The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and W/T3 directly to the AC mains circuit power supply. Ground the VFD-G using the ground terminal. The grounding method must comply with the laws of the country where the AC motor drive is to be installed.
Page 5
WARNING! DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor drive is easily damaged by high-pressure. There are highly sensitive MOS components on the printed circuit boards. These components are especially sensitive to static electricity. To prevent damage to these components, do not touch these components or the circuit boards with metal objects or your bare hands.
2.3 Main Circuit Connection...2-3 2.4 Control Terminals ...2-3 2.5 Specification for main circuit terminals and control terminals...2-3 2.6 Wiring Explanation for Analog Input Terminal...2-3 Chapter 3 Keypad and Start Up ...3-3 3.1 Digital Keypad VFD-PU01 ...3-3 3.1.1 Description of the Digital Keypad ... 3-3 3.1.2 How to Operate the Digital Keypad VFD-PU01 ...
5.9 Motor cannot Run... 5-3 5.10 Motor Speed cannot be Changed... 5-3 5.11 Motor Stalls during Acceleration... 5-3 5.12 The Motor does not Run as Expected ... 5-3 5.13 Electromagnetic/Induction Noise ... 5-3 5.14 Environmental Condition ... 5-3 5.15 Affecting Other Machines ... 5-3 Chapter 6 Fault Code Information and Maintenance...
B.6.2 Explanation of Display Message ...B-3 B.6.3 PU06 Operation Flow Chart ...B-3 Appendix C How to Select the Right AC Motor Drive ... C-3 C.1 Capacity Formulas ... C-3 C.2 General Precaution ... C-3 C.3 How to Choose a Suitable Motor... C-3...
1.1 Receiving and Inspection This VFD-G AC motor drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC motor drive, please check for the following: Check to make sure that the package includes an AC motor drive, the User Manual/Quick Start and CD, dust covers and rubber bushings.
Chapter 1 Introduction| 1.1.3 Series Number Explanation 075F43AG4 T 7 01 0001 460V 3-PHASE 10HP(7.5kW) If the nameplate information does not correspond to your purchase order or if there are any problems, please contact your distributor. 1.1.4 Drive Frames Frame Power Range 7.5-20HP (5.5-15kW) 25-40HP (18.5-30kW)
Page 12
Chapter 1 Introduction| 50-125HP/37-90kW(Frame E, E1) 150-215HP/110-160kW(Frame G) 250-300HP/185-220kW(Frame H) Revision July 2008, EG03, SW V1.06...
1.4 Lifting Please carry only fully assembled AC motor drives as shown in the following. For 50-125HP (Frame E, E1) Step 1 Step 3 Revision July 2008, EG03, SW V1.06 Chapter 1 Introduction| Step 2 Step 4...
Chapter 1 Introduction| 1.5 Preparation for Installation and Wiring 1.5.1 Ambient Conditions Install the AC motor drive in an environment with the following conditions: Air Temperature: Relative Humidity: Atmosphere Operation pressure: Installation Site Altitude: Vibration: Temperature: Relative Humidity: Storage Atmosphere Transportation pressure: Vibration:...
Page 20
CAUTION! Operating, storing or transporting the AC motor drive outside these conditions may cause damage to the AC motor drive. Failure to observe these precautions may void the warranty! Mount the AC motor drive vertically on a flat vertical surface object by screws. Other directions are not allowed.
After removing the front cover, check if the power and control terminals are clear. Be sure to observe the following precautions when wiring. General Wiring Information Applicable Codes All VFD-G series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters Laboratories (cUL) listed, and therefore comply with the requirements of the National Electrical Code (NEC) and the Canadian Electrical Code (CEC).
Page 25
Users must connect wires according to the circuit diagrams on the following pages. Do not plug a modem or telephone line to the RS-485 communication port or permanent damage may result. Pins 1 & 2 are the power supply for the optional copy keypad only and should not be used for RS-485 communication.
Page 26
For 460V series, 20hp and below R/L1 S/L2 T /L3 Recommended C ircui t when power s upply is turned O FF by a O FF fault output E.F. F WD/ST OP REV/STO P Multi-s tep1 F ac tor y Multi-s tep2 Setting Multi-s tep3...
Page 27
Chapter 2 Installation and Wiring| For 460V series, 25hp and above R/L1 S/L2 T /L3 Recommended C ircui t when power s upply is turned O FF by a O FF fault output E.F. F WD/ST OP REV/STO P Multi-s tep1 F ac tor y Multi-s tep2 Setting...
Page 28
Wiring for SINK mode and SOURCE mode SINK Mode SOURCE Mode Sink Source CAUTION! The wiring of main circuit and control circuit should be separated to prevent erroneous actions. Please use shield wire for the control wiring and not to expose the peeled-off net in front of the terminal.
Page 29
Chapter 2 Installation and Wiring| With long motor cables, high capacitive switching current peaks can cause over-current, high leakage current or lower current readout accuracy. To prevent this, the motor cable should be less than 20m for 3.7kW models and below. And the cable should be less than 50m for 5.5kW models and above.
AC line disturbances (surges, switching spikes, short interruptions, etc.). AC line reactor should be installed when the power supply capacity is ≧500kVA or phase lead reactor will be switched. And the mains wiring distance Please refer to Appendix B for more details.
Chapter 2 Installation and Wiring| 2.3 Main Circuit Connection For 460V series, 20hp and below R/L1 S/L2 T /L3 For 460V series, 25hp and above R/L1 S/L2 T /L3 Terminal Symbol R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 +1, +2 +2/B1~B2 +2~ -, +2/B1~ - DC Reactor Br ak e Resistor...
Page 32
CAUTION! Mains power terminals (R/L1, S/L2, T/L3) Connect these terminals (R/L1, S/L2, T/L3) via a non-fuse breaker or earth leakage breaker to 3- phase AC power (some models to 1-phase AC power) for circuit protection. It is unnecessary to consider phase-sequence. It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off power quickly and reduce malfunction when activating the protection function of AC motor drives.
Page 33
Chapter 2 Installation and Wiring| To improve the power factor and reduce harmonics, connect a DC reactor between terminals [+1, +2(+2/B1)]. Please remove the jumper before connecting the DC reactor. Models of 18.5kW~160kW have a built-in DC reactor; models of 185kW~220kW have a built-in AC reactor.
2.4 Control Terminals Terminal Terminal Function Symbol Forward-Stop command Reverse-Stop command External fault Multi-function Input 1 Multi-function Input 2 Multi-function Input 3 Multi-function Input 4 +24V DC Voltage Source Digital Signal Common AFM1 Analog output meter 1 AFM2 Analog output meter 2 Analog control signal common Used as common for analog outputs.
Page 35
Chapter 2 Installation and Wiring| Terminal Terminal Function Symbol +12V/ACM Potentiometer power source Analog voltage/current Input Analog voltage/current Input AC1/AC2 Analog control signal common Used as common for analog inputs. Analog inputs (AI1, AI2, AC1, AC2) Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible (<20m) with proper grounding.
Page 36
General Keep control wiring as far away as possible from the power wiring and in separate conduits to avoid interference. If necessary let them cross only at 90º angle. The AC motor drive control wiring should be properly installed and not touch any live power wiring or terminals.
Chapter 2 Installation and Wiring| 2.5 Specification for main circuit terminals and control terminals 7.5 HP to 20 HP (VFD055F43B-G, VFD075F43B-G, VFD110F43A-G, VFD150F43A-G) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 30Kgf-cm (26 in-lbf) Wire: 12-8 AWG Wire Type: Stranded copper only, 75°...
Page 38
Chapter 2 Installation and Wiring| 25 HP to 40 HP (VFD185F43A-G, VFD220F43A-G, VFD300F43A-G) R/L1 T/L3 +1 S/L2 V/T2 W/T3 ( ) + - ( ) POWER MOTOR Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 30Kgf-cm (26 in-lbf) Wire: 8-2 AWG Wire Type: Stranded copper only, 75°...
Page 39
Chapter 2 Installation and Wiring| 50 HP to 60 HP (VFD370F43A-G, VFD450F43A-G) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 57kgf-cm (49.5 in-lbf) min. Wire: VFD370F43A-G: 3AWG VFD450F43A-G: 2AWG Wire Type: Stranded copper only, 75° C 2-16 POWER ALARM...
Page 40
75 HP to 125 HP (VFD550F43A-G, VFD750F43A-G, VFD900F43C-G) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 200kgf-cm (173 in-lbf) Wire: VFD550F43A-G: 1/0-4/0 AWG VFD750F43A-G: 3/0-4/0 AWG VFD900F43C-G: 4/0 AWG Wire Type: Stranded copper only, 75°C Revision July 2008, EG03, SW V1.06 CHARGE R/L1 S/L2...
Page 41
Chapter 2 Installation and Wiring| 150 HP to 215 HP (VFD1100F43C-G, VFD1320F43A-G, VFD1600F43A-G) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 300kgf-cm (260 in-lbf) Wire: 1/0 AWG*2-300 MCM*2 Wire Type: Stranded copper only, 75°C 2-18 R/L1 S/L2 T/L3 U/T1...
Page 42
250 HP to 300 HP (VFD1850F43A-G, VFD2200F43A-G) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 408kgf-cm (354 in-lbf) Wire: 500 MCM (max) Wire Type: Stranded copper only, 75°C Revision July 2008, EG03, SW V1.06 Chapter 2 Installation and Wiring| R/L1 S/L2 T/L3 U/T1...
Chapter 2 Installation and Wiring| 2.6 Wiring Explanation for Analog Input Terminal When using analog input, please pay attention to the jumper on the control board. Whether the jumper is cut off or not is determined by analog input type (voltage or current). See the figure below and refer to the following explanation for more details.
Page 44
When using analog current input (0~1A), please plug into the left two pins (See the red mark), and make sure the jumper is connected well (See what the following yellow arrows point at). When using analog voltage input (0~10V), please transfer to the right two pins (See the red mark), and cut off the jumper (See what the following yellow arrows point at).
Page 45
Chapter 2 Installation and Wiring| This page intentionally left blank. 2-22 Revision July 2008, EG03, SW V1.06...
3.1 Digital Keypad VFD-PU01 3.1.1 Description of the Digital Keypad By pressing JOG key. Initiates jog operation. Left key moves cursor to the left UP and DOWN Key Sets the parameter number and changes the numerical data, such as Master Frequency. Display Message Display the AC drive Master Frequency.
Page 47
Chapter 3 Keypad and Start Up| Display Message Display “End” for approximately 1 second if input has been accepted. After a parameter value has been set, the new value is automatically stored in memory. To modify an entry, use the Display “Err”, if the input is invalid.
3.1.3 VFD-PU01 Dimensions 73.0 [2.87] 3.1.4 Reference Table for the LED Display of the Digital Keypad Digit Display English alphabet Display English alphabet Display English alphabet Display Revision July 2008, EG03, SW V1.06 19.0 [0.75] MODE PROG DATA STOP Chapter 3 Keypad and Start Up| 44.0 [1.73] M4* 0.7(2X) Unit: mm [inch]...
Chapter 3 Keypad and Start Up| 3.2 Operation Method The operation method can be set via communication, digital keypad and control terminals. Please choose a suitable method depending on application and operation rule. Operation Method Refer to the communication address Operate from the 2001H setting for details.
3.3 Trial Run you can perform a trial run by using digital keypad with the following steps. The factory setting of the operation source is from the keypad (Pr.02-01=00). After applying power, verify that LED “F” is on and the display shows 60.00Hz. Setting frequency to about 5Hz by using Pressing key for forward running.
Page 51
Chapter 3 Keypad and Start Up| This page intentionally left blank. Revision July 2008, EG03, SW V1.06...
Chapter 4 Parameters The VFD-G parameters are divided into 10 groups by property for easy setting. In most applications, the user can finish all parameter settings before start-up without the need for re-adjustment during operation. The 10 groups are as follows: Group 0: User Parameters Group 1: Basic Parameters Group 2: Operation Method Parameters...
Chapter 4 Parameters| 4.1 Summary of Parameter Settings : The parameter can be set during operation. Group 0 User Parameters Parameter Functions 00-00 Software Version 00-01 AC Drive Status Indication 1 Settings Read only 00: No Fault occurred 01: oc (over current) 02: ov(over voltage) 03: oH(over temperature) 04: oL(overload)
Page 54
Parameter Functions 00-02 AC Drive Status Indication 2 00-03 Frequency Setting (F) or Closed Loop Control Setting Point 00-04 Output Frequency (H) Read only 00-05 Output Current (A) 00-06 DC-BUS Voltage (U) 00-07 Output Voltage (E) 00-08 Output Power Factor 00-09 Output Power (kW) 00-10...
Page 55
Chapter 4 Parameters| Parameter Functions 00-13 User Target Value (High bit) uH 0-9999 00-14 PLC Time 00-15 Output Reactive Power (KVAR) Group 1 Basic Parameters Parameter Functions 01-00 Maximum Output Frequency 01-01 Maximum Voltage Frequency (Base Frequency) 01-02 Maximum Output Voltage 01-03 Mid-point Frequency...
Page 56
Parameter Functions 01-17 JOG Acceleration Time 01-18 JOG Deceleration Time 01-19 JOG Frequency 01-20 S Curve Delay Time in Accel 01-21 S Curve Delay Time in Decel 01-22 Modulation Index 01-23 Accel/Decel Time Unit 00: Unit is 1 Sec Group 2 Operation Method Parameters Parameter Functions 02-00...
Page 57
Chapter 4 Parameters| Parameter Functions 02-04 Forward/Reverse Enable 02-05 2-wire/3-wire Operation Control Modes 02-06 Line Start Lockout 02-07 Reserved 02-08 Start-up Display Selection 02-09 Special Display 02-10 User Defined Coefficient 02-11 Flying Start 02-12 Flying Start Frequency 02-13 Master Frequency Memory Setting Settings 00: Forward enabled...
Page 58
Group 3 Output Function Parameters Parameter Functions 03-00 Multi-function Output Terminal 1 (Relay) 03-01 Reserved 03-02 Master Frequency Attained 1 03-03 Master Frequency Attained 2 03-04 DC Fan Control 03-05 Analog Output Signal 03-06 Analog Output Signal 03-07 Analog Output Gain 1 01~200% 03-08 Analog Output Gain 2 01~200% 03-09...
Page 59
Chapter 4 Parameters| Group 4 Input Function Parameters Parameter Functions 04-00 Multi-function Input Terminal 1 04-01 Multi-function Input Terminal 2 04-02 Multi-function Input Terminal 3 04-03 Multi-function Input Terminal 4 04-04 Digital Input Terminal Response Time 04-05 Minimum AI1 Analog Input 04-06 Maximum AI1 Analog...
Page 60
Parameter Functions 04-14 2nd AI1 Gain 04-15 3rd AI1 Gain 04-16 4th AI1 Gain 04-17 5th AI1 Gain 04-18 1st AI2 Gain 04-19 2nd AI2 Gain 04-20 3rd AI2 Gain 04-21 4th AI2 Gain 04-22 5th AI2 Gain 04-23 Analog Input Delay 04-24 Analog Input Delay 04-25...
Page 61
Chapter 4 Parameters| Group 5 Multi-step Speed Parameters Parameter Functions 05-00 1st Step Speed Frequency 05-01 2nd Step Speed Frequency 05-02 3rd Step Speed Frequency 05-03 4th Step Speed Frequency 05-04 5th Step Speed Frequency 05-05 6th Step Speed Frequency 05-06 7th Step Speed Frequency...
Page 62
Parameter Functions 05-20 Time Duration Step 4 05-21 Time Duration Step 5 05-22 Time Duration Step 6 05-23 Time Duration Step 7 05-24 Time Duration Step 8 05-25 Time Duration Step 9 05-26 Time Duration Step 10 0.0 to 65500 Sec / 0.0~6550.0 Sec 05-27 Time Duration Step 11 0.0 to 65500 Sec / 0.0~6550.0 Sec 05-28...
Page 63
Chapter 4 Parameters| Parameter Functions 06-06 Electronic Thermal Relay Selection 06-07 Electronic Thermal Characteristic 06-08 Low Current Detection Level 06-09 Low Current Detection Time 06-10 Low Current Detection Treatment 06-11 Present Fault Record 06-12 Second Most Recent Fault Record 06-13 Third Most Recent Fault Record 06-14...
Page 64
Parameter Functions 06-15 Parameter Reset 06-16 Parameter Protection Password Input 06-17 Parameter Protection Password Setting Group 7 AC Drive and Motor Parameters Parameter Functions 07-00 Identity Code of AC Drive 07-01 Rated Current of AC Drive 07-02 Full-load Current of Motor 07-03 No-load Current of...
Page 65
Chapter 4 Parameters| Parameter Functions 07-08 Calculate Total Running Time of the Motor (Min) 07-09 Calculate Total Running Time of the Motor (Day) 07-10 Electric Bill for One Time 07-11 Accumulated Electric Bill (per currency unit) 07-12 Accumulated Electric Bill (per 10 currency unit) 07-13...
Page 66
Parameter Functions 08-11 Operation Frequency Inhibition 1 UP 08-12 Operation Frequency Inhibition 1 DOWN 08-13 Operation Frequency Inhibition 2 UP 08-14 Operation Frequency Inhibition 2 DOWN 08-15 Operation Frequency Inhibition 3 UP 08-16 Operation Frequency Inhibition 3 DOWN 08-17 Automatic Energy- saving 08-18 Automatic Voltage...
Page 67
Chapter 4 Parameters| Parameter Functions 09-05 Even/Odd Parity and Stopping Parity Setting 09-06 Communication Operation Command 1 09-07 Communication Frequency Setting 09-08 Communication Operation Command 2 4-16 Settings 00: None parity + 2 stop bit 01: Even parity + 2 stop bit 02: Odd parity + 2 stop bit 03: None parity + 1 stop bit 04: Even parity + 1 stop bit...
Page 68
Group 10 PID Control Parameters Parameter Functions 10-00 Input Terminal for PID Feedback 10-01 PID Control Detection Signal Reference 10-02 PID Feedback Control Method 10-03 Proportional Gain (P) 10-04 Integral Time (I) 10-05 Differential Time (D) 10-06 Upper Bound for Integral Control 10-07 Primary Low Pass...
Chapter 4 Parameters| 4.2 Parameter Settings for Applications Speed Search Applications Windmill, winding Restart free- machine, fan and all running motor inertia load DC Brake before Running Applications When e.g. windmills, Keep the free- fans and pumps rotate running motor at freely by wind or flow standstill.
Page 70
Overheat Warning Applications Air conditioner Safety measure Two-wire/three-wire Applications To run, stop, forward and General application reverse by external terminals Operation Command Applications Selecting the General application source of control signal Frequency Hold Applications Acceleration/ General application deceleration pause Auto Restart after Fault Applications For continuous and Air conditioners,...
Page 71
Chapter 4 Parameters| Emergency Stop by DC Brake Applications Emergency stop High-speed rotors without brake resistor Over-torque Setting Applications To protect Pumps, fans and machines and to extruders have continuous/ reliable operation Upper/Lower Limit Frequency Applications Control the motor Pump and fan speed within upper/lower limit Skip Frequency Setting...
Page 72
Output Signal during Running Applications Provide a signal for General application running status Output Signal in Zero Speed Applications Provide a signal for General application running status Output Signal at Master Frequency Applications Provide a signal for General application running status Output signal for Over-torque Applications To protect...
Page 73
Chapter 4 Parameters| Output Signal for Base Block Applications Provide a signal for General application running status Overheat Warning for Heat Sink Applications General application For safety Multi-function Analog Output Applications Display running General application status 4-22 Purpose When executing Base Block, a signal is sent by an external system or control wiring.
4.3 Description of Parameter Settings Group 0: User Parameters 00 - 00 Software Version This parameter displays the software version of AC drive. 00 - 01 AC Drive Status Indication 1 This parameter displays the AC drive status. Code AC Drive Status No fault occurred EF (external fault) occ (AC drive IGBT fault )
Page 75
Chapter 4 Parameters| Code AC Drive Status PHL (phase loss) Lc (Low Current) FbL(Feedback Loss) Reserved FANP FF123 FF12 FF13 FF23 35~40 Reserved HPF1 HPF2 HPF3 HPF4 CF3.3 CF3.4 CF3.5 CF3.6 CF3.7 CF3.8 00 - 02 AC Drive Status Indication 2 Display Bit 0~1: 00: Run LED is off and stop led is on.
Page 76
Bit 8: Master frequency source via communication interface Bit 9: Master frequency source via analog Bit10: Running command via communication interface Bit11: Parameter locked Bit12~15: Reserved 00 - 03 Frequency Setting (F) or Closed Loop Control Setting Point This parameter displays the frequency command set by the user. 00 - 04 Output Frequency (H) This parameter displays actual output frequency of the AC drive.
Page 77
Chapter 4 Parameters| 00 - 10 Feedback Signal Actual Value This parameter displays feedback signal value. 00 - 11 Feedback Signal (%) This parameter displays feedback signal value(%). 00 - 12 User Target Value (Low bit) uL 0-99.99 00 - 13 User Target Value (High bit) uH 0-9999 User Target Value = Actual output frequency (0-04) ×...
Page 78
Group 1: Basic Parameters 01 - 00 Maximum Output Frequency Settings 50.00~160.00Hz This parameter determines the AC drives maximum output frequency. All master frequency commands set by the keypad or analog inputs are limited by this parameter. The analog commands (ACI1 and ACI2) may be scaled to correspond to the output frequency range. (Please refer to 04-05~04-12.) 01 - 01 Maximum Voltage Frequency (Base Frequency)
Page 79
Chapter 4 Parameters| 01 - 04 Mid-point Voltage Settings 0.2V~510.0V This parameter sets the Mid-point Voltage of the V/F curve. This parameter must meet the following argument. Pr.1-02 >= Pr.1-04 >= Pr.1-06. 01 - 05 Minimum Output Frequency Settings 0.10~20.00 Hz This parameter sets the Minimum Output Frequency of the AC drive.
Page 80
Output voltage 01-02 01-04 01-06 01-05 01 - 09 Acceleration Time 1 01 - 10 Deceleration Time 1 01 - 11 Acceleration Time 2 01 - 12 Deceleration Time 2 01 - 13 Acceleration Time 3 01 - 14 Deceleration Time 3 01 - 15 Acceleration Time 4 01 - 16...
Page 81
Chapter 4 Parameters| 01 - 19 JOG Frequency Settings 0.0 Hz~160.00 Hz When the JOG function is to be utilized, users need to use the multi-function input terminals (Pr. 04-00 to 04-03 set to 07) or the JOG key on keypad. Once a JOG command is initiated, the AC drive will accelerate from the Minimum Output Frequency (Pr.01-05) to the JOG frequency (Pr.01-19).
Page 82
Chapter 4 Parameters| A high resolution decreases the accel/decel time range as shown in the following chart. 01-23 Accel/Decel time unit Accel/Decel time range 1 Sec 1~36000 Sec 0.1 Sec 0.1~3600.0 Sec 0.01 Sec 0.01~360.00 Sec Revision July 2008, EG03, SW V1.06 4-31...
Page 83
Chapter 4 Parameters| Group 2: Operation Method Parameters 02 - 00 Source of Frequency Command Settings 00: via keypad 01: via analog input AI1 (10bit) 02: via analog input AI2 (10bit) 03: via RS485 serial communication (RJ-11) 04: via External Reference Settings: 00: Frequency command source is the keypad.
Page 84
Coast: The AC drive output instantly stops upon command and the motor free spins until it comes to a complete stop. External Fault may be enabled by the EF terminal or a Multi-Function terminal. Please refer to Pr.04-00 to 04-03. Frequency Output Frequency...
Page 85
Chapter 4 Parameters| 02 - 04 Forward/Reverse Enabled Settings 00: Forward/Reverse enabled 01: Reverse disabled 02: Forward disabled This parameter enables the direction of the AC drive. 02 - 05 2-wire/3-wire Operation Control Modes Settings 00: 2-wire (#1), FWD / STOP, REV / STOP 01: 2-wire (#2), RUN/STOP, FWD/REV 02: 3-wire operation This parameter sets the operation mode when operating by external terminals.
Page 86
02 - 07 Reserved 02 - 08 Start-up Display Selection Settings This parameter determines the display on keypad after each power up. To program this parameter the user must first generate a Hex value with the information above. Then using the Hex to Decimal conversion to find the corresponding Decimal value and enter it into this parameter.
Page 87
Chapter 4 Parameters| 02 - 10 User Defined Coefficient Settings 0.01~160.00 When this parameter is set, the “H “display value = actual output frequency of AC drive x 02- If output frequency of AC drive is 90Hz, set 02-10 to 2.5. When H LED lights, the value on the display is 225.00.
Page 88
Group 3: Output Function Parameters 03 - 00 Multi-function Output terminal 1 (Relay) Settings 00-21 Setting Functions Disabled Indication during operation Master frequency attained Zero Speed (including shutdown) Over-torque External Fault Low voltage detection Operation Mode indication Fault Indication Master Frequency Attained 1 Master Frequency Attained 2...
Page 89
Chapter 4 Parameters| Setting Functions PID feedback error indication Auto Running Command 1-Step Running Completed Auto Running Completed Auto Running Paused Standard relay specifications = 10A/250VAC or 12A/24VDC. Relay delay time is 5~10 msec. 03 - 01 Reserved Master Frequency Attained 1 03 - 02 Master Frequency Attained 2 03 - 03...
Page 90
03 - 04 DC Fan Control Settings 00: Fan runs on power up. 01: Fan begins upon a RUN command. Fan stops 1 minute after a STOP 02: Fan begins upon a RUN command. Fan stops after a STOP command 03: Fan is controlled by temperature.
Page 91
Chapter 4 Parameters| 03 - 09 Analog Output 2 Selection Settings 00: 0~20mA 01: 4~20mA This parameter selects the output range of Analog Output 2 (AFM2). 4-40 Factory Setting: 01 Revision July 2008, EG03, SW V1.06...
Page 93
Chapter 4 Parameters| Setting Functions PID disabled Run PLC Program Pause PLC Program 1st Output Frequency Gain (Pr.04-30) 2nd Output Frequency Gain (Pr.04-31) 3rd Output Frequency Gain (Pr.04-32) 04 - 04 Digital Input Terminal Response Time Settings 01~20 This parameter selects the response time of digital input terminals MI1 to MI4, EF and FWD. AC drive will scan the digital input terminals once every 2msec.
Page 94
04 - 09 Minimum AI2 Analog Input Settings 0 ~ 100% 04 - 10 Maximum AI2 Analog Input Settings 0 ~ 100% 04 - 11 Minimum Output that corresponds to AI2 Settings 0.0~100.0% 04 - 12 Maximum Output that corresponds to AI2 Settings 0.0~100.0% 04 - 13...
Page 95
Chapter 4 Parameters| 01-08 AI1 Gain AI2 Gain 04 - 23 Analog Input Delay AI1 04 - 24 Analog Input Delay AI2 Settings 0.00 ~ 10.00 Sec These parameters select the time constant for the analog input signal filter. A properly adjusted time constant may help filter noise on the analog input terminals.
Page 96
04 - 26 1st Analog Input Frequency Gain 04 - 27 2nd Analog Input Frequency Gain 04 - 28 3rd Analog Input Frequency Gain 04 - 29 4th Analog Input Frequency Gain Settings 0.00~160.00Hz These parameters divide output frequency into several sections. (Refer to Pr.04-22). 04 - 30 1st Output Frequency Gain 04 - 31...
Page 97
Chapter 4 Parameters| Group 5: Multi-step Speed Parameters 05 - 00 1st Step Speed Frequency 05 - 01 2nd Step Speed Frequency 05 - 02 3rd Step Speed Frequency 05 - 03 4th Step Speed Frequency 05 - 04 5th Step Speed Frequency 05 - 05 6th Step Speed Frequency 05 - 06...
Page 98
Example 1 (Pr.05-15 = 1): Execute one cycle of the PLC program. Its relative parameter settings are: Pr.05-00 to 05-14: 1st to 15th step speeds (sets the frequency of each step speed) Pr.04-00 to 04-03: Multi-Function Input Terminals (set one multi-function terminal as 32 - PLC auto-operation).
Page 99
Chapter 4 Parameters| Example 3 (Pr.05-15 = 3) Execute one cycle step by step: The example below shows how the PLC can perform one cycle at a time, within in a complete cycle. Each step will use the accel/decel times in Pr.01-09 to Pr.01-16. It should be noticed that the time each step spends at its intended frequency is diminished, due to the time spent during accel/decel.
Page 101
Chapter 4 Parameters| 05 - 17 Time Duration of 1st Step Speed 05 - 18 Time Duration of 2nd Step Speed 05 - 19 Time Duration of 3rd Step Speed 05 - 10 Time Duration of 4th Step Speed 05 - 21 Time Duration of 5th Step Speed 05 - 22 Time Duration of 6th Step Speed...
Page 102
1st step speed Multi-function Terminal Pr.04-00 to Pr.04-07 (MI1 to MI8 1) 2nd step speed Multi-function Terminal Pr.04-00 to Pr.04-07 (MI1 to MI8 2) 3rd step speed Multi-function Terminal Pr.04-00 to Pr.04-07 (MI1 to MI8 3) 4th step speed Multi-function Terminal Pr.04-00 to Pr.04-07 (MI1 to MI8 4) 05 - 32 Time Unit Settings...
Page 103
Chapter 4 Parameters| Group 6: Protection Function Parameters 06 - 00 Over-voltage Stall Prevention Settings 660.0V~820.0VDC 00: Disabled This parameter selects the voltage level for the Over-Voltage Stall Prevention function. During decelerations, the DC bus voltage may exceed its maximum allowable value due to motor regeneration.
Page 104
When the over-current stall prevention is activated, the acceleration time of the AC drive will be longer than the time set in Pr. 01-09. Over-current Stall Prevention during acceleration 06-01 06 - 02 Over-current Stall Prevention during operation Settings 20~250% This parameter selects the percentage of allowable over-current during operation before the stall prevention function is enabled.
Page 105
Chapter 4 Parameters| 06 - 03 Over-torque Detection Selection Settings 00: Over-torque detection disabled. 01: Over-torque detection enabled during constant speed operation (OL2), 02: Over-torque detection enabled during constant speed operation (OL2), 03: Over-torque detection enabled during operation (OL2), and operation 04: Over-torque detection enabled during constant speed operation (OL2), This parameter selects the Over-torque Detection operation.
Page 106
When Pr.6-06 is set for 1 or 2 and the output current exceeds Pr.7-02 for the time set in Pr.6- 07, the drive will fault with an OL1. The common electronic thermal reaction time (150% output current for 1 minute) is shown in the chart below.
Page 107
Chapter 4 Parameters| Settings 35~40 Reserved 4-56 No fault occurred Over-current (oc) Over-voltage (ov) Overheat (oH) Overload (oL) Overload1 (oL1) External fault (EF) IGBT protection (occ) CPU failure (CF3) Hardware protection failure (HPF) Over-current during acceleration (OcA) Current exceeds 2 times rated current during decel. (ocd) Current exceeds 2 times rated current during steady state operation (ocn) Ground fault (GFF)
Page 108
06 - 15 Parameter Reset Settings 00~65535 09: Reset parameters (50Hz, 380) 10: Reset parameters (60Hz, 440) This parameter resets all parameters to the factory setting. 06 - 16 Parameter Protection Password Input Settings 00~65535 This parameter allows the user to enter their password to unlock the Parameter Protection feature.
Page 109
Chapter 4 Parameters| Group 7: AC Drive and Motor Parameters 07 - 00 Identity Code of AC Drive Settings Display by model type This parameter displays the AC drive model code. This parameter is read-only. 07 - 01 Rated Current of AC Drive Settings Display by model type This parameter displays rated output current of the AC drive.
Page 110
07 - 03 No-load Current of Motor Settings 1~99% This parameter sets the no-load current of the motor. Pr.7-03 = (no load current / drive rated current) Example: If the rated current of the AC drive is 150A and no-load current of the motor is 40A, then Pr.7-03 should be set to 27%.
Page 111
Chapter 4 Parameters| 07 - 05 Rated Slip Frequency of Motor Settings 0.00~20.00Hz This parameter is to set rated slip of loaded motor. Users need to input rated rotation speed according to nameplate of loaded motor. If rated frequency of motor is 60Hz, number of motor poles is 4 and rated rotation speed of motor is 1650rpm.
Page 112
This parameter could display running time of the motor. 07 - 10 Electric Bill for One Time 07 - 11 Accumulated Electric Bill (per currency unit) 07 - 12 Accumulated Electric Bill (per 10 07 - 13 Electric Rate (per currency unit) Settings 0.01 to 655.35 You can get electric bill from Pr.
Page 113
Chapter 4 Parameters| Group 8: Special Parameters 08 - 00 DC Braking Current Level Settings 00~100% This parameter determines the level of DC braking current output. 08 - 01 DC Braking Time during Start-up Settings 0.0~60.0 Sec This parameter determines the duration of time that the DC braking current will be applied to the motor during the AC drive start-up.
Page 114
Output frequency DC braking current level Run/Stop 08 - 04 Momentary Power Loss Operation Selection Settings 00: Disabled 01: Trace from top downward 02: Trace from bottom upward This parameter determines the start-up mode after momentary power loss operation. The power system connects to AC drive may occurred momentary power loss by any probably reason.
Page 115
Chapter 4 Parameters| The allowable power loss time must in the condition that AC drive auxiliary power is working normally. If auxiliary power is turned off in the allowable power loss time, the actual allowable power loss time will be shorter than the parameter setting. 08 - 06 Speed Search Time Settings...
Page 116
Master frequency command 08-07 Output voltage 08 - 08 BB Speed Search Method Settings 00: Trace from top downward 01: Trace from bottom upward This parameter determines BB speed search method when multi-function input terminal 04-00 to 04-03 is set to BB External interrupt (11 or 12) and activates. BB speed search method is the same with restart speed search after momentary loss power.
Page 117
Chapter 4 Parameters| 08 - 10 Auto Restart Time after Fault Settings 00 to 60000 sec This parameter determines auto restart time after fault. After fault occurs and restart, there is no fault occurs during 08-10 setting time, AC drive will reset fault occurred record to zero. 08 - 11 Operation Frequency Inhibition 1 UP 08 - 12...
Page 118
100% 08 - 18 Automatic Voltage Regulation (AVR) Settings 00: AVR function enabled 01: AVR function disabled 02: AVR function disabled for deceleration This parameter determines the function of Automatic Voltage Regulation is enabled or disabled. This parameter is set to 01: when AVR function is disabled, AC drive will calculate input voltage by DC Bus value (620VDC).
Page 119
Chapter 4 Parameters| 08 - 20 Vibration Compensation Factor Settings 00~1000 This parameter will minimize vibration at low speed during vector control. The value of the parameter is a GAIN. The higher the value, the more vibration dampening that will occur. 4-68 Unit: 1 Factory Setting: 00...
Page 120
Group 9: Communication Parameters 09 - 00 Communication Address Settings 01-254 00: Disabled If the AC drive is controlled by RS-485 serial communication, the communication address for this drive must be set via this parameter. 09 - 01 Transmission Speed (Baud Rate) Settings 00: Baud rate 4800 01: Baud rate 9600...
Page 121
Chapter 4 Parameters| 09 - 05 Even/Odd Parity and Stopping Parity Setting Settings 00: None parity + 2 stop bit 01: Even parity + 2 stop bit 02: Odd parity + 2 stop bit 03: None parity + 1 stop bit 04: Even parity + 1 stop bit 05: Odd parity + 1 stop bit This parameter determines the communication format of serial communication.
Page 122
This parameter can be set by communication settings. It can’t be set by keypad. 09 - 07 Communication Frequency Setting Settings 0~160.00Hz This parameter can be set by communication settings. It can’t be set by keypad. 09 - 08 Communication Operation Command 2 Settings Bit0: 1: EF ON Bit1: 1: Reset...
Page 123
Chapter 4 Parameters| Character ‘0’ ASCII Code Character ‘8’ ASCII Code RTU mode: Each 8-bit is the combination of two 4-bit hexadecimal characters. For example, 64 Hex. Data format 2.1 10-bit character frame (for 7-bit): (7, N, 2: 9-04=0, 9-05=0) Start (7, E, 1: 9-04=0, 9-05=04) Start...
Page 124
(8 , E , 1 : 9-04=1 or 2, 9-05=04) Start (8, O, 1: 9-04=1 or 2, 9-05=05) Start Communication Protocol 3.1 Communication Data Frame: ASCII mode: ADR 1 ADR 0 CMD 1 CMD 0 DATA (n-1) ……. DATA 0 LRC CHK 1 LRC CHK 0 END 1...
Page 125
Chapter 4 Parameters| 3.2 ADR (communication address) Valid communication addresses are in the range of 0 to 254. a communication address equal to 0, means broadcast to all AC drives (AMD). In this case, the AMD will not reply any message to the master device.
Page 126
RTU mode: Command message: Starting data address Number of data (Word) CRC CHK Low CRC CHK High ● Command code: 06H, write a word For example, writing 6000(1770H) to address 0100H of AMD with address 01H. ASCII mode: Command message: ADR 1 ADR 0 CMD 1...
Page 127
Chapter 4 Parameters| RTU mode: Command message: data Starting address data CRC CHK LOW CRC CHK HIGH ● Command code: 08H, loop detection This command is used to test the communication condition between master control equipment (usually is PC or PLC) and AC drive. AC drive will deliver the data that received from AC drive to master control equipment.
Page 128
RTU mode: Command message: data Starting address data CRC CHK LOW CRC CHK HIGH ● Command code: 10H, write continuous words For example, modify multi-step speed setting of AC drive (address 01H) 05-00=50.00(1388H),05-01=40.00(0FA0H) ASCII mode: Command message: ADR 1 ADR 0 CMD 1 CMD 0 Data...
Page 129
Chapter 4 Parameters| LRC CHK 1 LRC CHK 0 END 1 END 0 RTU mode: Command message: Data starting address Number of data (Word) Number of data (Byte) The first data The second data CRC CHK LOW CRC CHK HIGH 3.4 CHK (check sum) ASCII mode: LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the...
Page 130
01H+03H+04H+01H+00H+01H=0AH, 2’s complement of 0AH is F6H. RTU mode: RTU mode uses CRC (Cyclical Redundancy Check) detect value. CRC (Cyclical Redundancy Check) is calculated by the following steps: Step 1: Load a 16-bit register (called CRC register) with FFFFH. Step 2: Excusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit CRC register, putting the result in the CRC register.
Page 131
Chapter 4 Parameters| The following is an example of CRC generation using C language. The function takes two arguments: Unsigned char* data Unsigned char length The function returns the CRC values as a type of unsigned integer. unsigned int crc_chk(unsigned char* data, unsigned char length){ int j;...
Page 132
3.5 Address list: The contents of available addresses are shown as below: Content Address AC drive GGnnH Parameters Command Write only Revision July 2008, EG03, SW V1.06 GG means parameter group, nn means parameter number, for example, the address of Pr 04-01 is 0401H. Refer to chapter 5 for the function of each parameter.
Page 133
Chapter 4 Parameters| Content Address Status monitor 2100H Read only 4-82 Function Fault code: 00: No error occurred 01: Over-current (oc) 02: Over-voltage (ov) 03: Overheat (oH) 04: Overload (oL) 05: Overload1 (oL1) 06: External fault (EF) 07: IGBT short circuit protection (occ) 08: CPU failure (cF3) 09: Hardware protection failure (HPF) 10: Current exceeds 2 times rated current during accel (ocA)
Page 134
Content Address Status monitor Read only Revision July 2008, EG03, SW V1.06 35~40: Reserved 41: GFF hardware error (HPF1) 42: CC,OC hardware error (HPF2) 43: OC hardware error (HPF3) 44: OV hardware error (HPF4) 45: U-phase error (CF3.3) 46: V-phase error (CF3.4) 47: W-phase error (CF3.5) 48: OV or LV (CF3.6) 49: Isum error (CF3.7)
Page 135
Chapter 4 Parameters| Content Address 2108H 2109H 210AH 210BH 210CH 210DH 210EH 210FH 3.6 Exception response: The AC drive is expected to return a normal response after receiving command messages from the master device. The following depicts the conditions that no normal response is replied to the master device.
Page 136
The explanation of exception codes: Exception code Illegal command code: The command code received in the command message is not available for the AC drive. Illegal data address: The data address received in the command message is not available for the AC drive. Illegal data value: The data value received in the command message is not available for the AC drive.
Page 137
Chapter 4 Parameters| Group 10: PID Control Parameters 10 - 00 Input Terminal for PID Feedback Settings 00: Disabled 01: Input via AI1 02: Input via AI2 03: Input via External Reference This parameter is to set the source of PID control feedback signal. The source could be AI1, AI2 or external reference that defined by 04-20.
Page 138
When this parameter is set to 01: when positive control, the deviation equation is deviation = detection signal - target value. When increasing output frequency will decrease detection value, this setting should be chose. 10 - 03 Proportional Gain (P) Settings 0.0~10.0 This parameter is to set proportional gain (P).
Page 139
Chapter 4 Parameters| 10 - 07 Primary Low Pass Filter Time Settings 0.0~2.5 Sec This parameter determines primary Low Pass filter time. Output frequency of PID controller will filter by primary low pass function. This function could decrease change of output frequency. A long primary low pass time means filter degree is high and vice versa.
Page 140
This parameter is to set V/F curve. If this parameter isn’t set to 00, parameter 01-03 and 01-04 will disable. Input current of the motor could divide into two orthogonal vectors: magnetic vector and torque vector. Gap flux, which is produced by Magnetic vector, is in direct proportion with output voltage of motor.
Page 141
Chapter 4 Parameters| This page intentionally left blank. 4-90 Revision July 2008, EG03, SW V1.06...
5.1 Over Current (OC) Remove short c ircuit or groun d fault Reduce the load or increase the power of AC motor drive N o Reduce tor que compen sation Red uce tor que com pensa tion Maybe AC motor dri ve has malfunction or error due to noise.
Chapter 5 Troubleshooting | 5.2 Ground Fault Ground fault 5.3 Over Voltage (OV) Reduce voltage to be within spec. Maybe AC motor drive has malfunction or misoperation due to noise. Please contact DELTA. Reduce moment of inertia Need to check control method. Please contact DELTA. Is output circuit(cable or motor) of AC motor drive grounded?
DELTA. Revision July 2008, EG03, SW V1.06 Change defective component and check connection Make necessary corrections, such as change power supply system for requirement Using the different power supply for this drive and heavy load system Maybe AC motor drive has malfunction.
Chapter 5 Troubleshooting | 5.5 Over Heat (OH) AC motor drive overheats Heat sink overheats Check if temperature of heat sink is greater than 90 Is load too large If cooling fan functions normally Check if cooling fan is jammed Check if surrounding temperature is within specification Adjust surrounding temperature...
5.7 Keypad Display is Abnormal Abnormal display or no display Cycle power to AC motor drive Display normal? AC motor drive works normally 5.8 Phase Loss (PHL) Check wiring at R, S and T terminals Check if the screws of terminals are tightened Check if the input voltage of R, S, T is unbalanced Maybe AC motor drive has malfunction or misoperation due to noise.
Chapter 5 Troubleshooting | 5.9 Motor cannot Run Motor cannot run Reset after clearing fault and then RUN It can run when no faults occur Press RUN key to check if it can run Press UP key to set frequency Check if input FWD or REV command Press UP to...
5.10 Motor Speed cannot be Changed Modify the setting If the setting of Pr.05-17toPr.05-31 is too high If finished with executing Pr.05-15 If the setting of Pr.05-00 to Pr.05-14 are the same Revision July 2008, EG03, SW V1.06 Motor can run but cannot change speed Check if the setting of the max.
Chapter 5 Troubleshooting | 5.11 Motor Stalls during Acceleration Motor stalls during acceleration Thicken or shorten the wiring between the motor and AC motor drive Reduce load or increase the capacity of AC motor drive 5.12 The Motor does not Run as Expected Motor does not run as expected Run in low speed continuously...
5.13 Electromagnetic/Induction Noise There are many noises surround the AC motor drives and invade it by radiation or power circuit. It may cause the misoperation of control circuit and even damage the AC motor drive. Of course, that is a solution to increase the noise tolerance of AC motor drive. But it is not the best one due to the limit. Therefore, solve it from the outside as following will be the best.
Chapter 5 Troubleshooting | 5.15 Affecting Other Machines AC motor drive may affect the operation of other machine due to many reasons. The solutions are as follows. High Harmonic at Power Side If there is high harmonic at power side during running, the improved methods are: Separate power system: use transformer for AC motor drive.
Chapter 6 Fault Code Information and Maintenance 6.1 Fault Code Information The AC motor drive has a comprehensive fault diagnostic system that includes several different alarms and fault messages. Once a fault is detected, the corresponding protective functions will be activated.
Page 153
Chapter 6 Fault Code Information and Maintenance | Fault Fault Descriptions Name The AC drive temperature sensor detects excessive heat. The AC drive detects that the DC bus voltage has fallen below its minimum value. The AC drive detects excessive drive output current.
Page 154
Fault Fault Descriptions Name Over-current during deceleration: 1. Short-circuit at motor output. 2. Deceleration time too short. 3. AC drive output capacity is too small. Over-current during steady state operation: 1. Short-circuit at motor output. 2. Sudden increase in motor loading.
Page 155
Chapter 6 Fault Code Information and Maintenance | Fault Fault Descriptions Name Feedback Loss GFF hardware error CC (current clamp) OC hardware error OV hardware error Internal memory IC cannot be programmed. Internal memory IC cannot be read. U-phase error V-phase error W-phase error OV or LV...
6.1.2 Reset There are three methods to reset the AC motor drive after solving the fault: STOP RESET Press key on the digital keypad PU01. Set external terminal to “RESET” (set one of Pr.04-00~Pr.04-03 to 05) and then set to be Send “RESET”...
Page 157
Chapter 6 Fault Code Information and Maintenance | DANGER! Disconnect AC power before processing! Only qualified personnel can install, wire and maintain AC motor drives. Please take off any metal objects, such as watches and rings, before operation. And only insulated tools are allowed.
Page 158
Keypad Check Items Is the display clear for reading? Any missing characters? Mechanical parts Check Items If there is any abnormal sound or vibration If there are any loose screws If any part is deformed or damaged If there is any color change by overheating If there is any dust or dirt Main circuit...
Page 159
Chapter 6 Fault Code Information and Maintenance | Terminals and wiring of main circuit Check Items If the wiring shows change of color change or deformation due to overheat If the insulation of wiring is damaged or the color has changed If there is any damage DC capacity of main circuit...
Page 160
Transformer and reactor of main circuit Check Items If there is any abnormal vibration or peculiar smell Magnetic contactor and relay of main circuit Check Items If there are any loose screws If the contact works correctly Printed circuit board and connector of main circuit Check Items If there are any loose screws and connectors...
Page 161
Chapter 6 Fault Code Information and Maintenance | Cooling fan of cooling system Check Items If there is any abnormal sound or vibration If there is any loose screw If there is any change of color due to overheating Ventilation channel of cooling system Check Items If there is any obstruction in the heat sink, air intake or air outlet...
Voltage Class Model Number VFD- G43X 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600 1850 2200 Max. Applicable Motor Output 5.5 7.5 (kW) Max. Applicable Motor Output 7.5 10 (HP) Rated Output Capacity (KVA) 10 Rated Output Current (A)
Page 163
Appendix A Specifications| AVR, 2 types of S-Curve, Over-Voltage, Over-Current Stall Prevention, Fault Records, Reverse inhibition, DC Braking, Momentary Power Loss restart, Auto torque and slip Other Functions compensation, PID Control, Parameter Lock/Reset, Frequency Limits, Adjustable Carrier Frequency Self-testing, Over Voltage, Over Current, Under Voltage, Overload, Overheating, Protection External Fault, Electronic thermal, Ground Fault, Phase-loss Cooling Methods...
B.1 All Brake Resistors & Brake Units Used in AC Motor Drives Note: Please only use DELTA resistors and recommended values. Other resistors and values will void Delta’s warranty. Please contact your nearest Delta representative for use of special resistors. For instance, in 460 V series, 100 HP, AC drive has 2 brake units with total of 16 brake resistors, so each brake unit uses 8 brake resistors.
Page 165
Appendix B Accessories| NOTE Please select the brake unit and/or brake resistor according to the table. “-“ means no Delta product. Please use the brake unit according to the Equivalent Resistor Value. ‘’*’’ means it is under development. If damage to the drive or other equipment is due to the fact that the brake resistors and the brake modules in use are not provided by Delta, the warranty will be void.
Page 166
R/L1 S/L2 T/L3 O.L. Thermal Overload Relay or Surge temperature Absorber switch Note1: When using the AC drive with DC reactor, please refer to wiring diagram in the AC drive user manual for the wiring of terminal +(P) of Brake unit. Note2: Do NOT wire terminal -(N) to the neutral point of power system.
Appendix B Accessories| B.2 Non-fuse Circuit Breaker Chart The fuse should comply with UL248 and the breaker should comply with UL489. The current rating of the breaker shall be 2~4 times maximum output current rating. (Refer to Appendix A for rated input/output current) Model VFD055F43B-G VFD075F43B-G...
B.3 Fuse Specification Chart Smaller fuses than those shown in the table are permitted. Model VFD055F43B-G VFD075F43B-G VFD110F43A-G VFD150F43A-G VFD185F43A-G VFD220F43A-G VFD300F43A-G VFD370F43A-G VFD450F43A-G VFD550F43A-G VFD750F43A-G VFD900F43C-G VFD1100F43C-G VFD1320F43A-G VFD1600F43A-G VFD1850F43A-G VFD2200F43A-G Revision July 2008, EG03, SW V1.06 I (A) I (A) Input Output...
Appendix B Accessories| B.4.3 Applications Connected in input circuit Application 1 When more than one AC motor drive is connected to the same mains power, and one of them is ON during operation. Correct wiring Application 2 Silicon rectifier and AC motor drive are connected to the same power.
Page 172
Application 3 Used to improve the input power factor, to reduce harmonics and provide protection from AC line disturbances (surges, switching spikes, short interruptions, etc.). The AC line reactor should be installed when the power supply capacity is 500kVA or more and exceeds 6 times the inverter capacity, or the mains wiring distance Correct wiring...
Appendix B Accessories| B.5 Zero Phase Reactor (RF220X00A) Dimensions are in millimeter and (inch) Recommended Wire Cable Size type Nominal (Note) AWG mm ≦10 ≦5.3 ≦5.5 Single- core ≦2 ≦33.6 ≦38 ≦12 ≦3.3 ≦3.5 Three- core ≦1 ≦42.4 ≦50 Note: 600V Insulated unshielded Cable. Diagram A Please wind each wire 4 times around the core.
B.6 PU06 B.6.1 Description of the Digital Keypad VFD-PU06 Frequency Command Status indicator Output Frequency Status indicator User Defined Units Status indicator By pressing JOG key, Jog frequency operation. UP and DOWN Key Set the parameter number and changes the numerical data, such as Master Frequency.
Appendix B Accessories| Display Message The actual value stored in the specified parameter. External Fault “End” displays for approximately 1 second if the entered input data have been accepted. After a parameter value has been set, the new value is automatically stored in memory. To modify an entry, use the “Err”...
Continuous operation, Short-time operation Long-time operation at medium/low speeds Maximum output current (instantaneous) Constant output current (continuous) Maximum frequency, Base frequency Power supply transformer capacity or percentage impedance Voltage fluctuations and unbalance Number of phases, single phase protection Frequency Mechanical friction, losses in wiring Duty cycle modification Revision July 2008, EG03, SW V1.06...
Appendix C How to Select the Right AC Motor Drive| C.1 Capacity Formulas 1. When one AC motor drive operates one motor The starting capacity should be less than 1.5x rated capacity of AC motor drive The starting capacity= ⎛ ×...
Page 178
Symbol explanation : Motor shaft output for load (kW) : Motor efficiency (normally, approx. 0.85) η ϕ : Motor power factor (normally, approx. 0.75) : Motor rated voltage(V) : Motor rated current(A), for commercial power : Correction factor calculated from current distortion factor (1.05 - 1.1, depending on PWM method) : Continuous motor capacity (kVA) P : Starting current/rated current of motor...
Appendix C How to Select the Right AC Motor Drive| C.2 General Precaution Selection Note When the AC Motor Drive is connected directly to a large-capacity power transformer (600kVA or above) or when a phase lead capacitor is switched, excess peak currents may occur in the power input circuit and the converter section may be damaged.
If the stall prevention function is activated, the accel./decel. time is automatically extended to a length that the AC Motor Drive can handle. If the motor needs to decelerate within a certain time with high load inertia that can’t be handled by the AC Motor Drive in the required time, either use an external brake resistor and/or brake unit, depending on the model, (to shorten deceleration time only) or increase the capacity for both the motor and the AC Motor Drive.
Page 181
Appendix C How to Select the Right AC Motor Drive| Motor torque characteristics vary when an AC Motor Drive instead of commercial power supply drives the motor. Check the load torque characteristics of the machine to be connected. Because of the high carrier frequency PWM control of the VFD series, pay attention to the following motor vibration problems: Resonant mechanical vibration: anti-vibration (damping) rubbers should be used to mount equipment that runs at varying speed.
Page 182
Synchronous motor: The rated current and starting current are higher than for standard motors. Please check before operation and choose the capacity of the AC motor drive carefully. When the AC motor drive operates more than one motor, please pay attention to starting and changing the motor.
Page 183
Appendix C How to Select the Right AC Motor Drive| This page intentionally left blank. Revision July 2008, EG03, SW V1.06...
Need help?
Do you have a question about the AC Motor Drive VFD-G and is the answer not in the manual?
Questions and answers