0.3.
Alternatively, you must ensure that :
- The location has natural ventilation through another
room where the combined volume of the two rooms
is greater than "liquid fi ll load" (in kg) / 0.3kg/m
Ventilation between the two rooms is ensured by
openings of at least: see
- Or that the location is mechanically ventilated:
• Minimum fl ow rate of 165m3/H;
• Extraction at less than 0.20m from the fl oor.
- 22 -
ystem's hydraulic
fi g.
23) :
fi g. 24
and
fi g.
25.
Refrigeration connections
Length
R32 gas
charge
15 m
min room
volume
R32 gas
charge
16 m
min room
volume
R32 gas
charge
17 m
min room
volume
.
3
R32 gas
charge
20 m
min room
volume
R32 gas
charge
21 m
min room
volume
R32 gas
charge
22 m
min room
volume
R32 gas
charge
23 m
min room
volume
R32 gas
charge
25 m
min room
volume
R32 gas
charge
30 m
min room
volume
fi g. 23 - Minimum room volume
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN
Modele (kW)
5, 6
8
g
970
1020
m
3.2
3.4
3
g
995
1045
m
3.3
3.5
3
g
1020
1070
m
3
3.4
3.6
g
1095
1145
m
3.65
3.8
3
g
1120
1170
m
3.73
3.9
3
g
1145
1195
m
3
3.82
3.98
g
1170
1220
m
3
3.9
4.1
g
1220
1270
m
4.1
4.2
3
g
1345
1395
m
4.5
4.7
3
10
1630
5.4
1630
5.4
1630
5.4
1630
5.4
1650
5.5
1670
5.57
1690
5.6
1730
5.8
1830
6.1