CONSTRUCTION SITES
Continuously switching of the mains power supply that is connected to emergency light fittings during the construction phase of an
installation will cause these fittings to discharge and charge their batteries many times over a short period; this can shorten the life of the
battery. Thomas & Betts does not recommend such practices and may not honour the warranty on batteries when they are subjected
to such harsh operating conditions. Emergency light fittings are designed to be discharge tested once every 6 months as per AS/
NZS2293.2, subjecting the product to repeated discharge or charge cycles is regarded as an abuse of the fittings.
TROUBLE SHOOTING GUIDE
If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the following table
as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes from the right column.
#
Fault
1
LED light source and indicating LED not lit
2
LED light source is lit but indicating LED not lit
3
LED light source does not switch to emergency mode
when the test button is pressed
4
LED light source works momentarily on emergency when
the test button is pressed
If the unit still does not work after checking these possible causes, contact Thomas & Betts Service in Australia on 1300 666 595, Monday
to Friday, 8.30am to 4.30pm (AEST) and ask for help. Our trained service personnel will usually be able to take your call immediately and
assist you in resolving your difficulty. Thomas & Betts is committed to providing valuable Through-Life Support for its products.
© Thomas & Betts (Australasia) Pty. Ltd. 2015
STANILITE
Possible Causes
AC supply not connected; or
AC supply turned off; or
Test switch damaged
Test switch damaged; or
Battery not connected or faulty
Test switch damaged; or
Battery not connected or faulty
Battery not yet charged (allow up to 24 hours)
Rev: 6.0
2 November 2015
Complete Solutions in Emergency Lighting
Thomas & Betts (Australasia) Pty. Ltd. ABN: 062 074 810 898
Head Office: Unit D3, 3-29 Birnie Avenue, Lidcombe NSW 2141, Australia
Manufacturing: 23a Nyrang Street, Lidcombe NSW 2141, Australia
Phone: 1300 666 595 Fax: 1300 666 594 Email: austsales@tnb.com Website: www.tnbaust.com
LED Spitfire Recessed
Standard, Nexus LX, Nexus RF
This Document Covers
What's Inside the box
Safety Warning
Lamp Head Assembly
Installation Instructions
Battery and Control Pack
Removal Instructions
Accessory Kit
Testing Precautions
Installation Manual
Trouble Shooting Guide
Warranty Information
GREETINGS
Congratulations on choosing to use this Thomas & Betts product covered by our unique Through-Life Support system. This document is
designed to assist you during the installation of this product; for the safety of yourself and others Thomas & Betts recommends
that you read this document thoroughly before commencing installation. The fittings are designed for easy
installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through regular and
appropriate servicing, will perform reliably for many years to come.
SAFETY WARNING
In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 Volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000, AS/NZS2293).
Refer to the applicable standards for data and mains cabling installation procedures and requirements.
Important Note: This product is designed for indoor use only
NEXUS LX (DATA CABLE SYSTEM)
The Nexus range of emergency light fitting are designed to be connected together into a special communication network over a Level
4 (or higher) high speed, single twisted pair data cable. The Nexus LX User & Technical Guide describes all you need to know to
successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your nearest Thomas & Betts product
supplier. The network cabling of the building must be installed as per the procedure detailed in the Nexus LX User & Technical Guide. No
mains or mains carrying cables are to be connected to the data terminals or cables.
NEXUS RF (WIRELESS SYSTEM)
The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical installation of the
fittings is identical to that of a standard non-monitored fitting.
4
© Thomas & Betts (Australasia) Pty. Ltd. 2015
Installation Manual
STANILITE
Doc No: 29-01095
Rev: 6.0
2 November 2015
1

Advertisement

loading

Summary of Contents for ABB Thomas & Betts Standard

  • Page 1 Complete Solutions in Emergency Lighting STANILITE Complete Solutions in Emergency Lighting STANILITE Doc No: 29-01095 CONSTRUCTION SITES Continuously switching of the mains power supply that is connected to emergency light fittings during the construction phase of an installation will cause these fittings to discharge and charge their batteries many times over a short period; this can shorten the life of the battery.
  • Page 2 Complete Solutions in Emergency Lighting STANILITE Complete Solutions in Emergency Lighting STANILITE INSTALLATION INSTRUCTIONS Fitting Type LED State - on initial powering - no fitting faults Remove the unit from the packing box and inspect it for damage or imperfections. If any damage is found, do not install the unit, Non-monitored Solid red but replace it carefully into the packing box and notify the Thomas &...

This manual is also suitable for:

Thomas & betts nexus lxThomas & betts nexus rf