TROUBLE SHOOTING GUIDE
If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the following table
as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes from the right column.
#
Fault
1
Lamp and LED not lit
2
Lamp not lit but LED is lit
3
Lamp is lit but LED not lit
4
The lamp does not switch to emergency mode when the
test button is pressed
5
The lamp works momentarily on emergency when the test
button is pressed
If the unit still does not work after checking these possible causes, contact Thomas & Betts Service in Australia on 1300 666 595, Monday
to Friday, 8.30am to 4.30pm (AEST) and ask for help. Our trained service personnel will usually be able to take your call immediately and
assist you in resolving your difficulty. Thomas & Betts is committed to providing valuable Through-Life Support for its products.
© Thomas & Betts (Australasia) Pty. Ltd. 2016
STANILITE
Possible Causes
AC mains supply not connected; or
AC mains supply turned off; or
Unit not inserted into the base properly; or
Test switch damaged
Lamp damaged; or
Lamp incorrectly inserted
Test switch damaged; or
Battery not connected
Test switch damaged
Battery not yet charged (allow up to 16 hours)
Rev: 2.0
24 February 2016
Complete Solutions in Emergency Lighting
Thomas & Betts (Australasia) Pty. Ltd. ABN: 062 074 810 898
Head Office: Unit D3, 3-29 Birnie Avenue, Lidcombe NSW 2141, Australia
Manufacturing: 23a Nyrang Street, Lidcombe NSW 2141, Australia
Phone: 1300 666 595 Fax: 1300 666 594 Email: austsales@tnb.com Website: www.tnbaust.com
LED Quickfit Vandal Resistant Jumbo Exit
Standard, Nexus LX, Nexus RF
This Document Covers
What's Inside the box
Safety Warning
Main Frame
Installation Instructions
Diffusers
Removal Instructions
Ceiling Bracket
Testing Precautions
Hole Plug Set (6 Pieces)
Trouble Shooting Guide
Installation Manual
Warranty Information
GREETINGS
Congratulations on choosing to use this Thomas & Betts product covered by our unique Through-Life Support system. This document is
designed to assist you during the installation of this product; for the safety of yourself and others Thomas & Betts recommends
that you read this document thoroughly before commencing installation. The fittings are designed for easy
installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through regular and
appropriate servicing, will perform reliably for many years to come.
SAFETY WARNING
In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 Volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000, AS/NZS2293).
Refer to the applicable standards for data and mains cabling installation procedures and requirements.
Important Note: This product is designed for indoor use only.
NEXUS LX (DATA CABLE SYSTEM)
The Nexus range of emergency light fitting are designed to be connected together into a special communication network over a Level
4 (or higher) high speed, single twisted pair data cable. The Nexus LX User & Technical Guide describes all you need to know to
successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your nearest Thomas & Betts product
supplier. The network cabling of the building must be installed as per the procedure detailed in the Nexus LX User & Technical Guide. No
mains or mains carrying cables are to be connected to the data terminals or cables.
NEXUS RF (WIRELESS SYSTEM)
The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical installation of the
fittings is identical to that of a standard non-monitored fitting.
4
© Thomas & Betts (Australasia) Pty. Ltd. 2016
Installation Manual
STANILITE
Doc No: 29-99569
Rev: 2.0
24 February 2016
1

Advertisement

loading

Summary of Contents for ABB Thomas & Betts Standard

  • Page 1 Complete Solutions in Emergency Lighting STANILITE Complete Solutions in Emergency Lighting STANILITE Doc No: 29-99569 TROUBLE SHOOTING GUIDE If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the following table as a guide to fixing the problem.
  • Page 2 Complete Solutions in Emergency Lighting STANILITE Complete Solutions in Emergency Lighting STANILITE INSTALLATION INSTRUCTIONS Fit the LED lamp (carefully follow the instruction label on top of the Quickfit unit) and attach the Quickfit unit to the mounting bracket by aligning the top left hand end of the unit (the end without the protruding electrical connecting metal lugs) with the large cut-away slot towards the left hand end of the bracket.

This manual is also suitable for:

Thomas & betts nexus lxThomas & betts nexus rf